| 2006-06-28 00:00:00 | PERMIT: 05071027 |
| | ADD: 2211 N FLAGLER DR |
| | CONT: PLAN REVIEW |
| | OWNER: MERCO GROUP |
| | TEL: (561)296-3300 |
| | ARCH: SONG & ASSOC/ JOHN STRNDBERG |
| | |
| | TEL: (561) 655-2423 |
| | |
| | -PALADIO TERRACE- |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1)LS 0.00 SHEET: |
| | A) OCCUPANCY CALCULATION AT THE BOTTOM |
| | OF SHEET, THE OCCUPANCY LOADS FOR THE |
| | VARIOUS FLOORS DO NOT TOTAL WHAT THE |
| | PLAN CALLS FOR, INDICATED 6316 ACTUAL |
| | COUNT IS 6186, CORRECT. |
| | |
| | B) TOP CENTER THE TABLE FOR TRAVEL |
| | DISTANCE AND DEAD ENDS TOTAL THE |
| | OCCUPANT LOAD BY FLOOR AND THE TOTAL IS |
| | 100 LESS THAN THE OCCUPANT LOAD TABLE. |
| | |
| | C) ON THE RIGHT SIDE OF THE PAGE THERE |
| | IS A THIRD AREA WHICH PROVIDES THE |
| | OCCUPANT LOAD AND THE FIGURE STATED |
| | THERE (6081) DOESN'T MATCH EITHER OF THE |
| | OTHERS QUOTED. |
| | |
| | 2)COMMENT2A FROM THE PREVIOUS REVIEW.ATRIUM.WE |
| | WILL BE REVIEWING FOR CODE |
| | COMPLIANCE UNDER SECTION 412.5 (HIGH |
| | RISE SMOKE CONTROL) AND SECTION 414.1-10 (ATRIUM). |
| | |
| | THE NEW LIFE SAFETY PLANS DATED 07-07-06 INDICATE THE |
| | NEW |
| | RATED WALL AND OPENING PROTECTIVES FOR TTHE ATRIUM |
| | AREA. THE ARCHITECTURAL PLANS NEED TO BE UPDATED TO |
| | REFLECT |
| | THE FIRE RATINGS AS WELL AS THE DOOR SCHEDULE. |
| | CURRENTLY THTHE A SHEETS DO NOT INDICATE ANY RATINGS AT |
| | ALL. |
| | 2ND FLOOR: C207B, C205A, C206A, |
| | DOUBLE DOORS TO GARAGE NOT IDENTIFIED, |
| | C203A INDICATES 45MIN RATED, PIVOT |
| | DELUGE PROTECTION FRAMELESS, SEE NFPA 80 |
| | DELUGE SYSTEM IS FOR WINDOWS NOT DOORS, |
| | THE SECOND ISSUE IS THE 45 MIN RATING ON |
| | A FRAMELESS GLASS DOOR, HOW DO YOU SEAL |
| | FOR SMOKE AND FIRE? |
| | 3RD FLOOR: AREA WITH ISSUES, STILL |
| | UNDER CONSIDERATION IN COMMUNICATING |
| | WITH DESIGN TEAM.C301 PIVOT, FRAMELESS, |
| | |
| | |
| | |
| | SHEET LS1-02C HAS A 8 1/2X11 SHEET STAPLED TO THE PLAN |
| | INDICATING THE SEQUENCE OF OPERATION FOR THE MECHANICAL |
| | AND ELECTRICAL DEVISES. |
| | THE MECHANICAL AND ELECTRICAL SHEETS WILL NEED TO BE |
| | FURTHER DEVELOPED TO INCORPORATETHE SEQUENCE OF |
| | OPERATION ALSO. |
| | |
| | PLEASE PROVIDE COMPUTER MODELING FOR |
| | THE ATRIUM THERE HAS BEEN NO STUDY |
| | COMPLETED EITHER FOR SMOKE / FIRE PLUME. |
| | |
| | 3) A SHEETS ARE RED LINED WHERE MISSING FIRE RATINGS ON |
| | WALLSOR DOORS ARE MISSING IDENTIFICATION. |
| | |
| | 4)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | |
| | A) R.C. HORIZONTAL ROLLING WINDOWS LOW |
| | PRESSURE. |
| | |
| | B) R.C. FX100 ALUMINUM FIXED WINDOWS |
| | LOW PRESSURES. |
| | |
| | C) GAF MODIFIED BITAMEN ROOF FOR |
| | CONCRETE DECKS, THE CONTRACTOR |
| | DIDN'T HIGHLIGHT WHICH SUBSYSTEM |
| | WILL BE USED. MAY HAVE LOW PRESSURE |
| | DEPENDING ON THE TYPE OF SYSTEM. |
| | D) EXTERIOR GUARDRAIL- NO REPORT |
| | SUBMITTED. |
| | E) PANEL WALL SYSTEMS: SOFFITS, EFIS |
| | SYSTEMS, DENSEGLASS |
| | |
| | 5)SHEET A6.01 DETAIL# 1, INDICATES THE USE OF AN |
| | EMERGENCY OVERFLOW DRAIN 4 INCHES ABOVE THE ROOF DECK. |
| | 1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | 6 COMMENT#37 FROM THE PREVIOUS REVIEW, |
| | 50) A6.06 MAIN GLASS CANOPY, PROVIDE |
| | INFORMATION ON THE CANOPY SYSTEM. ALSO |
| | PROVIDE INFORMATION ON THE GLAZING |
| | SYSTEM INDICATING COMPLIANCE WITH |
| | 2407.2.1 ALLOWABLE GLAZING MATERIALS. |
| | THIS SYSTEM SHALL ALSO BE AN ENGINEERED |
| | SYSTEM. IT DOESN,T FIT THE PARAMETERS OF |
| | THE PRODUCT APPROVAL UNDER RULE 9-B, THE |
| | CANOPY DESIGN WILL BE SITE SPECIFIC. SEE |
| | "FLORIDA.BUILDING.ORG" FOR REQUIREMENTS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |