| Date |
Text |
| 2005-12-09 00:00:00 | DENIED: |
| | RESPONSE TO REVIEW COMMENTS BY HAROLD |
| | MOSER DATED 8-25-05: |
| | COMMENT #4- PLEASE SHOW SEQUENCE OF |
| | OPERATION FOR SF35 AND SF37.RESPONSE |
| | REFERENCES PLAN SHEET AC-38, SEQUENCE OF |
| | OPERATION.PLEASE NOTE ACCORDING THE |
| | FAN SCHEDULE LOCATED ON PLAN SHEET |
| | AC-28, SF37 IS NOT IDENTIFIED. |
| | |
| | COMMENT # 4 PLEASE SHOW SEQUENCE OF |
| | OPERATION OF SF-35 & SF-37.PLEASE |
| | NOTE, SF-37 IS NOT INDICATED ON THE FAN |
| | SCHEDULE (PLAN SHEET AC-28). |
| | |
| | COMMENT #6 GARAGE VENTLATION, RESPONSE |
| | REFERENCES 2001 FMC 403.4 & 403.4.1. |
| | PLEASE NOTE AS QUOTED IN RESPONSE THIS |
| | APPLICATION IS FOR A PUBLIC GARAGE. |
| | WILL ANYONE OTHER THAN TENANTS & |
| | EMPLOYEES BE ALLOWED TO PARK AT THIS |
| | FACILITY?SHOULD USE OF THE PARKING |
| | GARAGE BE EXCLUSIVE TO THIS BUILDING AND |
| | ITS TENANTS IT IS NOT CONSIDERED A |
| | "PUBLIC GARAGE". |
| | |
| | UNIT COMMENTS - |
| | COMMENT #1RESPONSE INDICATES DOORS ARE |
| | TO BE PAINTED WITH INTUMESCENT PAINT. |
| | THIS IS NOT AN APPROVED METHOD FOR NEW |
| | CONSTRUCTION.PLEASE INQUIRE WITH DOOR |
| | MANUFACTURER FOR COMPLIANCE WITH THE |
| | 25/50 FLAME SPREAD INDEX & SMOKE |
| | DEVELOPED INDEX. WHEN TESTED IN |
| | ACCORANCE WTIH ASTM E 84 (2001 FMC |
| | 602.2.1). |
| | |
| | COMMENT #3 BALANCED AIR RETURN, RESPONSE |
| | INDICATES TRANSFER DUCTS WERE REVISED. |
| | VARIOUS TRANSFER DUCTS DO NOT COMPLY |
| | WITH THE REQUIREMENT OF 2001 FBC 601.4 |
| | EXCEPTION 1 & 3.EXAMPLE; PLAN SHEET |
| | AC-16 UNIT D THE INDICATES A 14" X 6" |
| | FOR THE "TOTAL" SUPPLY AIR INTO THE |
| | MASTER SUITE WHICH WOULD REQUIRE A 25" X |
| | 6" RETURN TRANSFER DUCT.PLEASE REVISE |
| | ALL UNITS IN WHICH THIS OCCURS. |
| | |
| | NEW COMMENTS: |
| | 1.PLEASE PROVIDE CALCULATIONS FOR THE |
| | ATRIUM.PLEASE PROVIDE TOTAL VOLUME. |
| | |
| | 2.PLEASE PROVIDE A DETAIL FOR THE |
| | ATRIUM SECTION ONLY (ELEVATION).THIS |
| | INCLUDES ANY CORRIDOR OR ADJACENT SPACES |
| | THAT A CONSIDERED PART OF THE ATRIUM IN |
| | ACCORDANCE WITH 414.5 OF THE 2001 FBC. |
| | |
| | 3.PLAN SHEET AC-01 INDICATES GARAGE |
| | EXHAUST FANS TERMINATING AT THE 1ST |
| | LEVEL.ARCHITECTURAL PLAN A2.04-NW |
| | INDICATES THE WINDOWS ON LEVEL 3 (R03) & |
| | 4 (R04) ARE TO BE FIXED GLASS.PLANS DO |
| | NOT INDICATE THIS AS "TYPICAL" AND DO |
| | NOT SPECIFY IF THE WINDOWS AT LEVEL 2 |
| | ARE FIXED.PER 2001 FMC 401.5, EXHAUST |
| | SHALL BE LOCATED A MINIMUM OF 10FT FROM |
| | LOT LINES & WHERE OPENINGS FRONT ON A |
| | PUBLIC WAY, THE DISTANCE SHALL BE |
| | MEASURED TO THE CENTERLINE OF STREET. |
| | |
| | 4.INTAKE OPENINGS SHALL BE LOCATED A |
| | MINIMUM OF 10FT FROM ANY NOXIOUS |
| | CONTAMINANT, 2001 FMC 401.5.1. |
| | |
| | 5.PLAN SHEET AC-13 LOBBY FLOOR PLAN |
| | INDICATES SF-34 & ON THE EQUIPMENT |
| | SCHEDULE IT INDICATES SF-34 FAN WILL NOT |
| | BE USED.PLEASE CLARIFY. |
| | |
| | 6.PLAN SHEET AC-13 THE MEZZANINE FLOOR |
| | PLAN INDICATES 66" X 14" UP TO SF- ON |
| | ROOF.IT ALSO INDICATES A 22" X 12" |
| | DOWN TO THE 1ST FLOOR.PLEASE INDICATE |
| | IF THIS IS A SHAFT.PLEASE CLARIFY IF |
| | THIS IS FOR THE MAKE-UP AIR FOR THE |
| | ATRIUM OR OUTSIDE AIR FOR THE A/C |
| | SYSTEM.PLEASE NOTE, PER 2001 FMC 607.4 |
| | DUCTS EXTENDING THROUGH MORE THAN ONE |
| | FLOOR SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE.FIRE DAMPERS WILL BE |
| | REQUIRED WHERE DUCTS PENETRATE THE RATED |
| | ENCLOSURE.PLEASE IDENTIFY ALL FIRE & |
| | COMBINATION DAMPERS, 2001 FMC 607.6. |
| | |
| | 7.PLAN SHEET AC-16 NOTE #2 SPECIFIES |
| | "VENTLESS" DRYERS, PLEASE PROVIDE |
| | MANUFACTURER SUBMITTAL DATA. |
| | |
| | 8.LIFE SAFETY & MECHANICAL PLANS |
| | (AC-3) REFER TO A "MEZZANINE" LEVEL |
| | WHEREAS THE ARCHITECTURAL PLANS REFER TO |
| | THIS AREA AS "LEVEL 3", PLEASE |
| | CORRELATE. |
| | |
| | 9.ARCHITECTURAL PLAN (A0.005) |
| | PARTITION/WALL TYPES, DETAILS INDICATE |
| | RATING OF PARTITION/WALL IS TO BE |
| | INDICATED UNDER THE WALL TYPE.THIS IS |
| | NOT REFLECTED ON THE PLANS. |
| | |
| | 10. PROVIDE SEQUENCE OF OPERATION OF THE |
| | SMOKE EVAC FOR THE ATRIUM. |
| | |
| | 11. PLAN SHEET AC-38 THE SEQUENCE OF |
| | OPERATION FOR FLOORS 2 THROUGH 18 |
| | INDICATE PRESSURIZATION BUT DOES NOT |
| | INDICATE THE MITIGATION OF SMOKE.SMOKE |
| | CONTROL SHALL COMPLY WITH ONE OF THE |
| | ITEMS INDICATED IN 2001 FBC 412.5. |
| | |
| | 12. PLEASE ANNOTATE ON THE PLANS, |
| | DISTANCE FROM THE EXHAUST TERMINATIONS |
| | (I.E. GENERATOR, GARAGE, ETC) FROM |
| | WINDOWS, DOORS, FRESH AIR INTAKES, |
| | WALKWAYS, LOT LINES & ADJACENT |
| | BUILDINGS.SHOW COMPLIANCE WITH 2001 |
| | FMC 401.5, 401.5.1 & 501.3. |
| | |
| | PLEASE NOTE RESPONSE TO COMMENTS MAY |
| | CREATE ADDITIONAL COMMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |