| 2005-08-31 00:00:00 | ******* UNSAT ******* |
| | |
| | 1)NOTE:PLEASE SEE MECH NOTES, SITE |
| | PLANS, PLANS ARE TO INDICATE 10' |
| | CLEARENCE FROM ANY OPENINGS IN HOUSE, |
| | ATTIC VENTILATION, OPERABLE WINDOWS, |
| | DOORS. ETC. |
| | PLEASE SEE SITE PLANS DO NOT INDICATE |
| | DIMENTIONS FROM DWELLINGS. |
| | |
| | 2)NOTE: PLEASE SUBMIT SPECS FOR TRANSFER |
| | SWITCH WHICHINDICATE BEING "SERVICE |
| | EQUIPMENT RATED" AS REQUIRED UNDER |
| | 225.36 |
| | PLEASE ALSO SEE THE ATS AS SHOWN DOES |
| | NOT MEET 230.76, 230.79, 110.27 |
| | MUST CONTAIN AN MANUAL MEANS OF |
| | DISCONNECT LOCATED ON THE OUTSIDE OF THE |
| | EQUIPMENT. |
| | PLEASE SEE THIS MAN MEANS OF DISCONNECT |
| | MUST BE RATED FOR THE LOAD SERVED. |
| | 110.27 |
| | |
| | 3)NOTE: PLEASE SEE RISER INDICATES AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" BEING |
| | INSTALLED FROM METER TO MAIN/FIRST MEANS |
| | OF DISCONNNECT. |
| | PLEASE SEE EQUIPMENT GRNDS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF DISC. |
| | 250.6 |
| | |
| | 4)NOTE: PLEASE SEE MISSING COLD WATER |
| | PIPE AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM. |
| | 250.50 |
| | |
| | 5)NOTE: PLEASE SEE RISER INDICATES THE |
| | ENTIRE SERVICE WILL BE FED FROM THIS NEW |
| | GENERATOR, HOWEVER PLEASE SEE THE |
| | CIRCUITS AS SHOWN ON LOAD CALCULATIONS, |
| | DO NOT SEEM TO INDICATE ALL CIRCUITS IN |
| | THIS HOUSE. |
| | PUMPS, SPECIFIC APPLIANCES, MOTOR LOADS |
| | ETC, ETC. |
| | PLEASE SUPPLY COMPLETE PANEL SCHEDULES |
| | INDICATING ALL CIRCUITS AND LOADS. |
| | PLEASE SEE MIN KW RATING FOR RANGES.8KW. |
| | PLEASE ADJUST AND SUBMIT REVISED LOAD |
| | CALCULATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |