| 2005-12-16 00:00:00 | 1. MORE DETAILS REQUIRED ON THE ATRIUM. |
| | THIS WOULD INCLUDE FIRE SEPERATIONS, |
| | DEFINED AREAS, EXITING, AND MECHANICAL |
| | SYSTEMS. VOLUME CALCULATIONS NEEDED. |
| | |
| | 2. DOOR MARKS MISSING FROM LEVEL THREE, |
| | PAGE A1.04C. |
| | |
| | 3. ELEVATOR SHAFTS (TOPS) ON LSO.10 DO |
| | NOT DISPLAY ANY FIRE RATING. |
| | |
| | 4. EXIT SIGNS APPEAR TO BE MISSING ON |
| | PAGE LSO.05A. |
| | |
| | 5. AN ENGINEERING ANALYSIS WILL BE |
| | REQUIRED FOR THE NEW ATRIUM. |
| | |
| | 6. SITE PLAN PAGE A0.03 ONLY DISPLAYS |
| | THREE FIRE HYDRANTS. THIS IS NOT |
| | SUFFICIENT FOR THE SIZE AND COMPLEXITY |
| | OF THIS PROJECT. |
| | |
| | 7. TWO SIDE SWINGING DOORS LOCATED ON |
| | PAGE A1.02C APPEAR TO BE DIRECTLY NEXT |
| | TO CURBING. |
| | |
| | 8. PLEASE HATCH AREA OF ATRIUM. |
| | |
| | 9. PLEASE EXPLAIN BUS DUCT STORAGE ROOM |
| | DOORS. THEY APPEAR TO OPEN TOO FAR INTO |
| | EXIT CORRIDOR. |
| | |
| | 10. PLEASE VERIFY ATRIUM SMOKE SYSTEM |
| | FANS, CFM'S, ETC. THERE APPEARS TO BE |
| | SOME DISCREPANCY WITH INFORMATION. |
| | |
| | 11. COLUMN WAS OBSERVED DIRECTLY INFRONT |
| | OF DOOR LEADING INTO CORRIDOR FOR HEALTH |
| | CLUB, C-101. |
| | |
| | 12. PLEASE DISPLAY EXIT ROUTES FROM |
| | STORAGE 00. |
| | |
| | 13. PARKING CARS, COLUMN, AND SHEER WALL |
| | OBSERVED. |
| | |
| | 14. PLEASE EXPLAIN MEZZANINE. PLEASE |
| | PROVIDE PRESCRIPTIVE REQUIREMENTS |
| | REGARDING MEZZANINE. |
| | |
| | 15. PLEASE PROVIDE DETAILS ON GLASS WALL |
| | SYSTEM AROUND MONUMENTAL STAIR. |
| | |
| | 16. POOL EQUIPMENT ROOM 00 WILL BE |
| | CONSIDERED HAZARDOUS UNTIL SUFFICIENT |
| | INFORMATION IS PROVIDED. |
| | |
| | 17. JANITOR CLOSET AND CLOSET DOOR NEAR |
| | KICHEN C0405 OPPOSE ONE ANOTHER. |
| | |
| | 18. PLEASE IDENTIFY SMALL AREA WITH DOOR |
| | NEAR TOWER 7 ELEVATOR LOBBY. |
| | |
| | 19. WHAT INTERPRETATION IS BEING USED |
| | FOR DOORS OPENING ONTO EXIT ACCESS |
| | CORRIDORS. PLEASE SEE TELLCOM CLOSETS. |
| | |
| | 20. ALL NEW ELEVATORS SHALL COMPLY WITH |
| | ASME A17.1 SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. |
| | |
| | 21. EGRESS SIGN MISSING NEAR STAIR |
| | LOCATED AT G25 LOCATION ON PAGE |
| | A1.05S-2. |
| | |
| | 22. MORE DETAILS NEEDED FOR THE TWO HOUR |
| | RATED SLIDING DOORS SHOWN IN FRONT OF |
| | ELEVATORS. HOW WOULD FIRE RESCUE ACCESS |
| | BEYOND THESE DOORS. |
| | |
| | 23. ON ELEVATION DRAWINGS A REVISION IS |
| | SHOWN FOR ITEM # 4 HOWEVER ON PAGE |
| | A2.02-N ITEM # 7 IS DEPICTED. |
| | |
| | 24. WILL ANY COMBUSTIBLE MATERIALS BE |
| | STORED OR HANDELED UNDERNEATH THE PORTE |
| | COCHERE. |
| | |
| | 25. PLEASE ILLUSTRATE DISTANCES OF FIXED |
| | GLASS ANGLED WINDOWS FOR THE ATRIUM |
| | ENCLOSURE TO TOWER WINDOWS. IT IS |
| | DIFFICULT TO DETERMINE. PLEASE SEE PAGE |
| | A3.05-A. |
| | |
| | 26. WHAT FIRE PROTECTION IS PLANNED FOR |
| | THE CABANA'S. |
| | |
| | 27. DUCTS OVER FOUR FEET WIDE SHALL HAVE |
| | FIRE SPRINKLER PROTECTION BELOW THEM. |
| | |
| | 28. UNIT DOOR AND HARDWARE SCHEDULE DOES |
| | NOT ILLUSTRATE THAT THE GALLERY DOOR TO |
| | THE STAIRWELL IS FIRE RATED. PLEASE |
| | EXPLAIN RATIONALE. PLEASE SEE PAGE |
| | A4.02. |
| | |
| | 29. NO FIRE RATING NOTED ON UNIT DOOR |
| | AND HARDWARE SCHEDULE LOCATED ON PAGE |
| | A4.08. |
| | |
| | 30. SAME CONDITION EXISTS ON PAGES |
| | A4.09-20. |
| | |
| | 31. PRESSURE REGULATING VALVES SHOWN ON |
| | PAGE SP-34. WILL THESE DEVICES BE |
| | FACTORY SET OR FIELD SET. FACTORY SET |
| | ONES ARE PREFERRED. |
| | |
| | 32. NO COMBUSTIBLES ALLOWED IN ANY |
| | RETURN AIR PLENUM. |
| | |
| | 33. PLEASE ILLUSTRATE EMERGENCY LIGHTING |
| | ON RECREATIONAL PLAZA. |
| | |
| | 34. SINCE EXITING IS DIRECTED FROM THE |
| | GARAGE TOWARDS THE FUTURE TENANT |
| | BUILD-OUT AREA ON LEVEL ON PAGE E-03, |
| | PLEASE EXPLAIN HOW THIS WILL WORK. |
| | |
| | 35. SEQUENCE OF OPERATIONS PAGE AC-38 |
| | NEEDS TO BE REVISED. DUCT SMOKE |
| | DETECTORS SHALL INITIATE AN ALARM NOT A |
| | SUPERVISORY SIGNAL. |
| | |
| | 36. ELECTRONIC SWITCHES, CHAINS AND |
| | LOCKS ARE REQUIRED ON THE FIRE LINE |
| | BACKFLOW DEVICE. |
| | |
| | 37. ANY SECURITY DEVICES PLANNED SHALL |
| | NOT INTERFERE WITH ANY REQUIRED EXITING |
| | FROM THE BUILDING. PLEASE REVIEW SPECIAL |
| | LOCKING ARRANGEMENTS IN THE LIFE SAFETY |
| | CODE, 2003 EDITION. |
| | |
| | 38. PLEASE PROVIDE CODE REQUIREMENTS FOR |
| | SECURITY DEVICES ON THE APPROPRIATE |
| | PAGES. |
| | |
| | 39. PLEASE EXPLAIN ELEVATOR CONTROL |
| | PROGRAMMING. ARE THERE GOING TO BE ANY |
| | SPECIAL FEATURES REGARDING THE |
| | ELEVATORS. |
| | |
| | 40. PLEASE PROVIDE FLAME SPREAD FOR CORK |
| | WALLCOVERINGS AND FLOOR, PAGE ID3.04. |
| | |
| | 41. ADDITIONAL FIRE EXTINGUISHERS APPEAR |
| | TO BE REQUIRED. LARGE MECHANICAL AND |
| | SERVICE ROOMS APPEAR TO BE ABSENT OF |
| | THEM. NO FIRE EXTINGUISHERS APPEAR TO BE |
| | SHOWN ON THE OVERALL ROOF PLAN LS0.10. |
| | |
| | 42. COULD NOT LOCATE FIRE EXTINGUISHERS |
| | LOCATIONS FOR LONG CORRIDORS SHOWN ON |
| | PAGE LSO.06. |
| | |
| | 43. STAIR # 8B DISPLAYS 200 BUT IF THE |
| | DOOR CAN ONLY ACCOMODATE 140 PERSONS HOW |
| | DOES THIS WORK. |
| | |
| | 44. STAIRS 10,11,12,AND 13 SHOW LARGE |
| | OCCUPANT LOADS BUT DOORS CAN ONLY |
| | SUPPORT 140 PERSONS. HOW DOES THIS WORK. |
| | |
| | 45. WINDOWS APPEAR TO BE LOCATED |
| | DIRECTLY OPPOSITE OF EXIT STAIR DOORS ON |
| | THE RECREATIONAL DECK. WHAT PROTECTION |
| | IF ANY IS PLANNED. |
| | |
| | 46.STAIR PRESSURIZATION NOTES NEED TO BE |
| | INCORPORATED ONTO THE LIFE SAFETY PLANS. |
| | PLEASE PROVIDE PRESCRIPTIVE |
| | REQUIREMENTS. |
| | |
| | 47. THE STORE THAT IS PLANNED A SEPERATE |
| | TENANT OR WILL BE ANCILLARY TO THE REST |
| | OF THE BUILDING. |
| | |
| | 48. ALL DOORS FOR EXIT ACCESS CORRIDORS |
| | SHALL BE SELF-CLOSING AND SELF-LATCHING. |
| | |
| | 49. LISTED GUICK RESPONSE OR LISTED |
| | RESIDENTIAL FIRE SPRINKLERS SHALL BE |
| | USED IN LIVING AREAS. |
| | |
| | 50. PLEASE REVIEW ALL EXIT ACCESS, |
| | EXITING, AND EXIT DISCHARGE CALCULATIONS |
| | TO ENSURE THEY ARE PROPERLY CALCULATED. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |