2005-12-09 00:00:00DENIED:
 RESPONSE TO REVIEW COMMENTS BY HAROLD
 MOSER DATED 8-25-05:
 COMMENT #4- PLEASE SHOW SEQUENCE OF
 OPERATION FOR SF35 AND SF37.RESPONSE
 REFERENCES PLAN SHEET AC-38, SEQUENCE OF
 OPERATION.PLEASE NOTE ACCORDING THE
 FAN SCHEDULE LOCATED ON PLAN SHEET
 AC-28, SF37 IS NOT IDENTIFIED.
  
 COMMENT # 4 PLEASE SHOW SEQUENCE OF
 OPERATION OF SF-35 & SF-37.PLEASE
 NOTE, SF-37 IS NOT INDICATED ON THE FAN
 SCHEDULE (PLAN SHEET AC-28).
  
 COMMENT #6 GARAGE VENTLATION, RESPONSE
 REFERENCES 2001 FMC 403.4 & 403.4.1.
 PLEASE NOTE AS QUOTED IN RESPONSE THIS
 APPLICATION IS FOR A PUBLIC GARAGE.
 WILL ANYONE OTHER THAN TENANTS &
 EMPLOYEES BE ALLOWED TO PARK AT THIS
 FACILITY?SHOULD USE OF THE PARKING
 GARAGE BE EXCLUSIVE TO THIS BUILDING AND
 ITS TENANTS IT IS NOT CONSIDERED A
 "PUBLIC GARAGE".
  
 UNIT COMMENTS -
 COMMENT #1RESPONSE INDICATES DOORS ARE
 TO BE PAINTED WITH INTUMESCENT PAINT.
 THIS IS NOT AN APPROVED METHOD FOR NEW
 CONSTRUCTION.PLEASE INQUIRE WITH DOOR
 MANUFACTURER FOR COMPLIANCE WITH THE
 25/50 FLAME SPREAD INDEX & SMOKE
 DEVELOPED INDEX. WHEN TESTED IN
 ACCORANCE WTIH ASTM E 84 (2001 FMC
 602.2.1).
  
 COMMENT #3 BALANCED AIR RETURN, RESPONSE
 INDICATES TRANSFER DUCTS WERE REVISED.
 VARIOUS TRANSFER DUCTS DO NOT COMPLY
 WITH THE REQUIREMENT OF 2001 FBC 601.4
 EXCEPTION 1 & 3.EXAMPLE; PLAN SHEET
 AC-16 UNIT D THE INDICATES A 14" X 6"
 FOR THE "TOTAL" SUPPLY AIR INTO THE
 MASTER SUITE WHICH WOULD REQUIRE A 25" X
 6" RETURN TRANSFER DUCT.PLEASE REVISE
 ALL UNITS IN WHICH THIS OCCURS.
  
 NEW COMMENTS:
 1.PLEASE PROVIDE CALCULATIONS FOR THE
 ATRIUM.PLEASE PROVIDE TOTAL VOLUME.
  
 2.PLEASE PROVIDE A DETAIL FOR THE
 ATRIUM SECTION ONLY (ELEVATION).THIS
 INCLUDES ANY CORRIDOR OR ADJACENT SPACES
 THAT A CONSIDERED PART OF THE ATRIUM IN
 ACCORDANCE WITH 414.5 OF THE 2001 FBC.
  
 3.PLAN SHEET AC-01 INDICATES GARAGE
 EXHAUST FANS TERMINATING AT THE 1ST
 LEVEL.ARCHITECTURAL PLAN A2.04-NW
 INDICATES THE WINDOWS ON LEVEL 3 (R03) &
 4 (R04) ARE TO BE FIXED GLASS.PLANS DO
 NOT INDICATE THIS AS "TYPICAL" AND DO
 NOT SPECIFY IF THE WINDOWS AT LEVEL 2
 ARE FIXED.PER 2001 FMC 401.5, EXHAUST
 SHALL BE LOCATED A MINIMUM OF 10FT FROM
 LOT LINES & WHERE OPENINGS FRONT ON A
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF STREET.
  
 4.INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10FT FROM ANY NOXIOUS
 CONTAMINANT, 2001 FMC 401.5.1.
  
 5.PLAN SHEET AC-13 LOBBY FLOOR PLAN
 INDICATES SF-34 & ON THE EQUIPMENT
 SCHEDULE IT INDICATES SF-34 FAN WILL NOT
 BE USED.PLEASE CLARIFY.
  
 6.PLAN SHEET AC-13 THE MEZZANINE FLOOR
 PLAN INDICATES 66" X 14" UP TO SF- ON
 ROOF.IT ALSO INDICATES A 22" X 12"
 DOWN TO THE 1ST FLOOR.PLEASE INDICATE
 IF THIS IS A SHAFT.PLEASE CLARIFY IF
 THIS IS FOR THE MAKE-UP AIR FOR THE
 ATRIUM OR OUTSIDE AIR FOR THE A/C
 SYSTEM.PLEASE NOTE, PER 2001 FMC 607.4
 DUCTS EXTENDING THROUGH MORE THAN ONE
 FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE.FIRE DAMPERS WILL BE
 REQUIRED WHERE DUCTS PENETRATE THE RATED
 ENCLOSURE.PLEASE IDENTIFY ALL FIRE &
 COMBINATION DAMPERS, 2001 FMC 607.6.
  
 7.PLAN SHEET AC-16 NOTE #2 SPECIFIES
 "VENTLESS" DRYERS, PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA.
  
 8.LIFE SAFETY & MECHANICAL PLANS
 (AC-3) REFER TO A "MEZZANINE" LEVEL
 WHEREAS THE ARCHITECTURAL PLANS REFER TO
 THIS AREA AS "LEVEL 3", PLEASE
 CORRELATE.
  
 9.ARCHITECTURAL PLAN (A0.005)
 PARTITION/WALL TYPES, DETAILS INDICATE
 RATING OF PARTITION/WALL IS TO BE
 INDICATED UNDER THE WALL TYPE.THIS IS
 NOT REFLECTED ON THE PLANS.
  
 10. PROVIDE SEQUENCE OF OPERATION OF THE
 SMOKE EVAC FOR THE ATRIUM.
  
 11. PLAN SHEET AC-38 THE SEQUENCE OF
 OPERATION FOR FLOORS 2 THROUGH 18
 INDICATE PRESSURIZATION BUT DOES NOT
 INDICATE THE MITIGATION OF SMOKE.SMOKE
 CONTROL SHALL COMPLY WITH ONE OF THE
 ITEMS INDICATED IN 2001 FBC 412.5.
  
 12. PLEASE ANNOTATE ON THE PLANS,
 DISTANCE FROM THE EXHAUST TERMINATIONS
 (I.E. GENERATOR, GARAGE, ETC) FROM
 WINDOWS, DOORS, FRESH AIR INTAKES,
 WALKWAYS, LOT LINES & ADJACENT
 BUILDINGS.SHOW COMPLIANCE WITH 2001
 FMC 401.5, 401.5.1 & 501.3.
  
 PLEASE NOTE RESPONSE TO COMMENTS MAY
 CREATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  