| 2005-08-05 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| | 1- WINDOW MULLIONS: A) PROVIDE FLORIDA |
| | PRODUCT APPROVAL FOR MULLIONS USED OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL BY |
| | USING THE DADE COUNTY NOA AND COMPLETING |
| | THE LOCAL PRODUCT APPROVAL FORM |
| | DOWNLOADED FROM WWW.FLORIDABUILDING.ORG. |
| | |
| | B) SPECIFY MULLION SIZE AND ANCHORS TO |
| | BE USED TO VERIFY COMPLIANCE WITH |
| | ENGINEER CALCULATED DESIGN PRESSURES. |
| | |
| | 2- CUSTOMER QUOTE LIST AND CUSTOMER |
| | AGREEMENT SUBMITTED CALLSFOR SINGLE |
| | HUNG WINDOWS AND SLIDING GLASS DOORS |
| | WITH TEMPERED GLASS. PRODUCT APPROVALS |
| | SUBMITTED ARE FOR LARGE MISSILE IMPACT |
| | GLASS. CLARIFY AND REVISE AS REQUIRED. |
| | *NOTE: ENGINEER IS TAKING INTO |
| | CONSIDERATION THE BUILDING TO BE |
| | DESIGNED AS ENCLOSED, THEREFORE, IMPACT |
| | GLASS IS REQUIRED. |
| | REVISE VALUATION OF JOB ACCORDINGLY TO |
| | THE IMPACT GLASS DOORS/WINDOWS FEES. |
| | |
| | 3- SINGLE HUNG WINDOWS SUBMITTED DON'T |
| | RESIST THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER. NEED WINDOWS THAT MEET |
| | THE CALCULATED DESIGN PRESSURES. SEE |
| | PAGE 1 OF 5 OF DADE COUNTY NOA SINGLE |
| | HUNG WINDOWS |
| | |
| | 4- CLEARLY IDENTIFY WHICH GLAZING OPTION |
| | IS GOINT TO BE INSTALLED FOR SLIDING |
| | GLASS DOORS TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES CALCULATED BY THE |
| | ENGINEER. SEE PAGE 2 OF 8 OF DADE COUNTY |
| | NOA FOR SLIDING GLASS DOORS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |