| Notes |
| Date |
Text |
| 2005-08-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- A)PROVIDE FLORIDA PRODUCT APPROVAL OR | | | APPLY FOR LOCAL PRODUCT APPROVAL FOR | | | WINDOW MULLION TO BE INSTALLED. | | | | | | B) CLEARLY SPECIFY MULLION SIZE AND | | | ANCHORS TO BE USED TO VERIFY COMPLIANCE | | | WITH THE DESIGN PRESSURES CALCULATED BY | | | THE ENGINEER. | | | | | | C) MULLION DADE COUNTY NOA SUBMITTED IS | | | FOR 2X HEAVY WALL MULLION. MULLION SIZE | | | SPECIFIED ON CUSTOMER ORDER FORM IS | | | 1X2.75X.650. NEED PRODUCT APPROVAL FOR | | | ACTUAL MULLION SIZE TO BE INSTALLED TO | | | VERIFY FOR DESIGN PRESSURES COMPLIANCE. | | | | | | 2- CUSTOMER QUOTE AND SALES AGREEMENT | | | CALL FOR SINGLE HUNG WINDOWS WITH | | | TEMPERED GLASS. PRODUCT APPROVAL | | | SUBMITTED IS FOR IMPACT GLASS. PROVIDE | | | PRODUCT APPROVAL FOR CORRECT WINDOW TO | | | BE INSTALLED. | | | *NOTE: ENGINEER CALCS ASSUME BUILDING TO | | | BE ENCLOSED. THEREFORE, WINDOWS NEED TO | | | HAVE IMPACT GLAZING. | | | **UPDATE VALUATION OF PROJECT AS REQ.D . | | | SEE QUOTE LIST OF PRICES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|