M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-16 00:00:00 | GAS PERMIT FOR THE GENERATOR 05080022 | | | | | | SITE PLAN INDICATES GENERATOR 3 FT FROM | | | THE BUILDING.PER 2001 FBC(M)804.3.5 | | | ITEM #6, EXHAUST TERMINATION SHALL BE A | | | MINIMUM OF 3 FT HORIZONTALLY FROM ANY | | | PORTION OF THE ROOF STRUCTURE.SHOW | | | COMPLIANCE WITH 2001 FBC(M)804.3.3 | | | THROUGH 804.3.5. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|