| 2005-12-31 00:00:00 | IN ELEC FOR REVIEW, IN PROGRESS |
| | *********** UNSAT 2ND REVIEW ********** |
| | |
| | PALLADIO |
| | 2211 N. FLAGLER DR. |
| | PLANS CONVERTED BACK TO PERMIT> THIS IS |
| | TECHNICALLY THE 2ND REVIEW, HOWEEVR |
| | FIRST REVIEW WAS UNDER "PROJECT"/PLAN |
| | REVIEW. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO NEW |
| | INFORMATION, CHANGES, CODES. |
| | |
| | 1)NOTE: NOTE#1 NO. COULD NOT LOCATE |
| | SPECS AS REQUESTED. |
| | PLEASE SUBMIT ALL MANUFACTURE |
| | SPECIFICATION SHEETS/ CUT SHEETS FOR |
| | FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, |
| | GENERATOR, AUTOMATIC TRANSFER SWITCH |
| | (ATS) AND ANY SUB BASE FUEL TANKS. |
| | PLEASE SURE ALL INFORMATION SUBMITTED |
| | MUST SHOW LISTINGS FROM A NATIONALLY |
| | RECOGNIZED TESTING LAB. (NRTL). |
| | PLEASE BE SURE ALL FIRE PUMP CONTROLLERS |
| | ETC COMPLY WITH NFPA-20 AND OTHER |
| | APPLICABLE CODES. |
| | |
| | 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE |
| | NOTES PERTAINING TO SPECS SUBMITTED. |
| | PLEASE SEE 16450.1 WHICH REFERENCES |
| | CODES FROM THE 1996 NEC. |
| | PLEASE SEE COLOR CODING FOR 277/480V |
| | SYSTEMS SHALL BE BROWN/PURPLE/YELLOW. |
| | PLEASE SEE 16100-2 |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 YES,NO, PLEASE SEE STAIR |
| | AND EGRESS TUNNELS ARE OK, HOWEVER |
| | PLEASE SEE GARAGE AND OTHER EGRESS PATHS |
| | WHICH WILL REQUIRE A MIN OF 1 FT CANDLE. |
| | PLEASE ALSO SEE FIRE REVIOEW COMMENTS |
| | WITH RESPECT TO EM EGRESS LIGHTING FROM |
| | POOL AREA TO PUBLIC RIGHT OF WAY |
| | REQUIRED. |
| | PLEASE ALSO VERIFY THE LOBBY AREAS BEING |
| | USED AS A MEANS OF EGRESS FROM UNITS. |
| | 2003 NFPA-101 7.8.1.3, 7.9.2.2 |
| | ** PLEASE SEE NEW NOTES PERTAINING TO |
| | PHOTO-METRICS. |
| | |
| | 7)NOTE: NOTE #7 YES,NO, PLEASE SEE MOST |
| | WERE ADDED HOWEVER PLEASE SEE E-21 AN |
| | ELECTRICAL RM AND THE FIRE COMMAND RM DO |
| | NOT INDICATE A CHANGE IN FIXTURE TYPE. |
| | 700.16, LS 101 7-9, 90.4 |
| | |
| | 8)NOTE: NOTE #8OK. |
| | |
| | 9)NOTE: NOTE #9OK |
| | |
| | 10)NOTE: NOTE #10, OK. |
| | |
| | 11)NOTE: NOTE #11 OK |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 NO, PLEASE SEE SOME |
| | UNITS MISSING RECEPTS PER 210.52. |
| | PLEASE SEEONE REDLINED SET. |
| | "L" SOUTH, BED RM #3, "N", BR#3 #4, |
| | LOFTS WITH WHAT APPEARS TO BE WALL SPACE |
| | BY STAIRS ON LOWER LEVELS/ WITHIN 6' FRO |
| | THE EDGE. |
| | |
| | 19)NOTE: NOTE #19 NO,PLEASE SEE |
| | CIRCUITING MISSING FROM SOME DEVICES |
| | SHOWN IN SOME OF THE UNITS. PLEASE SEE |
| | SD'S, RECEPTS. |
| | PLEASE SEE REDLINED PLANS AS MOST ARE |
| | CIRCIRLED. |
| | |
| | 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE |
| | SOME AREA DESIGNATIONS ON UNITS ARE NOW |
| | SHOWN WHICH DINING AREAS/BREAKFAST AREAS |
| | ARE ON 15A #14 GEN LT CIRCUITS. |
| | CIR #42 |
| | PLEASE SEE UNIT "N", "Q" |
| | |
| | 21)NOTE: NOTE #21 OK. |
| | |
| | 22)NOTE: NOTE #22 OK. |
| | |
| | 23)NOTE: NOTE #23 OK. |
| | |
| | 24)NOTE: NOTE #24 OK, HOWEVER PLEASE SEE |
| | NEW NOTE FOR ONE GFI LOCATION. |
| | |
| | 25)NOTE: NOTE #25 OK. |
| | |
| | 26)NOTE: NOTE #26 OK. |
| | |
| | 27)NOTE: NOTE #27 OK. |
| | |
| | 28)NOTE: NOTE #28 OK. |
| | |
| | 29)NOTE: NOTE #29 OK. |
| | |
| | 30)NOTE: NOTE #30 OK. |
| | |
| | 31)NOTE: NOTE #31 OK. |
| | |
| | 32)NOTE: NOTE #32 NO. |
| | PLEASE SEE MISSING SMOKE DETECTORS |
| | REQUIRED UNDER NFPA-72 11.5.1.1, |
| | 11.8.3.5 |
| | PLEASE SEE SD'S ARE REQUIRED INSIDE AND |
| | OUTSIDE ALL SLEEPING RMS AND ON EACH |
| | LEVELOF A MULTY LEVEL DWELLING. |
| | PLEASE SEE SOME MISSING, DEN IN UNIT "R" |
| | WILL BE REQUIRED TO HAVE A SD AS IT IS |
| | SHOWN WITH AN ATTACHED BATH OR CLOSET |
| | WHICH MAKES THIS AN ADAPTABLE SLEEPING |
| | RM BY AHJ. PLEASE SEE MISSING SD "Q" |
| | NORTH,LEADING TO FLR ABOVE. |
| | PLEASE SEE SD'S ARE REDLINED AT |
| | LOCATIONS REQUIRED IN OTHER UNITS. |
| | |
| | 33)NOTE: NOTE #33 OK. |
| | |
| | 34)NOTE: NOTE #34 NO, PLEASE SEE THESE |
| | LOBBY AREAS ARE STILL UNCLEAR BY THE |
| | BLDG REVIEW COMMENTS IF THEY BELONG TO |
| | THE UNIT OR PART OF "HOUSE/COMMON" AREA. |
| | PLEASE SEE EXTENSIVE BLDG REVIEW |
| | COMMENTS. |
| | PLEASE SEE 210.25 WHICH STATES NO COMMON |
| | AREAS SHALL CONTAIN ELECTRICAL DEVICES |
| | FED FROM UNITS. IF THESE ARE "PRIVATE" |
| | LOBBIES,PLEASE SHOW HOW THESE AREAS |
| | CONTAIN NUMEROUS ELECTRICAL ITEMS FED |
| | FROM HOUSE POWER? |
| | PLEASE ALSO SEE NEW EXT LTS ETC ADDED TO |
| | UNITS. |
| | |
| | 35)NOTE: NOOTE #35 OK. |
| | |
| | 36)NOTE: NOTE #36 OK. |
| | |
| | 37)NOTE: NOTE #37 NO, PLEASE ADD NOTE TO |
| | THE ROOF TOP PLANS. |
| | PLEASE SEE ANY PROPOSED LIGHTNING |
| | PROTECTION SYSTEM SHALL BE |
| | INSTALLED AND ACCEPTABLE PER NFPA-780. |
| | ALTHOUGH A LIGHTNING PROTECTION SYSTEM |
| | IS NOT SHOWN ON ANY PLANS, PLEASE BE |
| | SURE A NOTE IS PLACED ON "ROOF-TOP" |
| | SHEET WITH REFERENCE TO NFPA-780. |
| | AS NOTED IN MEETING , "LIGHTNING |
| | PREVENTION" SYSTEMS ARE NOT PERMITTED OR |
| | ACCEPTABLE IN THIS JURISTICTION. |
| | |
| | 38)NOTE: NOTE #38 OK, HOWEVER SEE ELEC |
| | NOTES FOR SERVICE. |
| | |
| | 39)NOTE: NOTE #39 OK. |
| | |
| | 40)NOTE: NOTE #40,NO, PLEASE SEE |
| | ELECTRICAL SERVICE WAS MOVED AROUND , |
| | HOWEVER THE INTENT OF ORIGINAL NOTE HAS |
| | NOT BEEN ADDRESSED. PLEASE SEE EM MAIN |
| | HAS NOW BEEN MOVED TO MAIN ELECTRICAL |
| | RM, WHICH WHEN SHUT OFF WILL TRIGGER THE |
| | GEN TO START, TRANSFER POWER OVER TO |
| | HXDP, WHICH IS STILL LOCATED IN THE GEN |
| | RM. THEMCB ADDED TO THE HXDP WOULD NOT |
| | BE READILY ACCESSIBLE, GROUPED OR IN |
| | CLOSE PROXIMITY AND OTHER HAZARDS MAY |
| | PREVENT THE SHUTTING DOWN OF POWER IN A |
| | TIMELY AND SAFE MANOR. |
| | THIS LOCATION WITH A 1500KW GENERATOR |
| | RUNNING AT FULL NOISE LEVEL, HEAT ETC |
| | MAY DISTRACT IN SHUTTING DOWN OF EM |
| | POWER IN A SAFE AND TIMELY FASHION. IT |
| | IS NOTED THAT THESE MAINS AND GEN WILL |
| | HAVE SHUNT TRIPS IN FIRE COMMAND RM, |
| | HOWEVER THESE ARE NOT CONSIDERED AS THE |
| | MEANS OF DISC. 230.76,230.79 |
| | PLEASE SEE IT IS UNCLEAR AT THIS TIME IF |
| | BRKR ON GEN IS LOCATED ON THE OUTSIDE OF |
| | EQUIPMENT WITH A MANUAL MEANS OF |
| | DISCONNECT WITH EXPOSING OF LIVE PARTS. |
| | 110.27. |
| | PLEASE SEE SOME OF THIS CAN NOT BE |
| | VERIFIED AT THIS TIME AS SPECS FOR THIS |
| | EQUIPMENT, GENERATOR ETC WAS NOT |
| | SUBMITTED. |
| | PLEASE SEE ROUTE, LOCATION TRAVEL |
| | DISTANCE ETC MAY BE GONE IN A MEETING |
| | WHICH MAY BE REQUESTED. |
| | |
| | 41)NOTE: NOTE #41 OK. |
| | |
| | 42)NOTE: NOTE #42 OK. |
| | |
| | 43)NOTE: NOTE #43 OK. |
| | |
| | 44)NOTE: NOTE #44 OK. |
| | |
| | 45)NOTE: NOTE #45 OK. |
| | |
| | 46)NOTE: NOTE #46 OK, HOWEVER NO |
| | CONNECTION FOR GEN GROUNDING ELECTRODE |
| | SYSTEM WAS SHOWN. ONLY NOTES TO GEN |
| | FRAME. PLEASE SEE 250.30, AS THIS GEN IS |
| | SEPARATELY DERIVED. |
| | |
| | 47)NOTE: NOTE #47 OK. |
| | |
| | 48)NOTE: NOTE #48 OK. |
| | |
| | 49)NOTE: NOTE #49 OK. |
| | |
| | 50)NOTE: NOTE #50 OK. |
| | |
| | 51)NOTE: NOTE #51 OK. |
| | |
| | 52)NOTE: NOTE #52 OK. |
| | |
| | 53)NOTE: NOTE #53 OK. |
| | |
| | 54)NOTE: NOTE #54 OK. |
| | |
| | 55)NOTE: NOTE #55 OK. |
| | |
| | 56)NOTE: NOTE #56 OK, HOWEVER SEE NEW |
| | NOTE AS PANEL SCHEDULES REVIEWED FOR THE |
| | FIRST TIME. |
| | |
| | 57)NOTE: NOTE #57 OK. |
| | |
| | 58)NOTE: NOTE #58 OK. |
| | |
| | 59)NOTE: NOTE #59 OK. |
| | |
| | 60)NOTE: NOTE #60 OK. |
| | |
| | 61)NOTE: NOTE #61 |
| | |
| | 62)NOTE: NOTE #63, NOPLEASE SEE POOL |
| | WILL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT WHICH IS NOTED ON PLANS. |
| | THIS IS OK, HOWEVER PLEASE KNOW, IF |
| | THERE IS GOING TO BE ANY AFTER DUSK |
| | SWIMMING, THIS WILL HAVE AN IMPACT ON |
| | THE MIN LIGHTING LEVELS AND DESIGN FOR |
| | POOL DECK/EGRESS LIGHTING. PLEASE SEE |
| | OTHER NOTES PERTAINING TO EGRESS.. |
| | IF NIGHT-TIME/AFTER DUSK WILL BE |
| | PROPOSED, SIGNED, SEALED PHOTOMETRICS |
| | WILL BE REQUIRED TO BE SUBMITTED TO PALM |
| | BEACH COUNTY HEALTH DEPT FOR REVIEW AND |
| | STAMPING. |
| | |
| | |
| | |
| | ******* NEW NOTES ************ |
| | |
| | 1)NOTE: PLEASE CORRELATE CONDUCTORS |
| | SHOWN ON HS FOR LS. |
| | 215.5 |
| | PLEASE ALSO LABEL WHICH TRANSFORMER HS |
| | IS FEEDING AS OTHER PANEL SCHEDULES ARE |
| | LABELED. |
| | |
| | 2)NOTE: PLEASE SEE CIRCUITS WHICH |
| | REQUIRE ARC FAULT PROTECTION, PLEASE SEE |
| | "Q", #32, UNIT "A", #28. |
| | |
| | 3)NOTE: PLEASE SEE A "MISPRINT" OF AN |
| | ADDITIONAL "ELEC PANEL" IN UNIT "B". |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE NOTES WITH RESPECT TO |
| | ARC FAULT PROTECTION. NOTE MENTIONS |
| | "RECEPT" WHERE-AS ALL OTHER NOTES WERE |
| | CHANGED TO "OUTLETS". |
| | |
| | 5)NOTE: PLEASE SEE BLDG NOTES PERTAINING |
| | TO MEZZANINE, AND TOWNHOUSE DESIGNATIONS |
| | WHICH ARE ON E-SHEETS AND OTHER |
| | LOCATIONS. |
| | |
| | 6)NOTE: PLEASE PROVIDE THE INFORMATION |
| | AS REQUESTED BY FIRE AND BLDG REVIEW |
| | PERTAINING TO POOL EQUIPMENT ROOM AND |
| | ANY STORAGE OF HAZARDOUS MATERIALS. |
| | ADJUST ELECTRICAL AS NEEDED,PLACE NOTE |
| | ON PLANS. |
| | |
| | 7)NOTE: PLEASE PROVIDE A BUS-DUCT CURB |
| | DETAIL AS REQUIRED PER 368.6, THIS |
| | SHOULD HAVE BEEN REQUESTED ON ORIGINAL |
| | REVIEW. |
| | |
| | 8)NOTE: PLEASE VERIFY NEW NOTE WHICH |
| | MENTIONS A FLOOR? MOUNTED GFI IN BATHRM |
| | FOR JACUZZI TUB IN UNIT "Q". THIS SHALL |
| | NOT BE MOUNTED FACING UP, AND SHOWN BE |
| | OFF THE FLOOR/WET AREA LOCATED UNDER TUB |
| | ACCESS PANEL. |
| | PLEASE SEE MIN CLEARENCES FROM TUBS, |
| | 410.8 |
| | |
| | 9)NOTE: PLEASE KNOW THE FOLLOWING MAY BE |
| | SET-UP AS A "PROVISO" OR MAY BE |
| | ADDRESSED AT THIS TIME. |
| | PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR |
| | STAIRS TOWERS, EGRESS TUNNELS, AND ALL |
| | OTHER PATHS FOR MEANS OF EGRESS AS |
| | PREVIOUSLY NOTED TO PUBLIC RIGHT-OF-WAY. |
| | PLEASE SEE 7.8.1.3, WHICH REQUIRES A MIN |
| | OF 10FT CANDLES(108 LUX) UNDER NORMAL |
| | POWER AT ALL WALKING SURFACES OF |
| | STAIRS/STAIRWAYS. |
| | PLEASE SEE STAIRS CAN BE REDUCED TO .8 |
| | LUX OR 1FT CANDLE UNDER EM POWER/BATTERY |
| | BACK UP. |
| | PLEASE SEE ALL OTHER AREAS FOR EGRESS |
| | MUST HAVE A MIN OF 1 FT CANDLE UNDER |
| | NORMAL AND EM POWER ON ALL WALKING |
| | SURFACES. |
| | |
| | |
| | ** PLEASE SEE MOST OF THE ABOVE |
| | ITEMS ARE REDLINED ON ONE SET OF |
| | ELECTRICAL PLANS, HOWEVER THESE DO NOT |
| | IDICATE ALL POSSIBLE LOCATIONS OF NEEDED |
| | CORRECTIONS. |
| | |
| | **PLEASE KNOW, SOME ITEMS STILL NEED TO |
| | BE VERIFIED ONCE ALL INFORMATION IS |
| | SUBMITTED. |
| | |
| | **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE A |
| | DIRECT EFFECT ON ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE AREA ANY QUESTIONS, |
| | PLEASE DO NOT HESIATE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |