| Date |
Text |
| 2005-07-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. NOTICE OF COMMENCEMENT REQUIRED. |
| | 2. CHANGE OF OCCUPANCY - SPACE SHALL |
| | COMPLY WITH ALL FBC-2001 CODE |
| | REQUIREMENTS. SECTION 34. |
| | 3. APPLICATION REQUIRES A DETAILED |
| | DISCRIPTION OF WORK. |
| | 4. IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT OR ENGINEER, THEN HE/SHE SHALL |
| | AFFIX HIS/HER OFFICIAL SEAL.SECTION |
| | 104.2.12. |
| | 5. PLANS FOR REVIEW SHALL BE ROUTED TO |
| | DBPR HOTEL AND RESTURANT DIVISION FOR |
| | REVIEW PRIOR TO BEING SUBMITTED TO THE |
| | CITY WPB FOR PLAN REVIEW. MINIMUM OF TWO |
| | SETS OF PLANS STAMPED BY DBPR WITH THE |
| | TWO PAGE "WORKSHEETS" ATTACHED TO BE |
| | SUBMITTED. SECTION 101.4.7. |
| | 6. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | THE UTILITY DEPT. PLEASE CONTACT LYNN |
| | MASSON ENVIRONMENTAL COMPLIANCE. (561) |
| | 822-2271, FAX (561) 822-2279 OR E-MAIL |
| | [email protected]. WASTE ORD #3434. |
| | 7. SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES. SHOW ALL SEATING AND |
| | INDICATE IF SEATING IS FIXED OR NOT PER |
| | TABLE 1003.1 AND 403.1 - FOR THE |
| | PURPOSES OF CALCULATING THE MINIMUM |
| | NUMBER OF REQUIRED PLUMBING FACILITIES, |
| | THE REQUIREMENTS OF TABLE 403.1 SHALL |
| | APPLY TO ANY AREAS OUTSIDE OF THE |
| | BUILDING THAT ARE USED AS PART OF THE |
| | BUILDING'S DESIGNATED OCCUPANCY. SECTION |
| | 403.1 WHERE ADDITIONAL SEATING IS ALSO |
| | UTILIZED IN THESE AREAS, THE ACTUAL |
| | NUMBER OF SEATS SHALL BE ADDED TO THE |
| | NUMBER OF PERSONS CALCULATED BY TABLE |
| | 403.1 TO OBTAIN THE TOTAL ADDITIONAL |
| | FACILITIES REQUIRED. |
| | 8. SHT 3.0P NOTES PLUMBING SCOPE OF WORK |
| | NOTE NUMBER #4 CUT OFF AND CAN NOT BE |
| | READ. SECTION 104.2.1. |
| | 9. SHT 3.0P GREASE TRAP UNDER SINK IN |
| | FOOD PREP AREA IS NOT APPROVED. DELETE |
| | FROM PLANS. |
| | 10. SHT 3.0P TOILET ROOMS REQUIRE A LOCK |
| | ON THE DOOR PER SECTION 426.3.2.2. |
| | 11. SHT 3.0P WATER RISER DIAGRAM FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER |
| | DOWN FEED PIPES. SECTION 606.1(4)- |
| | KITCHEN FIXTURES AND ONE W/C AND THE |
| | URINAL ARE NOT SHOWN ON THE RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, |
| | WATER HAMMER ARRESTORS AS REQUIRED ON |
| | RISER. - WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. - THERMAL EXPANSION CONTROL |
| | REQUIRED PER SECTION 607.3.2. |
| | 12. SHT 3.0P SANITARY RISER DIAGRAM |
| | MISSING ONE HAND SINK AND THE SCULLARY |
| | SINK. SECTION 104.3.1.1. |
| | 13 SHT 3.0P EQUIPMENT SCHEDULE DOES NOT |
| | REFLECT THE FLOOR PLAN. SEE ITEM #1. |
| | SECTION 104.2.1. |
| | 14. SHT 3.0PPLUMBING NOTES #8, DOES |
| | NOT COMPLY WITH TABLE 704.1. 2-1/2"AND |
| | SMALLER PIPE SHALL BE PITCHED AT |
| | 1/4"/FT. - NOTE #11 "L" COPPER REQUIRED |
| | UNDER THE SLAB. M SOFT ROLL NOT |
| | MANUFACTURED AND NO JOINTS FOR COPPER |
| | ARE APPROVED UNDER THE SLAB. - NOTE #12 |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | REFERENCE FROM NOTE. SECTION 604.9 |
| | 15. SHOW THE FOLLOWING INFORMATION TO |
| | INDICATE COMPLIANCE: |
| | FOR THE URINAL: |
| | A. 11-4.18.4 CONTROLS |
| | FOR THE LAVS: |
| | B. 11-4.19.5 FAUCETS |
| | 16. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT AS INDICATED |
| | ON THE EQUIPMENT SCHEDULE: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | QUESTONS CONTACT 561-805-6692 |