| Date |
Text |
| 2006-07-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | COMMENTS FROM PREVIOUS REVIEWS: |
| | |
| | **************************************** |
| | A. COMMENTS FROM PREVIOUS REVIEW: NO |
| | COMMENT RESPONSES TO REVIEW WERE NOT |
| | SUBMITTED. COMMENT NUMBERS SHALL REMAIN |
| | THE SAME AS FIRST REVIEW UNTIL ADDRESSED |
| | **************************************** |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO |
| | INFORMATION ON THE SEAL HAS BEEN |
| | IMPRESSED ON THE SHEETS AS REQUIRED BY |
| | FAC 61G1-16.001. ALSO THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER AND THE PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT |
| | SHALL APPEAR ON THE TITLE BLOCK PER FAC |
| | 61G1-16.004(2) & (6) AND FS 481.219, |
| | 481.2055.(NO RESPONSE, SHEETS NOT |
| | RESUBMITTED. PLEASE CLARIFY) |
| | ****RESPONSE NOTED, BUT PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT AND CA# |
| | STILL NOT INDICATED. SEE ATTACHED SHEET |
| | FROM DBPR WEBSITE. |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW |
| | BACKING & OPENING DIMENSIONS FOR THE W/C |
| | OPENINGS FOR ADDITIONAL BATHROOMS PER |
| | BATHROOM REQUIREMENTS PAGE 7.35. THIS |
| | WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS' |
| | SHT A4.03 UNIT 'BS', SHT A4.04 UNIT |
| | 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06 |
| | UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15 |
| | UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20 |
| | UNIT 'KN', SHT A4.22 UNIT 'LS', SHT |
| | A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2', |
| | SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT |
| | 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28 |
| | UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT |
| | A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT |
| | 'QN', SHT A4.32 UNIT 'RN', SHT A4.33 |
| | UNIT 'RS', SHT A4.34 UNIT 'SN', SHT |
| | A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS', |
| | SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT |
| | 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT |
| | A4.31.1 UNIT 'STSM'. (NO RESPONSE, NOT |
| | ADDRESSED. ADDITIONAL BATHROOMS IN THE |
| | UNIT ARE EXEMPT -ONLY- FROM MANEUVERING |
| | AND CLEAR FLOOR SPACE REQUIREMENTS AT |
| | FIXTURES) |
| | ****RESPONSE NOTED, BUT DIMENSIONS SHALL |
| | BE SHOWN IN EACH UNIT, OR INDICATE IN |
| | EACH UNIT WHERE THE DIMENSIONS SHALL BE |
| | LOCATED. |
| | |
| | 13.OK |
| | 14. NOT USED |
| | 15. NOT USED |
| | |
| | 16. SHTS A4.38, A4.39, & A4.40 ENTRY |
| | LEVEL TO BE COVERED PER FHA. SUBMIT |
| | DETAILS FOR BATHROOMS. (RESPONSE NOTED, |
| | BUT THE FIRST FLOOR SHALL HAVE A |
| | ACCESSIBLE PATH TO THE ELEVATORS). |
| | |
| | 17. GROUND FLOOR CONFERENCE ROOM SINKS |
| | SHALL BE ACCESSIBLE. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE FOLLOWING |
| | INFORMATION SHALL BE SHOWN: |
| | A. 11-4.24.5 CLEAR FLOOR SPACE, CABINET |
| | DOORS SHALL BE REMOVED, NO DOORS IN THE |
| | CLEAR FLOOR SPACE. |
| | B. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | C. 11-4.24.7 FAUCETS |
| | 18. OK |
| | 19. OK |
| | 20. NOT USED |
| | 21. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT: |
| | |
| | C. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT INDICATE WHERE |
| | THE DETAIL CAN BE LOCATED. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE POOL/SPA |
| | HEATER SHEETS HAVE NOT BEEN FOUND. |
| | |
| | E. (NEW COMMENT) PIPE SIZE INCORRECT AT |
| | LAST SPA HEATER. 1-1/4" REQUIRED. 1-1/2" |
| | REQUIRED FOR 2 SPA HEATERS. 2" REQUIRED |
| | FOR 3 SPA HEATERS. |
| | |
| | 22.(INFORMATIONAL) |
| | |
| | 23. ALL FLOOR PLAN SHEETS, SHOW THE |
| | LOCATION & NUMBER OF EACH RISER THRU THE |
| | BUILDING ON EACH FLOOR PLAN AND EACH |
| | LEVEL. SECTION 104.2.1. (NO RESPONSE, |
| | NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE RISERS ARE |
| | ONLY SHOWN ON THE GROUND FLOOR. WHERE IS |
| | LEVEL 3? |
| | |
| | 24.OK |
| | |
| | 25. SHT P-2 SHOW THE PIPING FOR ALL |
| | TRENCH DRAINS WITH PIPE SIZES. THIS |
| | SHALL BE REFLECTED ON THE STORM RISER |
| | DIAGRAM. SECTION 104.3.1.1. (NO |
| | RESPONSE, NOT ADDRESSED FOR TRENCH DRAIN |
| | AT COL. LINE G/01). |
| | ****RESPONSE NOTED, BUT PIPING NOT SHOWN |
| | ON P-2 OR P-68 |
| | |
| | 26. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| | WASTE ORD. #3434. PLEASE CONTACT LYNN |
| | MASSON AT (561) 822-2271, FAX (561) |
| | 822-2279 OR E-MAIL [email protected]. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT APPROVAL |
| | REQUIRED BY LYNN MASSON FOR LOCATION AND |
| | MAINTENANCE. |
| | |
| | 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL |
| | PIPE SIZES. RECALCULATE ADDITION ON SOME |
| | RWL'S, INDICATE RWL RISER NUMBERS, 3" |
| | OVERFLOW SHOWN CONNECTING TO PRIMARY |
| | SYSTEM AT COL. 24 BETWEEN COLS, A&B. |
| | PLEASE CLARIFY. SECTION 104.2.1. -(SHOW |
| | ALL SECONDARY ROOF DRAINS, WITH PIPE |
| | SIZES, SF, ETC.). (NO RESPONSE NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, ADDITION STILL NOT |
| | CORRECT IN SOME PLACES. RECHECK ALL |
| | ADDITION OF THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. - RWL'S ARE |
| | NOT NUMBERED. THIS IS REQUIRED TO TRACK |
| | THE RISERS THRU THE BUILDING. - |
| | SECONDARY DRAINS ON THE 5TH FLOOR ARE |
| | SHOWN IN THE PLANTERS FOR SOME, AND IN |
| | OPEN AREAS FOR OTHERS. PLEASE CLARIFY. |
| | |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | |
| | 31. SHT P-7 SANT. PIPING NOT ALLOWED IN |
| | THE EGRESS STAIRWAY. NFPA-101 SECTION |
| | 7.1.3.2.1(6). (NO RESPONSE, NOT |
| | ADDRESSED).RESPONSE NOTED, BUT THE |
| | PIPING SHALL BE POURED IN SOLID |
| | CONCRETE, OR DRAIN SHALL BE DESIGNED FOR |
| | THE VOID. |
| | |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. SHT P-9 THE FOLLOWINGPIPING |
| | LAYOUTS DO NOT REFLECT RISER DIAGRAMS |
| | 44, 47, 42, 40, 39, 20, & 4. SECTION |
| | 104.2.1. (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISER #4 STILL |
| | DOES NOT REFLECT THE FLOOR PLAN. |
| | |
| | 36. SHT P-13 PIPING FOR THE DWV AND |
| | STORM SYSTEMS NOT APPROVED IN EGRESS |
| | STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6) |
| | AND SECTION 1006.1.3.1. (METHOD OF |
| | ADDRESSING NOT APPROVED. SEE BUILDING |
| | PLAN REVIEW COMMENT #38). |
| | ****RESPONSE NOTED, BUT THE PIPING WILL |
| | HAVE TO BE IN A SOLID POUR, OR A DRAIN |
| | FOR THE VOID WILL BE REQUIRED. |
| | |
| | 37. P-14. CONDENSATE IS INDICATED AS 5' |
| | SEPARATION FOR THE SUPPORTS. INDICATE |
| | MATERIAL FOR CONDENSATE PIPING. IF PVC, |
| | MAXIMUM 4' SEPARATION OF SUPPORTS PER |
| | TABLE 305.5. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH 140 MPH WIND LOAD FOR |
| | SUPPORTS. (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT S RESIDENTIAL |
| | TOWER ROOF LEVEL, NO DETAIL INDICATED. |
| | |
| | 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON |
| | RISER DIAGRAM 56, 59A, 92, 93, 94, 95, |
| | 96, 97, 98, 99, & 100. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISER 94 DOES |
| | NOT REFLECT THE FIXTURE/WALL LAYOUT. |
| | (SEE SHT P-17 ALSO). |
| | |
| | 39. SHT P-15 PIPING NOT APPROVED IN |
| | EGRESS STAIRWAYS. NFPA-101 SECTION |
| | 7.1.3.2.1(6). (METHOD OF ADDRESSING NOT |
| | APPROVED. SEE BUILDING PLAN REVIEW #38). |
| | ****RESPONSE NOTED, BUT THE PIPING SHALL |
| | BE IN SOLID POUR OR A DRAIN SHALL BE |
| | INSTALLED FOR THE VOID. |
| | |
| | 41. OK |
| | 42. OK |
| | 43. OK |
| | |
| | 44. SHT P-17 THE FOLLOWING RISERS DO NOT |
| | REFLECT PIPING LAYOUT: 50, 51, 52, & 55. |
| | SECTION 104.2.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT 50 & 52 DOES NOT |
| | REFLECT THE FLOOR PLAN AND 52 SHOWS AN |
| | OFFSET ON SHT P-16. |
| | |
| | 46. OK |
| | |
| | 48. SHT P-22 CONDENSATE LINE SHOWN AS 5' |
| | SEPARATION BETWEEN SUPPORTS. INDICATE |
| | TYPE OF MATERIAL. IF PVC PER TABLE 305.5 |
| | MAXIMUM 4' SEPARATION BETWEEN SUPPORTS. |
| | SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW |
| | THEY ARE ATTACHED TO THE ROOF AND SHOW |
| | COMPLIANCE WITH 140 MPH WIND LOAD. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT NO DETAIL |
| | LOCATED. |
| | 49. OK |
| | |
| | 50. SHT P-23 RECREATION AT LEVEL 4 |
| | PIPING DOES NOT REFLECT THE FIXTURE |
| | LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT |
| | WITH PIPING LAYOUT. SECTION 104.2.1. |
| | (RISER DIAGRAM DOES NOT REFLECT FIXTURE |
| | LAYOUT EITHER).(W/C MISSING ON RISER |
| | DIAGRAM). |
| | ****RESPONSE NOTED, BUT THE W/C IS STILL |
| | MISSING AT LEVEL 4 RECREATION. |
| | |
| | 51. OK |
| | 52. OK |
| | 53. OK |
| | 54. OK |
| | 55. OK |
| | 56. OK |
| | 57. SHT P-53 RISER 8 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SECTION 914.1. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT RELIEF VENT |
| | STILL SHOWN AFTER 11 BRANCH INTERVALS. |
| | 58. OK |
| | 59. OK |
| | |
| | 60. SHT P-54 RISER 14 LOWER OFFSET VENT |
| | REQUIRED. SEC. 915.3 - MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE LOWER OFFSET |
| | VENT SHALL CONNECT BETWEEN THE OFFSET & |
| | THE NEXT LOWER HORIZONTAL BRANCH. 915.3 |
| | |
| | 62. SHT P-55 RISER 20 BATHROOM SHOWN ON |
| | 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON |
| | 5TH FLOOR ON RISER. CORRELATE RISER AND |
| | FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH |
| | FLOOR NOT SHOWN ON RISER. SEC. 104.2.1. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE BATHROOM IS |
| | STILL SHOWN ON THE 5TH FLOOR. |
| | |
| | 63. OK |
| | |
| | 64. SHT P-55 RISER 23 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| | LOWER OFFSET VENT REQD. SEC. 915.3. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE LOWER OFFSET |
| | VENT SHALL CONNECT BETWEEN THE OFFSET |
| | AND THE NEXT LOWER BRANCH. SECTION |
| | 915.3. |
| | |
| | 65. OK |
| | |
| | 66. SHT P-56 RISER 26 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO BRANCH CONNECTIONS ON HORIZONTAL |
| | OFFSET. SEC. 711.2. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE LOWER OFFSET |
| | VENT SHALL CONNECT BETWEEN THE OFFSET |
| | AND THE NEXT LOWER BRANCH. SECTION |
| | 915.3. |
| | |
| | 67. SHT P-56 RISER 28 NO HORIZONTAL DRY |
| | VENTS. SEC. 905.3/905.4 (16TH FLOOR). |
| | ****NOT ADDRESSED. |
| | |
| | 68. SHT P-56 RISER 29 LOWER OFFSET VENT |
| | REQD. SEC 915.3. - NO CONNECTION TO |
| | HORIZONTAL OFFSET. SEC. 711.2. (NO |
| | RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE LOWER OFFSET |
| | VENT SHALL CONNECT BETWEEN THE OFFSET |
| | AND THE NEXT LOWER BRANCH. 915.3. |
| | |
| | 69. SHT P-56 RISER 30 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENTS. SEC. |
| | 905.3/905.4. (NO RESP0NSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT OFFSETS IN THE |
| | STACK VENT SHALL BE ABOVE THE FLOOD |
| | LEVEL OF THE HIGHEST FIXTURE. 905.4. |
| | |
| | 70. SHT P-56 RISER 32 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| | NO HORIZONTAL DRY VENTS. SEC. |
| | 905.3/905.4. - UPPER OFFSET VENT REQD. |
| | SEC. 915.2. - SEPARATE RISER SECTION AT |
| | BASE OF STACK FOR POWDER ROOM, INDICATE |
| | RISERS CONNECTING FROM UPSTREAM. (33, |
| | 37, 37A) SEC. 104.2.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE LOWER OFFSET |
| | VENT SHALL CONNECT BETWEEN THE OFFSET |
| | AND THE NEXT LOWER BRANCH. 915.3. |
| | |
| | 71. SHT P-56 RISER 33 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENT. SEC. 905.3/905.4 |
| | - DOES NOT REFLECT FLOOR PLAN @ 4TH |
| | LEVEL. (BASE OF STACK) SEC. 104.2.1. - |
| | VENT FROM 1ST FLOOR FLOOR DRAIN NOT |
| | SHOWN ON RISER. (SEE P-3, P-4, P-67). |
| | (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE VENT SHALL |
| | OFFSET ABOVE THE FLOOD LEVEL OF THE |
| | HIGHEST FIXTURE. 905.4. |
| | 72. OK |
| | 73. OK |
| | 74. OK |
| | |
| | 75. SHT P-59 RISER 50 DOES NOT REFLECT |
| | THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1. |
| | (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISER STILL DOES |
| | NOT REFLECT THE FLOOR PLAN. |
| | |
| | 76. OK |
| | |
| | 77. SHT P-59 RISER 52 DOES NOT REFLECT |
| | FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT |
| | REQUIRED. SEC. 915.2. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT OFFSET IS SHOWN |
| | ON P-15, BUT NOT ON THE RISER. |
| | |
| | 78. OK |
| | |
| | 79. SHT P-60 RISER 56 DOES NOT REFLECT |
| | THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS |
| | REQD. SECS. 915.2/915.3. - MAX. 10 |
| | BRANCH INTERVALS TO RELIEF VENT. SEC. |
| | 914.1. - NO CONNECTIONS TO HORIZONTAL |
| | OFFSET. SEC. 711.2.- NO HORIZONTAL DRY |
| | VENTS. SECS. 905.3/905.4. (NO RESPONSE, |
| | NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT VENT OFFSET |
| | SHALL BE ABOVE THE FLOOD LEVEL OF THE |
| | HIGHEST FIXTURE. 905.4. |
| | |
| | 80. OK |
| | 81. OK |
| | 82. OK |
| | 83. OK |
| | 84. OK |
| | |
| | 85. SHT P-61 RISERS 63, 64 DO NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CLARIFY |
| | SEC. 104.2.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISERS STILL DO |
| | NOT REFLECT THE FLOOR PLAN. |
| | |
| | 86. SHT P-61 RISER 67 MAX 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENTS. SECS. 905.3 |
| | 905.4. (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE VENT SHALL |
| | OFFSET ABOVE THE FLOOD LEVEL OF THE |
| | HIGHEST FIXTURE. 905.4. |
| | |
| | 87. OK |
| | 89. OK |
| | |
| | 90. SHT P-62 RISER 71 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO DRY HORIZONTAL VENT. SECS. 905.3 |
| | 905.4. (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT THE VENT OFFSET |
| | SHALL BE ABOVE THE FLOOD LEVEL OF THE |
| | HIGHEST FIXTURE. 905.4. |
| | |
| | 91. OK |
| | |
| | 92. SHT P-62 RISER 73 & 74 MAX. 10 |
| | BRANCH INTERVALS TO RELIEF VENT. SEC. |
| | 914.1. (NO RESPONSE, NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISER 73 SHOWS |
| | THE RELIEF VENT AFTER 11 BRANCH |
| | INTERVALS. |
| | |
| | 94. OK |
| | 95. OK |
| | 96. OK |
| | |
| | 97. SHT P-64 RISERS 89,94,95,99,101,102 |
| | & 103 DO NOT REFLECT THE FLOOR PLANS. |
| | SECTION 104.2.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISER 94 STILL |
| | DOES NOT REFLECT THE FLOOR PLAN. |
| | |
| | 98. OK |
| | |
| | 99. SHT P-67 FOLLOWING ARE CORRECTIONS |
| | TO BE MADE TO SANT. |
| | - RISERS 23 & 23A MISLABELED. |
| | - 2" VENT UP TO RISER |
| | 67 TO READ "TO RISER 67A". (SEE RISER |
| | 67A). - "2" VENT FOR CONT. SEE P-53" |
| | INDICATE RISER VENT WILL CONNECT TO. - |
| | - THIS SHEET SHOWS LEVELS AS PARK, |
| | PARK 2, PARK 3 ECT., BUT SHEETS P-15, |
| | P-16. & P-17 SHOWS LEVELS AS GROUND |
| | FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS |
| | MEZZ. ECT. PLEASE CLARIFY & CORRELATE |
| | SHEET LEVELS. - RECHECK ADDITION OF |
| | FIXTURE UNITS AS THEY ACCUMULATE IN THE |
| | SYSTEM. SOME FIXTURES UNITS ARE NOT |
| | SHOWN AND ADDED TO THE SYSTEM. INDICATE |
| | THE SLOPE OF THE PIPE WHERE THE FIXTURES |
| | UNITS ARE MORE THAN ALLOWED FOR MINIMUM |
| | SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE |
| | INSTALLED IN A UNIFORM SLOPE AS REQUIRED |
| | IN SECTION 704.1. INDICATE ON PLANS. |
| | SECTION 104.2.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | ****RESPONSE NOTED, BUT RISERS 23 & 23A |
| | ARE STILL MISLABELED. (SHOULD NOW BE 23, |
| | 23A, 21, NOT 23, 234. - RISER NOT |
| | INDICATED FOR VENT. - LEVELS STILL |
| | DIFFERENT FROM SHEET TO SHEET. CLARIFY. |
| | - STILL MISSING PIPE SIZE, AND NEED TO |
| | SHOW DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. ADDITION TO BE CHECKED AS IT IS |
| | NOT CORRECT IN SOME AREAS. - CHECK |
| | PROPER APPLICATION TO THE FIXTURE UNIT |
| | TABLES 709.1, 709.2, (FOR TRAPS LARGER |
| | THAN INDICATED IN 709.1), 710.1(1), |
| | 710.1(2). - CONFLICTS IN SLOPE, SHOWS |
| | 1/16"/FT IN SOME AREAS, BUT NOTE STATES |
| | "1/8"/FT FOR ALL PIPE 3" & LARGER. |
| | PLEASE CORRELATE. |
| | |
| | 100. SHT P-68 HORIZONTAL STORM RISER |
| | DOES NOT REFLECT STORM PIPING IN |
| | BUILDING. STRUCTURES S1 THRU S9 NOT |
| | SHOWN. - NO ROOF DRAINS 2650SF, 2350SF, |
| | 2450SF ECT. FOUND. - NO EXFILTRATION |
| | TRENCHES FOUND. - NO TRENCH DRAINS |
| | FOUND, RISERS SHOWS 25TH, 26TH, 27TH |
| | FLOORS ECT. - NO POINT OF REFERENCE TO |
| | FLOOR PLAN CAN BE FOUND. - RISER HARD TO |
| | READ, PLEASE INCREASE THE SIZE OF THE |
| | STORM RISER DIAGRAM AND POSSIBLY SPLIT |
| | UP TO TWO PAGES TO MAKE RISER EASIER TO |
| | READ. SECTION 104.2.1.3. (NO RESPONSE, |
| | NOT ADDRESSED). |
| | ****RESPONSE NOTED, BUT ADDITION ON |
| | RISER DIAGRAM AND FLOOR NEEDS TO BE |
| | RECHECKED. SOME INCONSISTANCIES. ALSO |
| | SOME AREAS OF THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CHECK |
| | ENTIRE RISER DIAGRAM. |
| | |
| | 101. OK |
| | 102. OK |
| | 103. OK |
| | |
| | 104. BACKFLOW PROTECTION REQUIRED FOR |
| | IRRIGATION, POOLS, TRASH CHUTE WASH |
| | DOWNS, AND COOLING TOWER MAKE UP WATER. |
| | SECTION 608. INDICATE METHOD OF |
| | PROTECTION FOR EACH SYSTEM. (NO |
| | RESPONSE, NOT ADDRESSED. |
| | ****RESPONSE NOTED, BUT NO PROTECTION |
| | INDICATED FOR THE IRRIGATION, NOR FOR |
| | THE POOL MAKE UP WATER. |
| | |
| | 105. PLANS ARE INCOMPLETE AT THIS TIME |
| | AND MORE COMMENTS MAY BE FORTHCOMING |
| | WITH THE NEXT REVIEW. |
| | ****PLANS STILL DO NOT SEEM TO BE 100% |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | (NO RESPONSE) |
| | ****RESPONSE NOTED, BUT ON SOME COMMENTS |
| | WITH MULTIPLE COMMENTS, NOT ALL SECTIONS |
| | OF THE COMMENT WERE ADDRESSED IN |
| | RESPONSE. ALSO RSPONSES WERE NOT |
| | DETAILED AS TO WHERE THE CORRECTION |
| | COULD BE FOUND. |
| | **************************************** |
| | **************************************** |
| | |
| | NEW COMMENTS: (2ND REVIEW) |
| | |
| | 1B. OK |
| | |
| | 2B. SHOW PIPING FOR FIXTURES IN THE |
| | SHEET WITH FIXTURES, NOT ON THE FLOOR |
| | BELOW. THIS IS CONFUSING AND IS HARD TO |
| | FOLLOW THE PIPING, FIXTURES, AND RISER |
| | DIAGRAM ISOMETRICS. SECTION 104.2.1. |
| | ****RESPONSE NOTED, BUT THIS IS NOT |
| | ACCEPTABLE. THE PIPING AS SHOWN IS STILL |
| | CONFUSING. SOME PIPING THAT SHOULD BE ON |
| | THE SAME FLOOR AS THE FIXTURES, (SUCH AS |
| | WASH MACHINE PIPING, LAV AND KITCHEN ARM |
| | PIPING, ETC.), IS SHOWN ON THE FLOOR |
| | BELOW ALSO. ALL PIPING SHALL BE SHOWN ON |
| | THE SAME FLOOR AS THE FIXTURES. |
| | |
| | 3B. BUILDING PLANS SHALL BE DRAWN TO |
| | MINIMUM OF 1/8" SCALE. SECTION |
| | 104.2.1.3. ( SEE SHEETS P-2 THRU P-6. |
| | PLEASE SUBMIT 1/8" SCALE FOR THESE |
| | SHEETS FOR REVIEW). |
| | ****RESPONSE NOTED, BUT SHT P-6 HAS NOT |
| | BEEN CHANGED. |
| | |
| | 4B. OK |
| | |
| | 5B. SHT P-1A LOCATED BETWEEN P-19 & |
| | P-20. INDEX CALLS FOR IT TO BE PRIOR TO |
| | SHT P-1. PLEASE CORRELATE SHEETS & |
| | INDEX. SHT 104.2.1. |
| | ****RESPONSE NOTED, BUT SHT P-1A IS |
| | INSERTED AFTER P-1. CORRELATE THE INDEX |
| | AND SHEETS. |
| | |
| | **************************************** |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | PLANS FOR COMPAIRSON. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUM- BER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICA TION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | **************************************** |
| | **************************************** |
| | |
| | NEW COMMENTS: (3RD REVIEW) |
| | |
| | 1C. SHT P-1 PIPE SIZES FOR THE SPA |
| | HEATERS ARE INCORRECT. 2" REQUIRED FOR 3 |
| | HEATERS, 1-1/2" REQUIRED FOR 2 HEATERS, |
| | AHD 1-1/4" REQUIRED FOR THE LAST HEATER. |
| | TABLE 402.2 |
| | |
| | 2C. SHTS P-2, P-2A, P-2B, P-2C, P-2D AND |
| | RISER DIAGRAM P-68, P-68A, P-68B, P-68C. |
| | CHECK THE ADDITION OF SQUARE FOOTAGE IN |
| | SYSTEM. ALSO MAKE SURE THE RISER DIAGRAM |
| | REFLECT THE FLOOR PLAN THROUGHOUT. |
| | SECTION 104.2.1, TABLE 1106.2, 1106.3 |
| | |
| | 3C. SHT P-7 DOWNSTREAM OF RISER 24, 24A |
| | DOES NOT REFLECT THE FLOOR PLAN. SECTION |
| | 104.2.1. |
| | |
| | 4C. ALL FLOOR PLAN SHEETS. NO PIPING IS |
| | SHOWN FOR WASH MACHINE DRAINS. (SEE |
| | RISER 32 FOR EXAMPLE). SECTION 104.2.1. |
| | |
| | 5C. SHT P-9 UNITS 'LT2' EITHER SIDE OF |
| | COL. LINE S.06 SHOW NO LAV FIXTURES. |
| | SECTION 104.2.1. |
| | |
| | 6C. SHT P-9 RISERS 16 & 22 OFFSETS SHOWN |
| | ARE NOT SHOWN ON THE RISER DIAGRAMS. - |
| | SHOW PIPING TO W/C'S AND LAVS. SECTION |
| | 104.2.1. |
| | |
| | 7C. SHT P-15 RISER 73,75,76,77,78,79 |
| | DFU'S DO NOT REFLECT DFU'F INDICATED ON |
| | THE RISER DIAGRAM. CORRELATE DFU'S. |
| | SECTION 104.2.1. |
| | |
| | 8C. SHT P-16 RISER 52 OFFSET NOT SHOWN |
| | ON THE RISER. CORRELATE FLOOR PLAN AND |
| | RISER DIAGRAM. SECTION 104.2.1. |
| | |
| | 9C. SHT P-17 RISERS 62 & 94 FLOOR PLANS |
| | DO NOT REFLECT THE RISER DIAGRAMS. |
| | |
| | 10C. SHT P-17 FLOOR PLAN INDICATED |
| | PARTIAL SOUTH NORTH RESIDENTIAL LOFTS |
| | 2ND LEVEL, BUT SHEET TITLE SHOWS NORTH |
| | RESIDENTIAL LOFTS 2ND LEVEL. PLEASE |
| | CORRELATE SHEET INFORMATION. 104.2.1. |
| | |
| | 11C. SHT P-19 FLOOR PLAN INDICATES NORTH |
| | RESIDENTIAL, BUT SHEET TITLE INDICATES |
| | SOUTH RESIDENTIAL. CORRELATE. 104.2.1. |
| | |
| | 12C. SHT P-23 RECREATION AT LEVEL 2 |
| | SHOWS TWO WASTE ARMS FOR ONE LAV. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | |
| | 13C. SHT P-37 MISLABELED AS P-39. |
| | 104.2.1. |
| | |
| | 14C. SHT P-52 RISER DIAGRAM FOR 1W UNIT, |
| | W/C FOR POWDER NOT VENTED. SECTION |
| | 901.2.1. |
| | |
| | 15C. SHT P-53 STACK DIAGRAM #4 DOES NOT |
| | REFLECT THE FLOOR PLAN AT LEVEL 4. |
| | PLEASE CORRELATE. 104.2.1. |
| | |
| | 16C. SHT P-54 STACK RISER #12 SHOWS A |
| | SHOWER, BUT FLOOR PLAN SHOWS A TUB. |
| | PLEASE CORRELATE. 104.2.1. |
| | |
| | 17C.SHT P-54 STACK RISER #16 CHECK |
| | VENTING LEVEL 2. SECTION 104.2.1. |
| | |
| | 18C. SHT P-54 STACK RISER #18 INDICATES |
| | AN EXTRA BRANCH LINE BETWEEN LEVELS 3 & |
| | 4. MORE INFORMATION REQUIRED. PLEASE |
| | EXPLAIN WHAT THIS CONNECTS TO. SECTION |
| | 104.2.1. |
| | |
| | 19C. SHT P-55 STACK RISER #24 HORIZONTAL |
| | BRANCH LINE SHALL NOT CONNECT TO THE |
| | HORIZONTAL STACK OFFSET. 711.2 (2 |
| | INSTANCES). |
| | |
| | 20C. SHT P-55 STACK RISER #23 HORIZONTAL |
| | BRANCH LINE SHALL NOT CONNECT TO THE |
| | HORIZONTAL STACK OFFSET. 711.2 (2 |
| | INSTANCES LEVEL 3 & LEVEL 4). |
| | |
| | 21C. SHT P-56 STACK RISER #29 DOES NOT |
| | REFLECT THE FLOOR PLAN LEVEL 2. |
| | CORRELATE. SECTION 104.2.1. |
| | |
| | 22C. SHT P-59 STACK RISER #50 DOES NOT |
| | REFLECT THE FLOOR PLAN LEVEL 4. |
| | CORRELATE. SECTION 104.2.1. |
| | |
| | 23C. SHT P-60 STACKS 56 & 58 HORIZONTAL |
| | BRANCH LINES SHALL NOT CONNECT TO THE |
| | HORIZONTAL STACK OFFSET. SECTION 711.2 |
| | (2 PLACES EACH STACK). |
| | |
| | 24C. SHT P-61 STACK RISER #62 HORIZONTAL |
| | BRANCH CONNECTIONS TO THE HORIZONTAL |
| | STACK OFFSETS NOT APPROVED. 711.2 (2 |
| | PLACES). |
| | |
| | 25C. SHT P-61 STACK RISER #63 FIXTURES |
| | NOT SHOWN ON THE FLOOR PLAN TO REFLECT |
| | THE RISER AT THE BOTTOM OF THE STACK. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | |
| | 26C. SHT P-61 STACK RISER #64 LEVEL 4 |
| | OFFSET NOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CORRELATE. SECTION 104.2.1. |
| | |
| | 27C. ALL RISERS & FLOOR PLANS WHERE |
| | THERE ARE HORIZONTAL OFFSETS. HORIZONTAL |
| | BRANCH CONNECTIONS SHALL NOT CONNECT |
| | WITH IN 2FT OF OFFSETS. SECTION 711.2. |
| | |
| | 28C. SHT P-64 STACK RISER #94 DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE BASE OF |
| | THE STACK. CORRELATE. 104.2.1. |
| | |
| | 29C. SHT P-67 MAXIMUM 2900 DFU'S ON 12" |
| | PIPE AT 1/16"/FT SLOPE. 3538 DFU'S |
| | SHOWN. NOTE INDICATED 3" OR MORE PIPE |
| | SIZE SHALL SLOPE 1/8"/FT. SOUTH BLDG. |
| | DRAIN SHOWS 1/16TH/FT SLOPE IN VARIOUS |
| | PLACES. CORRELATE. SECTION 104.2.1 AND |
| | TABLE 710.1(1) |
| | |
| | 30C. SHT P-67 5" MINIMUM REQUIRED |
| | UPSTREAM OF RISER 102. TABLE 710.1(1). |
| | PLEASE INDICATE ON RISER. |
| | |
| | 31C. SHT P-67 CLEANOUT MISSING UPSTREAM |
| | OF THE BASE OF RISER 26/27 ETC. DOES NOT |
| | REFLECT THE FLOOR PLAN. CORRELATE. |
| | 104.2.1. |
| | |
| | 32C. SHT P-67 SHOWS RISER 23, 234. |
| | SHOULD BE 23, 23A, 21. SECTION 104.2.1. |
| | |
| | 33C. SHT P-67 UPSTREAM OF RISER 39, 40 |
| | ETC., SHOWS VENT FOR FLOOR DRAINS. |
| | INDICATE WHERE VENT CONNECTS. SECTION |
| | 104.2.1. |
| | |
| | 34. THE FOLLOWING STACKS HAVE HORIZONTAL |
| | DRY VENTS AT THE TOP OF THE STACKS. |
| | THESE VENTS SHALL BE OFFSET ABOVE THE |
| | FLOOD LEVEL OF THE HIGHEST FIXTURES. |
| | THESE STACKS ARE ON SHEETS P-53, P-54K, |
| | P-55, P-56, P-59, P-60, AND P-62. - |
| | STACK NUMBERS 1, 2, 13, 15, 10, 12, 14, |
| | 16, 18, 20, 22, 23, 26, 28, 30, 32, 33, |
| | 48, 48A, 53, 55, 56, 57, 60, 67, 71, 73, |
| | 74. SECTION 905.4. |
| | |
| | 35C. SHT P-39 NO PIPING SHOWN ON THE |
| | FLOOR PLAN 2ND FLOOR LOFT UNITS. SHOW |
| | PIPING. SECTION 104.2.1. |
| | |
| | 36C. ALL RISERS WITH OFFSET VENTS. LOWER |
| | OFFSET VENTS SHALL CONNECT BETWEEN THE |
| | OFFSET AND THE NEXT LOWER HORIZONTAL |
| | BRANCH CONNECTION. SECTION 915.3. |
| | |
| | 37C. SHT P-62 RISER 72 NO LAV ARM SHOWN |
| | ON LEVEL 4. CLARIFY. SECTION 104.2.1. |
| | |
| | 38C. SHT P-62 RISER 79 SHOWS WASH |
| | MACHINE PIPING FOR 2ND LEVEL, BUT NO |
| | WASH MACHINE SHOWN. CLARIFY. 104.2.1. |
| | |
| | 39C. INDICATE THE LOCATION FOR THE VENTS |
| | FOR THE CONDENSATE RISERS. VENTS ARE NOT |
| | ALLOWED IN THE WALLS, OR IN THE A/C ROOM |
| | IF THE ROOM IS A PLENUM. SECTION |
| | 104.2.1. |
| | |
| | **************************************** |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | PLANS FOR COMPAIRSON. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUM- BER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICA TION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | **************************************** |
| | **************************************** |
| | |