| 2005-08-27 00:00:00 | PAUL SCHMITZ, PLUMBING PLAN REVIEW |
| | EXAMINER561-805-6692 |
| | [email protected] |
| | FBC 2001 |
| | DENIED |
| | |
| | |
| | |
| | 1. IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT OR ENGINEER, THEN HE/SHE SHALL |
| | AFFIX HIS/HER OFFICIAL SEAL.SECTION |
| | 104.2.12. |
| | 2. PLANS FOR REVIEW SHALL BE ROUTED TO |
| | DBPR HOTEL AND RESTURANT DIVISION FOR |
| | REVIEW PRIOR TO BEING SUBMITTED TO THE |
| | CITY WPB FOR PLAN REVIEW. MINIMUM OF TWO |
| | SETS OF PLANS STAMPED BY DBPR WITH THE |
| | TWO PAGE "WORKSHEETS" ATTACHED TO BE |
| | SUBMITTED. SECTION 101.4.7. |
| | 3. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | THE UTILITY DEPT. PLEASE CONTACT LYNN |
| | MASSON ENVIRONMENTAL COMPLIANCE. (561) |
| | 822-2271, FAX (561) 822-2279 OR E-MAIL |
| | [email protected]. WASTE ORD #3434. - MOP |
| | SINK SHALL CONNECT TO THE GREASE SYSTEM |
| | AND THE SAMPLE POINT SHALL BE LOCATED |
| | DOWNSTREAM OF THE LAST FIXTURE IN THE |
| | GREASE WASTE SYSTEM. |
| | 4. SHT 3.0P GREASE TRAP UNDER SINK IN |
| | FOOD PREP AREA IS NOT APPROVED. DELETE |
| | FROM PLANS. |
| | 5. SHT 3.0P WATER RISER DIAGRAM FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER |
| | DOWN FEED PIPES. SECTION 606.1(4) |
| | WATER HAMMER ARRESTORS AS REQUIRED ON |
| | RISER. - WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. |
| | 6. SHT 3.0P EQUIPMENT SCHEDULE DOES NOT |
| | REFLECT THE FLOOR PLAN. SEE ITEM #1. - |
| | SHOULD READ 3 COMPARTMENT SINK. ITEM #14 |
| | SHOULD READ MOP SINK. |
| | SECTION 104.2.1. |
| | 7. SHT 3.0PPLUMBING NOTES #8, DOES |
| | NOT COMPLY WITH TABLE 704.1. 2-1/2"AND |
| | SMALLER PIPE SHALL BE PITCHED AT |
| | 1/4"/FT. - NOTE #11 "L" COPPER REQUIRED |
| | UNDER THE SLAB. M SOFT ROLL NOT |
| | MANUFACTURED AND NO JOINTS FOR COPPER |
| | ARE APPROVED UNDER THE SLAB. - NOTE #12 |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | REFERENCE FROM NOTE. SECTION 604.9 |
| | 8. SHOW THE FOLLOWING INFORMATION TO |
| | INDICATE COMPLIANCE: |
| | FOR THE URINAL: |
| | A. 11-4.18.4 CONTROLS, HEGHT. |
| | FOR THE LAVS: |
| | B. 11-4.19.5 FAUCETS |
| | 9. SEE PERMIT #05071211 FOR GAS PERMIT |
| | REQUIRMENTS. |
| | END OF COMMENTS |
| | |