| 2005-08-24 00:00:00 | PLAN DENIED |
| | 1) PAGE AC-6 AND AC-7 NEED SMOKE FIRE |
| | DAMPERS AT RATED CHASE. |
| | 2) PAGE AC-9 NEED DUCT DETECTORS ON ALL |
| | PACKAGE UNITS OVER 2000 CFM.SECTION |
| | 606.2.1 FBC(M) |
| | 3) PAGE AC-9 PLEASE SHOW MOUNTING DETAIL |
| | ON A/C DUCT STANDS. |
| | 4) PLEASE SHOW SEQUENCE OF OPERATION FOR |
| | SF.35 AND SF.37. |
| | 5) PLEASE REFER TO SECTION 501.5 METAL |
| | DUCT. |
| | 6) GARAGE VENTILATION MUST RUN |
| | CONTINUOUSLY.PLEASE REMOVE CO2 SENCERS |
| | 7)PAGE AC-32PLEASE REMOVE SMOKE |
| | DETECTORS FROM |
| | SF9,15,17,11,13,19 STAIR RISER |
| | UNITS |
| | 1) PLEASE INDECATE TYPE OF DOORS USED ON |
| | A/C CLOSITS ON PLANS. |
| | 2) A/C UNITS OVER 2000 CFM INCLUDING |
| | COMBINED AIRWITH TWO A/C UNITSMUST |
| | HAVE FAN SHUTDOWN SECTION 606.2.1 |
| | 3) PLEASE REFER TO SECTION 601.4 |
| | BALANCED RETURN AIR. |
| | 4) DRYER BOOSTER FANS MUST BE SUBMITED |
| | THROUGH ALTERNATIVE METERALS ,METHODS. |
| | 5) NEED SMOKE FIRE DAMPERS IN ALL DUCT |
| | GOING THROUGH RATED WALLS IN LOBBEYS. |
| | 6) PLEASE REFER TO SECTION 307.2.3 |
| | AUXILIARY DRAIN PANS. |
| | 7) PLEASE REFER TO SECTION 602.2.1 |
| | MATERALS EXPOSED WITHIN PLENUMS. |
| | 8) PLEASE REFER TO SECTION 401.6 OUT |
| | DOOR OPENING PROTUCTION (BATHROOM |
| | EXHAUST CAPS NEED SCREENS) |
| | 9) PLEASE REFER TO SECTION 601.4 |
| | BALANCED RETURN AIR #3 HABITABLE ROOMS. |
| | 10) PAGE AC-20 RETURN AIR GRILL IS NOT |
| | IN RETURN AIR PLENUM. |
| | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
| | |