| 2005-10-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A0.04C ACCESSIBILITY REQUIREMENTS |
| | PER SECTIONS 11-4.16.5, 11-4.19.5 AND |
| | 11.4.21.7 TO BE SHOWN ON PLANS. |
| | 2. SHT A0.04.4 DETAIL 04. SUBMIT |
| | CALCULATIONS FOR GRAB BAR BACKING PER |
| | SECTION 609.8 OF THE ANSI A117.1 |
| | STANDARD FOR THE SUPPORTIVE STRUCTURE. |
| | INDICATE GUAGE OF METAL PLATE. |
| | 3. SHT C1 SURVEY NOT SIGNED, SEALED, AND |
| | DATED AS REQUIRED BY FAC 61G15-23.002 & |
| | FS 471.025. |
| | 4. SHTS C-2 THRU C-5 ENGINEERS SEAL |
| | SHALL IMPART INFORMATION REQUIRED BY FAC |
| | 61G15-233.001 & FS 471.025 ON EACH |
| | SHEET. THE INFORMATION REQUIRED ON SEAL |
| | HAS NOT BEEN IMPRESSED ON EACH SHEET AS |
| | REQUIRED. - THE SIGNATURE REQUIRED |
| | APPEARS TO BE INITIALS WHICH ACCORDING |
| | TO FBPE IS NOT APPROVED AND A SIGNATURE |
| | IS REQUIRED. IF INDEED THIS IS YOUR |
| | LEGAL SIGNATURE, PROVIDE A SIGNED, |
| | SEALED, DATED, AND NOTORIZED LETTER |
| | INDICATING YOUR LEGAL SIGNATURE FOR OUR |
| | FILES. |
| | 5. SHTS L-1, L4, AND IR-1 THRU IR-5, NO |
| | INFORMATION ON THE SEAL HAS BEEN |
| | IMPRESSED ON THE SHEETS AS REQUIRED BY |
| | FAC 61G1-16.001. ALSO THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER AND THE PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT |
| | SHALL APPEAR ON THE TITLE BLOCK PER FAC |
| | 61G1-16.004(2) & (6) AND FS 481.219, |
| | 481.2055. |
| | 6. SHT A1.02C DETAIL 04 SHOW TURNING |
| | AREA IN THE STAFF TOILET AS REQUIRED BY |
| | SECTION 11-4.22.3. |
| | 7. SHT A1.02C DETAIL 01 SHOW TURNING |
| | AREA IN THE RESTROOMS, NOT IN THE |
| | STALLS. SECTION 11-4.22.3 |
| | 8. SHT A1.02C A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTIONS AND WITH |
| | SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 9. SHT 1.05C DETAIL 02 SHOW THE TURNING |
| | AREA IN RESTROOM NOT IN THE STALL. |
| | SECTION 11-4.22.3 |
| | 10. PLEASE INDICATE IF THE KITCHEN WILL |
| | BE BUILT-OUT ON THIS PERMIT OR WILL IT |
| | BE A SEPARATE PERMIT, AS THE PLANS WILL |
| | HAVE TO BE ROUTED TO DBPR RESTURANT AND |
| | HOTEL DIVISION PRIOR TO APPROVAL. |
| | SECTION 101.4.7. |
| | 11. SHTS A1.05, A1.09, A1.10, & A1.11. |
| | SS-1 SUBMIT CALCULATIONS FOR PRIMARY & |
| | SECONDARY ROOF DRAINS. SHOW TOTAL AREA, |
| | 1/2 AREA OF ALL VERTICAL WALLS, |
| | (INCLUDING PARAPETS), ALL AREAS OF ROOFS |
| | ADDED TO ROOF AREA FROM ABOVE ADDED TO |
| | ROOF AREA IN CALCULATIONS. INDICATE |
| | TOTAL AREA DRAINED BY EACH ROOF DRAIN. - |
| | THIS IS REQUIRED FOR EACH ROOF LEVEL AND |
| | FOR THE RECREATION LEVEL. SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS |
| | AND SCUPPERS. INDICATE THE SIZE OF ALL |
| | SCUPPERS AND SUBMIT A DETAIL SHOWING THE |
| | HEIGHT, WIDTH AND THE HEIGHT OF THE FLOW |
| | LINE OFF THE ROOF. SECTIONS 1106 & 1107 |
| | AND ALL SUBSECTIONS. |
| | 12. SHT A4.01 TYPICAL UNIT 'AN' SHOW |
| | BACKING & OPENING DIMENSIONS FOR THE W/C |
| | OPENINGS FOR ADDITIONAL BATHROOMS PER |
| | BATHROOM REQUIREMENTS PAGE 7.35. THIS |
| | WILL BE REQUIRED FOR SHT A4.02 UNIT 'AS' |
| | SHT A4.03 UNIT 'BS', SHT A4.04 UNIT |
| | 'BSM', SHT A4.05 UNIT 'CN', SHT A4.06 |
| | UNIT 'CNM', A4.07 UNIT 'CS', SHT A4.15 |
| | UNIT 'FS2', A4.16 UNIT 'GN', SHT A4.20 |
| | UNIT 'KN', SHT A4.22 UNIT 'LS', SHT |
| | A4.23 UNIT 'MN1', SHT A4.24 UNIT 'MN2', |
| | SHT A4.25 UNIT 'MNM', SHT A4.26 UNIT |
| | 'MS1', SHT A4.27 UNIT 'MS2', SHT 4.28 |
| | UNIT 'MSM', SHT A4.29.1 UNIT 'NS', SHT |
| | A4.30.1 UNIT 'PS', SHT A4.31.1 UNIT |
| | 'QN', SHT A4.32 UNIT 'RN', SHT A4.33 |
| | UNIT 'RS', SHT A4.34 UNIT 'SN', SHT |
| | A4.35 UNIT 'SNM', SHT A4.36 UNIT 'TS', |
| | SHT A4.37 UNIT 'TSM', UNIT A4.41.1 UNIT |
| | 'LTN', SHT A4.42.1 UNIT 'LTS', & SHT |
| | A4.31.1 UNIT 'STSM'. |
| | 13. SHTS A4.10 - A4.16 CLEAR FLOOR SPACE |
| | SHALL BE FLUSH WITH THE CONTROL WALL FOR |
| | SHOWERS AND PARALLEL TO SHOWER. PAGE |
| | 7.56. |
| | 14. SHT A4.36 SUBMIT USABLE BATH DETAIL. |
| | 15. SHT A4.37 SUBMIT USABLE BATH DETAIL. |
| | 16. SHTS A4.38, A4.39, & A4.40 ENTRY |
| | LEVEL TO BE COVERED PER FHA. SUBMIT |
| | DETAILS FOR BATHROOMS. |
| | 17. GROUND FLOOR CONFERENCE ROOM SINKS |
| | SHALL BE ACCESSIBLE. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. |
| | 18. SHT P-1 REGULATORS SHOW 7"W/C - |
| | TABLE 402(2) IS FOR 1/2 PSI WHICH IS 11" |
| | TO 14"W/C. PLEASE CLARIFY AND VERIFY |
| | INPUT PRESSURE FOR GAS SYSTEM. |
| | 19. SHT P-1 INDICATE MATERIAL TO BE USED |
| | FOR THE REGULATOR VENT PIPING. (NON |
| | COMBUSTABLE REQUIRED). |
| | 20. GAS RISER INDICATES 6396 MBH, BUT |
| | ADDS UP TO 6196 MBH. PLEASE CLARIFY. - |
| | LAST PIPE SECTION TO SPA @ 300 MBH SHALL |
| | BE 1" NOT 3/4" AS SHOWN. TABLE 402(2). - |
| | ALL PIPE SECTIONS SHALL SHOW THE LENGTH |
| | OF EACH SECTION ON THE RISER DIAGRAM. |
| | SOME SECTIONS DO NOT SHOW A LENGTH. |
| | 21. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT: |
| | A. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | B. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | (DOWNSTREAM OF REGULATOR). |
| | C. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | 22. SEPARATE GAS PERMIT REQUIRED. AT |
| | TIME OF APPLICATION, CONTRACTOR SHALL |
| | SUBMIT A PICTURE I.D. OF THE WELDER, |
| | WELDING CERTIFICATION, AND A COPY OF THE |
| | WELDING PROCEDURE. |
| | 23. ALL FLOOR PLAN SHEETS, SHOW THE |
| | LOCATION & NUMBER OF EACH RISER THRU THE |
| | BUILDING ON EACH FLOOR PLAN AND EACH |
| | LEVEL. SECTION 104.2.1. |
| | 24.SHT P-2 RISER DESIGNATIONS 35, 36, |
| | 45, 46, 46A, & 47 ARE NOT SHOWN. |
| | 25. SHT P-2 SHOW THE PIPING FOR ALL |
| | TRENCH DRAINS WITH PIPE SIZES. THIS |
| | SHALL BE REFLECTED ON THE STORM RISER |
| | DIAGRAM. SECTION 104.3.1.1. |
| | 26. GREASE INTERCEPTOR SHALL BE SIZED BY |
| | THE ENVIRONMENTAL COMPLIANCE MANAGER. |
| | WASTE ORD. #3434. PLEASE CONTACT LYNN |
| | MASSON AT (561) 822-2271, FAX (561) |
| | 822-2279 OR E-MAIL [email protected]. |
| | 27. SHT P-4 RAIN WATER LEADERS, SHOW ALL |
| | PIPE SIZES. RECALCULATE ADDITION ON SOME |
| | RWL'S, INDICATE RWL RISER NUMBERS, 3" |
| | OVERFLOW SHOWN CONNECTING TO PRIMARY |
| | SYSTEM AT COL. 24 BETWEEN COLS, A&B. |
| | PLEASE CLARIFY. SECTION 104.2.1. - SHOW |
| | ALL SECONDARY ROOF DRAINS, WITH PIPE |
| | SIZES, SF, ECT. INDICATE SF OF DRAIN |
| | BETWEEN COLS. S.06 & S.05 BETWEEN COLS. |
| | 20 & 21, AND THE DRAIN BETWEEN COLS. H & |
| | I, AND BETWEEN COLS 18 & 19. |
| | 28. SHT P-4 STATES "3"S FOR CONT. SEE |
| | P-4 HEALTH CLUB". THIS WAS NOT FOUND ON |
| | SHT P-4. PLEASE CLARIFY. |
| | 29. SHT P-4 INDICATE WHAT THE |
| | DESIGNATION FOR "DL" REPRESENTS. |
| | 30. SHT P-7 RISER DESIGNATIONS 35, 36, |
| | 38, 45, 46, & 46A NOT SHOWN. PLEASE SHOW |
| | ALL RISERS FOR EACH FLOOR LEVEL. SECTION |
| | 104.2.1. |
| | 31. SHT P-7 SANT. PIPING NOT ALLOWED IN |
| | THE EGRESS STAIRWAY. NFPA-101 SECTION |
| | 7.1.3.2.1(6). |
| | 32. SHT P-8 OFFSETS SHOWN FOR RISERS 6, |
| | 10, 11, 12, 15, & 17, 18, 19, 20 ARE NOT |
| | SHOWN ON THE RISER DIAGRAMS. SECTIONS |
| | 104.2.1, & 104.3.1.1. |
| | 33. SHT P-9 OFFSETS SHOWN FOR RISERS 42, |
| | 44, 47, 30, 34, 35, 36, 21, 25, 1, AND |
| | TO TOILET ROOMS RECREATION LEVEL 4 ARE |
| | NOT SHOWN NO THE RISER DIAGRAMS. |
| | SECTIONS 104.2.1, & 104.3.1. |
| | 34. SHT P-9SHOW THE TYPICAL PIPING |
| | LAYOUTS FOR RISERS 16, 22, 28, & 29. |
| | SECTION 104.3.1.1. |
| | 35. SHT P-9 THE FOLLOWINGPIPING |
| | LAYOUTS DO NOT REFLECT RISER DIAGRAMS |
| | 44, 47, 42, 40, 39, 20, & 4. SECTION |
| | 104.2.1. |
| | 36. SHT P-13 PIPING FOR THE DWV AND |
| | STORM SYSTEMS NOT APPROVED IN EGRESS |
| | STAIRWAYS. NFPA-101 SECTION 7.1.3.2.1(6) |
| | AND SECTION 1006.1.3.1. |
| | 37. P-14. CONDENSATE IS INDICATED AS 5' |
| | SEPARATION FOR THE SUPPORTS. INDICATE |
| | MATERIAL FOR CONDENSATE PIPING. IF PVC, |
| | MAXIMUM 4' SEPARATION OF SUPPORTS PER |
| | TABLE 305.5. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH 140 MPH WIND LOAD FOR |
| | SUPPORTS. |
| | 38. SHT P-15 PIPING OFFSETS NOT SHOWN ON |
| | RISER DIAGRAM 56, 59A, 92, 93, 94, 95, |
| | 96, 97, 98, 99, & 100. |
| | 39. SHT P-15 PIPING NOT APPROVED IN |
| | EGRESS STAIRWAYS. NFPA-101 SECTION |
| | 7.1.3.2.1(6). |
| | 40. SHT P-15 RISER DIAGRAM 72 NOT SHOWN |
| | ON SHEET. SECTION 104.2.1. |
| | 41. SHT P-15 THE FOLLOWING PIPING |
| | LAYOUTS DO NOT REFLECT THE RISER |
| | DIAGRAMS: 48, 48A, 49, 50, 51, 56, 58, |
| | 59, 59A, 61, 62, 64, 67, & 67A. - NOT |
| | ALL PIPING SHOWN ON THE RISER DIAGRAMS. |
| | SECTION 104.3.1.1. |
| | 42. SHT P-16 NO PIPING TO W/M SHOWN AT |
| | EITHER SIDE OF STAIRS COL. LINE N.05, |
| | BETWEEN UNITS NLT103 & NLT104. INDICATE |
| | WHICH RISERS THESE W/M'S CONNECT TO. |
| | SECTION 104.2.1. |
| | 43. SHT P-17 MAXIMUM 6' FROM POINT OF |
| | VENT TO TUB TRAP. (NEAR RISER 95) TABLE |
| | 906.1. |
| | 44. SHT P-17 THE FOLLOWING RISERS DO NOT |
| | REFLECT PIPING LAYOUT: 50, 51, 52, & 55. |
| | SECTION 104.2.1. |
| | 45. SHT P-18 INDICATED AS LEVEL (5-15) |
| | PLEASE CLARIFY. |
| | 46. SHT P-18 RISER 102 INDICATES 3"V DN |
| | TO RISER #34. THIS IS NOT SHOWN ON SHT |
| | P-17 NOR ON RISER 102. PLEASE CLARIFY. |
| | SECTION 104.2.1. - WHAT IS RISER #3W? |
| | WHERE IS IT LOCATED? SECTION 104.2.1. |
| | 47. SHT P-20 PIPING FOR KIT SINKS NOT |
| | SHOWN. RISER #61. SECTION 104.3.1. |
| | 48. SHT P-22 CONDENSATE LINE SHOWN AS 5' |
| | SEPARATION BETWEEN SUPPORTS. INDICATE |
| | TYPE OF MATERIAL. IF PVC PER TABLE 305.5 |
| | MAXIMUM 4' SEPARATION BETWEEN SUPPORTS. |
| | SUBMIT A DETAIL FOR SUPPORTS SHOWING HOW |
| | THEY ARE ATTACHED TO THE ROOF AND SHOW |
| | COMPLIANCE WITH 140 MPH WIND LOAD. |
| | 49. SHT P-23 BATHROOM MAIN LOBBY LEVEL 1 |
| | SHOWN 36FU, BUT IS SHOWN AS 34FU ON SHT |
| | P-2. CORRELATE PLANS. SECTION 104.2.1. |
| | 50. SHT P-23 RECREATION AT LEVEL 4 |
| | PIPING DOES NOT REFLECT THE FIXTURE |
| | LAYOUT. PLEASE CORRELATE FIXTURE LAYOUT |
| | WITH PIPING LAYOUT. SECTION 104.2.1. |
| | (RISER DIAGRAM DOES NOT REFLECT FIXTURE |
| | LAYOUT EITHER). |
| | 51. SHT P-23 RECREATION AT LEVEL 2 |
| | INDICATES 40FU FOR FUTURE GYM, BUT ONLY |
| | 44FU AFTER ADDING MEN'S & WOMEN'S TOILET |
| | ROOMS. PLEASE RECALCULATE FU'S. (ALSO |
| | ADJUST ON RISER DIAGRAM). SECTION |
| | 104.2.1. |
| | 52. SHT P-23 RISER DIAGRAMS STATE "FOR |
| | CONT. SEE P-68". P-68 SHOWS STORM RISER |
| | ONLY. PLEASE CLARIFY. SECTION 104.2.1. |
| | 53. SHT P-39 FLOOR DRAIN NOT SHOWN |
| | BETWEEN 1ST & 2ND WLI UNITS FIRST FLOOR. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 54. SHT P-52 SANT. RISER DIAGRAM UNIT |
| | TOWNHOME, MAXIMUM 4FU ON 2" WET VENT PER |
| | TABLE 909.3. |
| | 55. SHT P-52 RISER DIAGRAMS STATE "FOR |
| | CONT. SEE P-69". CONT. NOT FOUND ON |
| | P-69. PLEASE CLARIFY. SECTION 104.2.1. |
| | 56. SHT P-53 RISER 13 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SECTION 914.1. |
| | - DRY HORIZONTAL VENTS NOT APPROVED 17TH |
| | FLOOR. SECTIONS 905.3/905.4. |
| | 57. SHT P-53 RISER 8 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SECTION 914.1. |
| | 58. SHT P-54 RISER 10 LOWER OFFSET VENT |
| | REQUIRED. SECTION 915.3. - HORIZONTAL |
| | BRANCH CONNECTIONS NOT APPROVED ON THE |
| | HORIZONTAL OFFSET. SECTION 711.2 |
| | 59. SHT P-54 RISER 12 LOWER OFFSET VENT |
| | REQUIRED. SECTION 915.3. - MAX 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SECTION 914.1. |
| | - 4" VENT TO RISER #8 READS "FROM RISER |
| | 8. PLEASE CORRELATE RISERS. SECTION |
| | 104.2.1. |
| | 60. SHT P-54 RISER 14 LOWER OFFSET VENT |
| | REQUIRED. SEC. 915.3 - MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. |
| | 61. SHT P-54 RISER 17 LOWER OFFSET VENT |
| | REQD. SEC. 915.3. - MAX 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SECT. 914.1. |
| | 62. SHT P-55 RISER 20 BATHROOM SHOWN ON |
| | 4TH FLOOR ON FLOOR PLAN, BUT SHOWN ON |
| | 5TH FLOOR ON RISER. CORRELATE RISER AND |
| | FLOOR PLAN. SEC. 104.2.1. - W/M FOR 16TH |
| | FLOOR NOT SHOWN ON RISER. SEC. 104.2.1. |
| | 63. SHT P-55 RISER 22 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. |
| | 64. SHT P-55 RISER 23 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| | LOWER OFFSET VENT REQD. SEC. 915.3. |
| | 65. SHT P-56 RISER 25 SINK MISSING 17TH |
| | FLOOR. SEC. 402.1.1. |
| | 66. SHT P-56 RISER 26 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO BRANCH CONNECTIONS ON HORIZONTAL |
| | OFFSET. SEC. 711.2. |
| | 67. SHT P-56 RISER 28 NO HORIZONTAL DRY |
| | VENTS. SEC. 905.3/905.4 (16TH FLOOR) |
| | 68. SHT P-56 RISER 29 LOWER OFFSET VENT |
| | REQD. SEC 915.3. - NO CONNECTION TO |
| | HORIZONTAL OFFSET. SEC. 711.2. |
| | 69. SHT P-56 RISER 30 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENTS. SEC. |
| | 905.3/905.4 |
| | 70. SHT P-56 RISER 32 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1 - |
| | NO HORIZONTAL DRY VENTS. SEC. |
| | 905.3/905.4. - UPPER OFFSET VENT REQD. |
| | SEC. 915.2. - SEPARATE RISER SECTION AT |
| | BASE OF STACK FOR POWDER ROOM, INDICATE |
| | RISERS CONNECTING FROM UPSTREAM. (33, |
| | 37, 37A) SEC. 104.2.1. |
| | 71. SHT P-56 RISER 33 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENT. SEC. 905.3/905.4 |
| | - DOES NOT REFLECT FLOOR PLAN @ 4TH |
| | LEVEL. (BASE OF STACK) SEC. 104.2.1. - |
| | VENT FROM 1ST FLOOR FLOOR DRAIN NOT |
| | SHOWN ON RISER. (SEE P-3, P-4, P-67). |
| | 72. SHT P-57. RISERS 39, 40,41, 42, 43, |
| | 44 DO NOT REFLECT THE FLOOR PLANS AT THE |
| | BASE OF RISER. SEC. 1-4.2.1. |
| | 73. SHT P-57 RISER 42 VENT FROM FIRST |
| | FLOOR FLOOR DRAINS NOT SHOWN. PLEASE |
| | CLARIFY. SEC. 104.2.1. |
| | 74. SHT P-58 RISERS 45, 46, 47 DO NOT |
| | REFLECT FLOOR PLANS FOR 4TH LEVEL. |
| | SECTION 104.2.1. |
| | 75. SHT P-59 RISER 50 DOES NOT REFLECT |
| | THE FLOOR PLAN 4TH LEVEL. SEC. 104.2.1. |
| | 76. SHT P-59 RISER 51 DOES NOT REFLECT |
| | THE FLOOR PLAN AT BASE OF RISER AND ON |
| | THE 4TH LEVEL. PLEASE CLARIFY SEC. |
| | 104.2.1. |
| | 77. SHT P-59 RISER 52 DOES NOT REFLECT |
| | FLOOR PLAN LEVEL 2. - UPPER OFFSET VENT |
| | REQUIRED. SEC. 915.2. |
| | 78. SHT P-59 RISERS 53, 55 DO NOT |
| | REFLECT THE FLOOR PLAN 4TH LEVEL. |
| | SECTION 104.2.1. |
| | 79. SHT P-60 RISER 56 DOES NOT REFLECT |
| | THE FLOOR PLAN 3RD LEVEL. - OFFSET VENTS |
| | REQD. SECS. 915.2/915.3. - MAX. 10 |
| | BRANCH INTERVALS TO RELIEF VENT. SEC. |
| | 914.1. - NO CONNECTIONS TO HORIZONTAL |
| | OFFSET. SEC. 711.2.- NO HORIZONTAL DRY |
| | VENTS. SECS. 905.3/905.4. |
| | 80. SHT P-60 RISER 58 DOES NOT REFLECT |
| | THE FLOOR PLAN, CHECK LOCATION OF |
| | CONNECTION OF RISER 59. - RISER 58 & 61 |
| | NOT TIED TOGETHER ON FLOOR PLAN. - UPPER |
| | OFFSET VENT REQD. 915.2 |
| | 81. SHT P-60 RISER 61 DOES NOT REFLECT |
| | THE FLOOR PLAN LEVEL 17. SEC. 104.2.1. |
| | 82. SHT P-60 RISER 57 DOES NOT REFLECT |
| | THE FLOOR PLAN UPPER LEVEL. - MAX 10 |
| | BRANCH INTERVALS TO RELIEF VENT. SEC. |
| | 914.1. |
| | 83. SHT P-60 RISER 60 DOES NOT REFLECT |
| | THE FLOOR PLAN. SHOWS CONNECTING TO |
| | HORIZONTAL DRAIN LINE. (GROUND FLOOR?) - |
| | UPPER OFFSET VENT REQD. SEC. 915.2. - |
| | DOES NOT REFLECT THE FLOOR PLAN AT THE |
| | TOP OF THE RISER. - MAX 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. |
| | 84. SHT P-61 RISER 62 DOES NOT REFLECT |
| | THE FLOOR PLAN. - LOWER OFFSET VENT REQD |
| | SEC. 915.3. |
| | 85. SHT P-61 RISERS 63, 64 DO NOT |
| | REFLECT THE FLOOR PLAN. PLEASE CLARIFY |
| | SEC. 104.2.1. |
| | 86. SHT P-61 RISER 67 MAX 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO HORIZONTAL DRY VENTS. SECS. 905.3 |
| | 905.4. |
| | 87. SHT P-61 RISER 67A DOES NOT REFLECT |
| | THE FLOOR PLAN. - LOWER OFFSET VENT REQD |
| | SEC. 915.3. |
| | 88. SHT P-61 RISER 68 FIXTURES NOT SHOWN |
| | FOR 4TH LEVEL ON THE RISER. PLEASE |
| | CLARIFLY. SECTION 104.2.1. |
| | 89. SHT P-62 RISER 70 LOWER OFFSET VENT |
| | REQD. SEC 915.3 |
| | 90. SHT P-62 RISER 71 MAX. 10 BRANCH |
| | INTERVALS TO RELIEF VENT. SEC. 914.1. - |
| | NO DRY HORIZONTAL VENT. SECS. 905.3 |
| | 905.4. |
| | 91. SHT P-62 RISER 72 DOES NOT REFLECT |
| | THE FLOOR PLAN PIPING LAYOUT LEVEL 3. |
| | SECTION 104.2.1. |
| | 92. SHT P-62 RISER 73 & 74 MAX. 10 |
| | BRANCH INTERVALS TO RELIEF VENT. SEC. |
| | 914.1. |
| | 93. SHT P-62 RISER 74A DOES NOT REFLECT |
| | THE FLOOR PLAN LEVEL 4. SECTION 104.2.1. |
| | 94. SHT P-62 RISER 79 DOES NOT REFLECT |
| | THE FLOOR PLAN PIPING LAYOUT LEVEL 4. |
| | SEC. 104.2.1. |
| | 95. SHT P-63 RISERS 75,76,77,78,87,88 |
| | DO NOT REFLECT THE FLOOR PLAN PIPING |
| | LAYOUTS LEVEL 4. SECTION 104.2.1. |
| | 96. SHT P-63 RISER 80 FLOOR DRAIN LEVEL |
| | 16 ROOF NOT SHOWN ON RISER DIAGRAM. |
| | SECTION 104.2.1. CORRELATE RISER/FLOOR |
| | PLAN. |
| | 97. SHT P-63 RISERS 89,94,95,99,101,102 |
| | & 103 DO NOT REFLECT THE FLOOR PLANS. |
| | SECTION 104.2.1. |
| | 98. SHT P-67 HORIZONTAL SANT. RISER |
| | DIAGRAM MISLABELED AS "WATER RISER |
| | DIAGRAM". PLEASE CLARIFY. SEC. 104.2.1. |
| | 99. SHT P-67 FOLLOWING ARE CORRECTIONS |
| | TO BE MADE TO SANT. RISER DIAGRAM: - |
| | RISERS 35 & 36 NOT SHOWN. - PIPING |
| | LAYOUT DOWNSTREAM OF RISER 33,37,37 DOES |
| | NOT REFLECT FLOOR PLAN FOR POWDER ROOM. |
| | - RISERS 23 & 23A MISLABELED. - 2" VENT |
| | UP TO RISER 42 NOT SHOWN ON RISER 42. - |
| | PIPING BETWEEN RISERS 6,10,11,12,15 & |
| | RISER 9,13 DOES NOT SHOW POWDER ROOM OR |
| | WASH MACHINE. - OFFSETS & PIPING LAYOUT |
| | SHOWN ON SHT P-9 ARE NOT SHOWN ON RISER |
| | DIAGRAM. - NO VENT SHOWN FOR GREASE |
| | LINE. - GREASE LINE DOES NOT REFLECT THE |
| | FLOOR PLAN, AND IS NOT SHOWN ON FLOOR |
| | PLANS P-15 THRU P-18. -4"-34FU FOR CONT. |
| | SEE P-23 SHOWS 36FU ON SHT P-23. |
| | CORRELATE SHEETS. - 2" VENT FROM 2 SINKS |
| | SHOWS 3" VENT ON SHTS P-3, P-4, & P-5. |
| | CORRELATE SHEETS. - 2" VENT UP TO RISER |
| | 67 TO READ "TO RISER 67A". (SEE RISER |
| | 67A). - "2" VENT FOR CONT. SEE P-53" |
| | INDICATE RISER VENT WILL CONNECT TO. - |
| | "UNITS WL1, WL2 & UNITS 1T THRU 10T, |
| | 4"-28FU FOR CONT. SEE P-53. NOT FOUND ON |
| | SHT P-53. PLEASE CLARIFY - 6" LINE FROM |
| | RISER 92,93,94,95,96,97,98, 99,100 DOES |
| | NOT SHOW OFFSET ON RISER SHOWN ON SHT |
| | P-15. - THIS SHEET SHOWS LEVELS AS PARK, |
| | PARK 2, PARK 3 ECT., BUT SHEETS P-15, |
| | P-16. & P-17 SHOWS LEVELS AS GROUND |
| | FLOOR, PARTIAL N. RES. LOFTS, N. LOFTS |
| | MEZZ. ECT. PLEASE CLARIFY & CORRELATE |
| | SHEET LEVELS. - RECHECK ADDITION OF |
| | FIXTURE UNITS AS THEY ACCUMULATE IN THE |
| | SYSTEM. SOME FIXTURES UNITS ARE NOT |
| | SHOWN AND ADDED TO THE SYSTEM. INDICATE |
| | THE SLOPE OF THE PIPE WHERE THE FIXTURES |
| | UNITS ARE MORE THAN ALLOWED FOR MINIMUM |
| | SLOPE. ALL PIPE IN A GIVEN RUN SHALL BE |
| | INSTALLED IN A UNIFORM SLOPE AS REQUIRED |
| | IN SECTION 704.1. INDICATE ON PLANS. |
| | SECTION 104.2.1. |
| | 100. SHT P-68 HORIZONTAL STORM RISER |
| | DOES NOT REFLECT STORM PIPING IN |
| | BUILDING. STRUCTURES S1 THRU S9 NOT |
| | SHOWN. - NO ROOF DRAINS 2650SF, 2350SF, |
| | 2450SF ECT. FOUND. - NO EXFILTRATION |
| | TRENCHES FOUND. - NO TRENCH DRAINS |
| | FOUND, RISERS SHOWS 25TH, 26TH, 27TH |
| | FLOORS ECT. - NO POINT OF REFERENCE TO |
| | FLOOR PLAN CAN BE FOUND. - RISER HARD TO |
| | READ, PLEASE INCREASE THE SIZE OF THE |
| | STORM RISER DIAGRAM AND POSSIBLY SPLIT |
| | UP TO TWO PAGES TO MAKE RISER EASIER TO |
| | READ. SECTION 104.2.1.3. |
| | 101. SUBMIT A CONDENSATE RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES AND INDICATE |
| | MATERIAL. SECTION 104.3.1.1. |
| | 102. SUBMIT A P/T VALVE DISCHARGE RISER |
| | DIAGRAM SHOWING ALL PIPE SIZES AND |
| | INDICATE PIPING/FITTING MATERIAL. |
| | SECTION 104.3.1.1. |
| | 103. SUBMIT AN EMERGENCY PAN DRAIN RISER |
| | DIAGRAM FOR THE WATER HEATERS. INDICATE |
| | PIPE SIZES AND MATERIAL FOR PIPE AND |
| | FITTINGS. |
| | 104. BACKFLOW PROTECTION REQUIRED FOR |
| | IRRIGATION, POOLS, TRASH CHUTE WASH |
| | DOWN, AND COOLING TOWER MAKE UP WATER. |
| | SECTION 608. INDICATE METHOD OF |
| | PROTECTION FOR EACH SYSTEM. |
| | 105. PLANS ARE INCOMPLETE AT THIS TIME |
| | AND MORE COMMENTS MAY BE FORTHCOMING |
| | WITH THE NEXT REVIEW. |
| | **************************************** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | **************************************** |
| | **************************************** |