| 2005-08-23 00:00:00 | *********** UNSAT *************** |
| | |
| | PALLADIO |
| | 2211 N. FLAGLER DR. |
| | PLANS SUBMITTED AND UNDER "PLAN REVIEW" |
| | ONLY. BROUGHT IN FOR PERMIT,HOWEVER PLAN |
| | REVIEW DONE UNDER PLAN REVIEW. |
| | |
| | 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECIFICATION SHEETS/ CUT SHEETS FOR |
| | FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, |
| | GENERATOR, AUTOMATIC TRANSFER SWITCH |
| | (ATS) AND ANY SUB BASE FUEL TANKS. |
| | PLEASE SURE ALL INFORMATION SUBMITTED |
| | MUST SHOW LISTINGS FROM A NATIONALLY |
| | RECOGNIZED TESTING LAB. (NRTL). |
| | PLEASE BE SURE ALL FIRE PUMP CONTROLLERS |
| | ETC COMPLY WITH NFPA-20 AND OTHER |
| | APPLICABLE CODES. |
| | |
| | 2)NOTE: PLEASE SEE SPEC BOOKS SUBMITTED |
| | ARE NOTED AS ELECTRICAL MECHANICAL SPECS |
| | BY OTHERS? |
| | PLEASE BE SURE THESE ARETO BE |
| | SUBMITTED AT THIS TIME. |
| | |
| | 3)NOTE: PLEASE SEE MAIN ELECTRICAL RM |
| | LOCATED ON E-PH-1 WHICH SHOWS DOORS WITH |
| | AN "IN-SWING", PLEASE SEE DOORS ARE |
| | REQUIRED TO SWING OUT AND SHALL CONTAIN |
| | OR "PANIC " HARDWARE AS LISTED IN 110.26 |
| | PLEASE NOTE: PANIC HARDWARE REQUIREMENTS |
| | ON ELECTRICAL PLANS. |
| | PLEASE SEE FIRE PUMP ROOM WILL BE |
| | REQUIRED TO HAVE DIRECT ACCES TO |
| | CORRIDOR WITHOUT TRAVEL THROUGH A |
| | "STORAGE ROOM". |
| | PLEASE SEE FIRE REVIEW COMMENTS ALSO. |
| | |
| | 4)NOTE: PLEASE SEE MISSING REQUIRED GFI |
| | RECEPT(S) TO BE LOCATED WITH/IN 20' OF |
| | POOL(S).PLEASE SEE 680.22 |
| | |
| | 5)NOTE: PLEASE SEE MIN CLEARENCES |
| | REQUIRED FOR LANDSCAPE LIGHTING FIXTURES |
| | PER 680.22(B)1 5' MIN FOR HV AND GFCI |
| | PROTECTION REQUIRED. PLEASE ALSO SEE |
| | 411.4 FOR LV TYPE FIXTURES AND MIN OF |
| | 10' FROM WATER'S EDGE. |
| | |
| | 6)NOTE: PLEASE SEE ALTERNATING |
| | CIRCUITING FOR EMERGENCY EGRESS LIGHTING |
| | REQUIRED IN HALLWAYS/CORRIDORS, EGRESS |
| | STAIRWAYS AND ("EGRESS TUNNELS"). |
| | PLEASE SEE NFPA-101 7-9, WHICH REQUIRES |
| | NOT TO LEAVE ANY EGRESS PATH IN TOTAL |
| | DARKNESS UPON THE SWITCHING/TRIPPING OF |
| | A SINGLE BREAKER. PLEASE SEE BATTERY |
| | BACK UP TYPE OF FIXTURES WOULD NOT |
| | REQUIRE ALTERNATING EM CIRUITS FOR |
| | EGRESS LIGHTING. |
| | |
| | 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL |
| | ROOMS, GEN RM, FIRE PUMP RM AND ELEVATOR |
| | EQUIPMENT ROOMS/EQUIPMENT BOILER RM |
| | SHALL A BATTERY BACK UP TYPE OF LIGHTING |
| | FIXTURE. |
| | 700.16, LS 101 7-9, 90.4 |
| | |
| | 8)NOTE: PLEASE SEE 620.23 AND 620.24 |
| | WHICH REQUIRES EQUIPMENT ROOMS/ARES TO |
| | HAVE A DEDICATED BRANCH CIRCUIT FOR |
| | RECEPTS AND LIGHTING. PLEASE KNOW, PER |
| | MEETING WITH OWNERS AND DESIGN TEAM, |
| | THIS ALSO INCLUDES ALL EQUIPMENT LOCATED |
| | A-TOP HOISTWAY. |
| | A RECEPT IN ELEVATOR EQUIPMENT CLOSET IS |
| | SHOWN ON PLANS. |
| | |
| | 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT |
| | LOCATIONS OF ANY "KNOX BOX" LOCATION(S) |
| | WHICH MAY BE REQUIRED. ONE OR MORE |
| | LOCATIONS SHALL BE PLACED/NOTED ON |
| | PLANS. |
| | |
| | 10)NOTE: PLEASE SHOW ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. PLEASE SEE THIS |
| | COMMENTS IS MAINLY FOR SOME COMMON AREAS |
| | MISSING DESIGNATIONS. |
| | |
| | 11)NOTE: : PLEASE SEE 210.63 FOR |
| | REQUIMENTS OF GFI RECEPTS FOR ALL A/C |
| | EQUIPMENT. PLEASE SEE THESE COULD NOT BE |
| | LOCATED ON ROOF PLANS ETC. |
| | |
| | 12)NOTE: PLEASE SEE ELEVATOR RMS, |
| | LAYOUTS ON E-09AND E-12, DOOR/OPEINGS |
| | FOR EQUIPMENT DO NOT SEEM TO CORRELATE. |
| | |
| | 13)NOTE: PLEASE KNOW IT WAS MENTIONED IN |
| | MEETING THE "CAFE" WOULD BE A "SHELL" |
| | AREA ONLY, HOEVER PLEASE SEE PLANS SHOW |
| | ALL ELECTRICAL DEVICES BEING INSALLED? |
| | PLEASE SEE RISER SHOWS CONDUIT FOR |
| | "FUTURE" RESTAURANT. IS THIS THE SAME ? |
| | PLEASE CLARIFY. |
| | |
| | 14)NOTE: PLEASE SEE SOME AREAS OF PLANS |
| | FOR COMMON AREA LIGHTING ETC WHICH ARE |
| | NOT "LEGALLY REQUIRED" SEEM TO BE ON THE |
| | EM LEGALLY REQUIRED STAND-BY POWER |
| | SYSTEM. |
| | PLEASE SEE THAT ANY "OPTIONAL STAND-BY" |
| | LOADS NOT LEGALLY REQUIRED MUST BE FED |
| | FROM A DIFFERENT TRANSFER SWITCH AND EM |
| | DISTRABUTION SYSTEM. PLEASE SEE 700.6D |
| | |
| | 15)NOTE: PLEASE SEE AS PER MEETING WITH |
| | OWNERS REP/DESIGN TEAM, DRYER BOOSTER |
| | FANS SHALL NOT BE USED, HOWEVER THESE |
| | ARE STILL BEING SHOWN? |
| | PLEASE CORRELATE AND PLEASE SEE |
| | MECHANICAL REVIEW COMMENTS. |
| | |
| | 16)NOTE: PLEASE SEE 210.52C2 AND 4 WITH |
| | REGARDS TO "SEPARATE" COUNTERSPACES FOR |
| | ISLANDS. PLEASE VERFIY SIZE OF COOKTOP |
| | AND A SAFE COUNTERSPACE FOR NTO |
| | EXTENDING CORDS NEAR HEAT SOURCES ETC. |
| | PLEASE SEE GFI RECEPTS AS SHOWN ON |
| | ISLANDS AT THIS TIME, APPEAR TO MEET |
| | CODE,PLEASE SEE THIS IS ONLY A NOTE FOR |
| | SIZING ETC TO BE VERIFIED. |
| | PLEASE SEE IF IF UNIT IS LARGER THAN IS |
| | SHOWN, A SEPARATE GFI AT OTHER END WILL |
| | BE REQUIRED. |
| | PLEASE BE SURE ALL ISLANDS SHOW A RECEPT |
| | AS REQUIED. PLEASE SEE REDLINED SETS FOR |
| | ANY MISSING. |
| | |
| | 17)NOTE: PLEASE SEE SOME MISSING GFI |
| | COUNTERSPACE RECEPTS AS REQUIRED ALONG |
| | WALL/COUNTERSPACE. 210.52C1 |
| | PLEASE SEE REDLINED SETS FOR LOCATIONS |
| | IN SOME UNITS. |
| | "B",DMOD, C, S. |
| | |
| | 18)NOTE: PLEASE SEE SOME UNITS MISSING |
| | RECEPTS PER 210.52. |
| | PLEASE SEE REDLINED SET. |
| | |
| | 19)NOTE: PLEASE SEE CIRCUITING MISSING |
| | FROM SOME DEVICES SHOWN IN SOME OF THE |
| | UNITS. PLEASE SEE GFI'S IN SOME BATHS. |
| | PLEASE SEE REDLINED PLANS AS MOST ARE |
| | CIRCIRLED. PLEASE SEE UNITS, G NORTH, L |
| | NORTH, E, F D NORTH MOD ETC. |
| | |
| | 20)NOTE: PLEASE SEE UNIT "B" SOUTH WHICH |
| | DOES NOT APPEAR TO SHOW ANY DINING RM/ |
| | AREA ON PLANS. PLEASE SEE POSSIBLE ARE |
| | SHOWN AS MEDIA/DEN? |
| | PLEASE VERIFY AS DINING RM/AREA AND THE |
| | LIKE SHALL BE FED FROM ONE OR MORE OF |
| | THE REQUIRED SMALL APPLIANCE CIRCUITS. |
| | 210.52B1, 210.11C1 20A AND #12. |
| | |
| | 21)NOTE: PLEASE SEE "D" NORTH WHICH |
| | SHOWS ISLAND RECEPT ON CIRCUIT #6, |
| | HOWEVER 6/8 IS SHOWN ON PANEL SCHEDULE |
| | AS OVEN. PLEASE ADJUST. |
| | |
| | 22)NOTE: PLEASE SEE "L" SOUTH WHICH |
| | SHOWS "FRIG" ON SM APPLIANCE CIRCUIT #8, |
| | HOWEVER FRIG IS LISTED AS #4 ON PANEL |
| | SCHEDULE. FRIG CIRCUIT NOT SHOWN ON |
| | PLANS. PLEASE ADJUST. |
| | |
| | 23)NOTE: PLEASE SEE SOME BATH(S) ARE |
| | MISSING THE REQUIRED GFI RECEPT WITHIN |
| | 3' OF LAV EDGE. PLEASE SEE "N", PLEASE |
| | ALSO SEE PLANS FOR ANY OTHER REDLINED |
| | LOCATIONS. |
| | 210.52D,210.11C3 |
| | |
| | 24)NOTE: PLEASE SEE SEE SOME |
| | "HYDRO-MASSAGE" CIRCUITS ARE NOTED ON |
| | PANEL SCHEDULE(S), HOWEVER THESE |
| | ELECTRICAL DEVICE LOCATIONS COULD NOT BE |
| | LOCATED ON PLANS. PLEASE SEE "K" |
| | NORTH,"H" NORTH AND ANY OTHER POSSIBLE |
| | REDLINES. |
| | |
| | 25)NOTE: PLEASE SEE THAT ALL RECEPTS |
| | SHOWN IN CLOSETS FOR LV TRNSFORMERS TO |
| | BE "PLUGGED IN" SHALL BE LOCATED ATLEAST |
| | 12" MIN FROM SHELVING. THESE MAY BE |
| | LOCATED ABOVE DOOR WAYS. |
| | PLEASE SEE PLUG-IN TYPE TRANSFORMERS |
| | CREATE VERY HIGH TEMPS AND SOME IN THIS |
| | JURISTICTION HAVE HEATED TO THE POINT OF |
| | MELTING, AND CUSE OF FIRE IN CLOSETS AND |
| | CLOSE PROIMITY TO COMBUSTIBLES. PLEASE |
| | SEE THIS CREATES A LIFE-SAFETY SITUATION |
| | AND ANY UNITS CONTAININGOCP, THERMAL |
| | CUT-OUT DEVICES WILL BE REQUIRED TO BE |
| | LOCATED AS ABOVE. 110.26,240.24D |
| | |
| | 26)NOTE: PLEASE SEE MISSING ISLAND |
| | RECEPT(S) FOR ISLAND IN UNIT "P". |
| | 210.52C2 |
| | AS REDLINED. |
| | |
| | 27)NOTE: PLEASESEE UNIT "N" WHICH |
| | APPEARS TO SHOW A FRIG #37, HOWEVER |
| | PLEASE SEE POSSIBLE SPACING FOR KITCHEN |
| | COUNTERSPACE DEPENDING ON FRIG SIZE AS |
| | SHOWN. PLEASE SEE "P", 210.52C1 |
| | LOCATIONS REDLINED. |
| | |
| | 28)NOTE: PLEASE SEE UNIT "P"SOUTH AND |
| | "Q" NORTH. PLEASE SEEUNIT "P" WITH |
| | LESS SQ FT SHOWS 3-HEAT-PUMPS SYSTEMS, |
| | HOWEVER UNIT "Q" WITH MUCH MORE SQ FT |
| | ONLY SHOWS 2-HEAT PUMP SYSTEMS. |
| | PLEASE SEE THIS IS ONLY A COMMENT AND NO |
| | ELECTRICAL CODE ISSUE EXISTS. |
| | |
| | 29)NOTE: PLEASE SEE COUNTERSPACES |
| | LOCATED AT LAUNDRY RM IN "Q" NORTH, DO |
| | NOT SHOW ANY COUNTERSPACE GFI RECEPTS. |
| | PLEASE SHOW IF ANY ARE TO BE INSTALLED. |
| | THIS IS ONLY A NOTE AS A MIN OF ONE |
| | LAUNDRY CIRCUIT AS REQUIRED UNDER |
| | 210.52C2,210.52F,220.16 |
| | PLEASE SEE NO ADDITIONAL ARE REQUIRED AS |
| | LONG AS ABOVE IS MET. |
| | PLEASE SEE NEXT COMMENT. |
| | |
| | 30)NOTE: PLEASE SEE PLANS INDICATE MANY |
| | OF THE UNITS PANEL SCHEDULES SHWOING TWO |
| | SEPARATE CIRCUITS FOR WASHER AND DRYER. |
| | PLEASE SEE MANY UNITS SHOW THIS |
| | WASHER/DRYER AS ONE UNIT. PLEASE SEE |
| | PREVIOUS COMMENT WITH RESPECT TO DESIGN |
| | OF "DUCTLESS" DRYERS. ALSO VERIFY IF |
| | LAUNDRY CIRCUIT REQUIRED IS THE SAME |
| | CIRCUIT FEEDING COMBO UNIT?? |
| | |
| | 31)NOTE: PLEASE ALSO SEE ABOVE "Q" UNIT |
| | APPEARS TO SHOW TWO PANELS, ONE WITH |
| | FEED THRU LUGS? HOWEVER PANEL SCHEDULE |
| | INDICATES ALL CIRCUITS IN ONE PANEL |
| | SCHEDULE. |
| | PLEASE SEE A MAX OF 42 OCP DEVICES ARE |
| | PERMITTED IN SINGLE PANEL.408.15 |
| | PLEASE INLCUDE PANEL SCHEDULE FOR |
| | "FEED-THRU" PANEL. PLEASE ADJUST |
| | CIRCUITING AS SHOWN ON PLANS. |
| | |
| | 32)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS REQUIRED UNDER NFPA-72 |
| | 8-1.4.1.6.2 , FBC ETC. |
| | PLEASE SEE SD'S ARE REQUIRED INSIDE AND |
| | OUTSIDE ALL SLEEPING RMS AND ON EACH |
| | LEVELOF A MULTY LEVEL DWELLING. |
| | PLEASE SEE SOME MISSING, DEN IN UNIT "R" |
| | WILL BE REQUIRED TO AHVE A SD AS IT IS |
| | SHOWN WITH AN ATTACHED BATH OR CLOSET |
| | WHICH MAKES THIS AN ADAPTABLE SLEEPING |
| | RM BY AHJ. PLEASE SEE MISSING SD "Q" |
| | NORTH LEADING TO FLR ABOVE. |
| | PLEASE SEE SD'S ARE REDLINED AT |
| | LOCATIONS REQUIRED IN OTHER UNITS. |
| | |
| | 33)NOTE:PLEASE SEE "NOTE"FOR LV |
| | SYSTEM(S)ON ALL ELECTRICAL SHEETS FOR |
| | UNITS MENTIONS THE "GENERAL CONTRACTOR' |
| | IS TO INSTALLED THIS LV IN HIS SCOPE OF |
| | WORK? |
| | PLEASE SEE FS 468 AND SCOPE WORK |
| | PERMITTED. PLEASE ALSO SEE ECLB. |
| | THIS APPEARS TO BE A MISPRINT.? |
| | |
| | 34)NOTE; PLEASE SEE BLDG/MECH/FIRE |
| | REVIEW COMMENTS FOR EQUIPMENT SHOWN IN |
| | ELEVATOR LOBBY'S. PLEASE ALSO SEE THESE |
| | ELEVATOR LOBBY'S SHALL BE CONSIDERED |
| | PART OF UNITS AS COMMON AREAS ARE NOT |
| | PERMITTED TO CONTAIN CIRCUITS FROM |
| | UNITS. PLEASE SEE 210.25 |
| | |
| | 35)NOTE: PLEASE SEE ALL SD'S ARE |
| | REQUIRED TO BE WIRED "IN-LINE", PLEASE |
| | SEE UNIT WLT3, WHICH SHOWS SD'S ON |
| | CIRCUITS 12 AND 24. PLEASE ADJUST. |
| | |
| | 36)NOTE: PLEASE SEE 210.702C FOR LOFT |
| | UNITS CONTAINING LANDINGS. PLEASE SEE |
| | THESE UNITS INDICATE 6 OR MORE RISERS IN |
| | BOTH DIRECTIONS, PLEASE SEE A 4-WAY SW |
| | WILL BE REQUIRED AT LANDING LOCATION. |
| | |
| | 37)NOTE: PLEASE SEE ANY PROPOSED |
| | LIGHTNING PROTECTION SYSTEM SHALL BE |
| | INSTALLED AND ACCEPTABLE PER NFPA-780. |
| | ALTHOUGH A LIGHTNING PROTECTION SYSTEM |
| | IS NOT SHOWN ON ANY PLANS, PLEASE BE |
| | SURE A NOTE IS PLACED ON "ROOF-TOP" |
| | SHEET WITH REFERENCE TO NFPA-780. |
| | AS NOTED IN MEETING , "LIGHTNING |
| | PREVENTION" SYSTEMS ARE NOT PERMITTED OR |
| | ACCEPTABLE IN THIS JURISTICTION. |
| | |
| | 38)NOTE: PLEASE SEE MAINS AS SHOWN RISER |
| | WITHOUTDIRECT BUS-STAB INTO FPL VAULT |
| | AND IF THERE ARE MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS IN BLDG, THESE |
| | CONDUITS AND SEC'S SHALL BE INCASED IN A |
| | MIN OF 2" OF CONCRETE. PLEASE SEE 230.6, |
| | 230.70 ALSO CITY OF WEST PALM BEACH |
| | LOCAL AMENDMENTS. |
| | |
| | 39)NOTE: PLEASE SEE CALCUALTIONS FOR |
| | BUS-DUCT #4, PLEASE INDICATE AS MAIN #4 |
| | AS OTHERS ARE NOTED. |
| | |
| | 40)NOTE: PLEASE SEE HXDP WILL BE |
| | REQUIRED TO HAVE A MCB. PLEASE SEE IF |
| | ATS CONTAINS A MANUAL MEANS OF |
| | DISCONNECT LOCATED ON OUTSIDE OF ATS AND |
| | CAPABLE OF BEING LOCKED IN THE "OPEN" |
| | POSITION, THEN A MCB IN HXDP. PLEASE SEE |
| | IN EITHER CASE THE MEANS OF DISCONNECT |
| | WILL BE REQUIRED TO BE IN CLOSE |
| | PROXIMITY TO MAIN ELECTRICAL RM FOR |
| | GROUPING OF MAINS. PLEASE SEE NEC DOES |
| | MENTIONS EM MAIN TO BE LOCATED REMOTE, |
| | HOWEVER A RESPONSE FROM NFPA MENTIONED |
| | THIS CAN BE LOCATED AS CLOSE AS 10 FEET. |
| | PLEASE SEE A CONCENSUS FROM ELECTRICAL |
| | PLAN REVIEW, FIRE MARSH.'S OFFICE AND |
| | CHIEF ELECTRICAL INSPECTOR RESULTS IN |
| | NOT HAVING THE MAIN FROM THE SECONDARY |
| | SIDE OF GENERATOR IN GENERATOR |
| | ELECTRICAL ROOM. 230.72 |
| | THIS LOCATION WITH A 1500KW GENERATOR |
| | RUNNING AT FULL NOISE LEVEL, HEAT ETC |
| | MAY DISTRACT IN SHUTTING DOWN OF EM |
| | POWER IN A SAFE AND TIMELY FASHION. IT |
| | IS NOTED THAT THESE MAINS AND GEN WILL |
| | HAVE SHUNT TRIPS IN FIRE COMMAND RM, |
| | HOWEVER THESE ARE NOT CONSIDERED AS THE |
| | MEANS OF DISC. 230.76,230.79 |
| | PLEASE SEE IT IS UNCLEAR AT THIS TIME IF |
| | BRKR ON GEN IS LOCATED ON THE OUTSIDE OF |
| | EQUIPMENT WITH A MANUAL MEANS OF |
| | DISCONNECT WITH EXPOSING OF LIVE PARTS. |
| | 110.27. |
| | PLEASE SEE SOME OF THIS CAN NOT BE |
| | VERIFIED AT THIS TIME AS SPECS FOR THIS |
| | EQUIPMENT, GENERATOR ETC WAS NOT |
| | SUBMITTED. |
| | PLEASE SEE ROUTE, LOCATION TRAVEL |
| | DISTANCE ETC MAY BE GONE IN A MEETING |
| | WHICH MAY BE REQUESTED. |
| | |
| | 41)NOTE: PLEASE SEE MISSING LOAD |
| | CALCULATIONS FOR MCVI, MCVII. |
| | 215.5 |
| | |
| | 42)NOTE: PLEASE SHOW GROUNDING SYSTEM |
| | FOR ALL TRANSFORMER. PLEASE INCLUDE |
| | GROUNDING OF THESE TRANSFOMERS ON RISER |
| | DIAGRAM IN NOTES/LINE DIAGRAM. |
| | 250.30, 250.50 ETC. |
| | |
| | 43)NOTE: PLEASE INCLUDE ALL EQUIPMENT |
| | GROUNDING CONDUCTORS FOR TRANSFOMERSON |
| | PRIMARY SIDE. 250.110,250.30 SIZED |
| | 250.122. |
| | |
| | 44)NOTE: PLEASE INDICATE OCP AT |
| | GENERATOR. PLEASE ALSO SEE 445.13 FOR |
| | SIZING OF CONDUCTORS. THIS CAN NOT BE |
| | VERIFIED AT THIS TIME. |
| | |
| | 45)NOTE: PLEASE SEE EM MAIN INDICATES |
| | GFCI PROTECTION. PLEASE SEE GFCI IS |
| | PERSONNEL PROTECTION AND 277/480V OVER |
| | 1000A'S 230.95,240.13. PLEASE SEE THESE |
| | AS GFP, GROUND FULT PROTECTION IS NOT |
| | THE SAME. |
| | |
| | 46)NOTE: PLEASE SEE 240.13, IF SYSTEM IS |
| | GROUND FAULT PROTECTD, THE ATS WILL BE |
| | REQUIRED TO BE 4-POLE AND GENERATOR WILL |
| | BE REQUIRED TO BE A SEPARATELY DERIVED |
| | SYSTEM. |
| | PLEASE SEE GROUNDING FOR ANY SEPARATELY |
| | DERIVED SYSTEMS SHALL BE SHOWN. |
| | 250.50 ETC |
| | |
| | 47)NOTE: PLEASE CORRELATE FEEDERS FOR |
| | LXRA ON RISER WITH PANEL SCHEDULE. |
| | |
| | 48)NOTE: PLEASE SEE PANELS LPA, LPB WITH |
| | X'S FOR LOADS, INFORMATION ETC??? |
| | PLEASE COMPLETE PANELS.215.5 |
| | |
| | 49)NOTE:PLEASE SEE SOME PANELS ARE SHOWN |
| | AS POSSIBLE "FEED-THRU" PANELS WITH MORE |
| | THAN THE PERMITTED 42 CIRCUITS 408.15, |
| | HOWEVER RISER DOES NOTE CORRELATE, ONLY |
| | SHOWS THE INDIVIDUAL PANEL. |
| | 215.5 PLEASE CORRELATE. |
| | |
| | 50)NOTE: PLEASE SEE PANEL SCHEDULES |
| | SHOWS "TYPICAL" PANELS FOR TRA, TRB , |
| | TRC ETC ETC, HOWEVER THESE COULD NTO BE |
| | LOCATED ON RISER DIAGRAM? |
| | 215.5 |
| | |
| | 51)NOTE: PLEASE SEE HP ON RISER IS SHOWN |
| | FEEDING LP, HOWEVER PLEASE SEE HP PANEL |
| | SCHEDULE WHICH DOES NOT INDICATE ANY |
| | FEEDS TO LP? 215.5 PLEASE CORRELATE. |
| | |
| | 52)NOTE:PLEASE SEE HG AS DOUBLE/FEED |
| | THRU PANEL, HOWEVER RISER INDICATES |
| | SINGLE PANEL. PLEASE SEE OTHER POSSIBLE |
| | PANELS, HB, LB AND PREVIOUS NOTE. #49 |
| | |
| | 53)NOTE: PLEASE SEE PANEL TF IS FED FROM |
| | LG AND LXG? PLEASE CORRELATE 215.5 |
| | |
| | 54)NOTE: PLEASE SEEA 600A MAIN FOR |
| | FUTURE REST. IS SHOWN, HOWEVER NO |
| | INFORMATION FOR VOLTAGE ETC WAS |
| | SUBMITTED. PLEASE SEE PREVIOUS COMMENT |
| | WITH RESPECT TO "CAFE".?? |
| | 215.5 |
| | |
| | 55)NOTE: PLEASE SEE NO PANEL SCHEDULE |
| | WAS SUBMITTED FOR PANEL HRA AT ROOF |
| | LEVEL?? |
| | 215. |
| | |
| | 56)NOTE: PLEASE SEE NO PANEL SCHEDULES |
| | WERE SUBMITTED FOR PANELS , HS, LS, HXS, |
| | LXS,,,?? |
| | 215.5 |
| | |
| | 57)NOTE: PLEASE SEE HXG WHICH SHOWS FEED |
| | TO LX6, MISPRINT? FOR LXG? |
| | 215.5 |
| | |
| | 58)NOTE: PLEASE SEE "ELB" WHICH |
| | INDICATES FEED TO LXRB ON RISER AND |
| | PANEL SCHEDULE INDICATES LXRA. |
| | PLEASE CORRELATE: 215.5 |
| | |
| | 59)NOTE: PLEASE SEE ELB FEEDS "HXRB" ON |
| | RISER , HOWEVER SHOWS "HXRA" ON PANEL |
| | SCHEDULE. PLEASE CORRELATE. 215.5 |
| | |
| | 60)NOTE: PLEASE SEE HXB FEEDS LXB ON |
| | RISER , HOWEVER THIS IS LXA ON PANEL |
| | SCHEDULE.215.5 |
| | |
| | 61)NOTE:PLEASE VERIFY2000A OCP AS |
| | NOTED FOR GENERATOR , HOWEVER LOAD SHOWN |
| | ON HXDP INDICATES LOADS ABOVE 2000A'S. |
| | PLEASE SEE MAIN AND ATS IS INDICATED AS |
| | 2500AS'. PLEASE CORRELATE. 215.5 |
| | PLEASE SEE GEN AND OCP SHALL BE SIZED |
| | FOR LOAD SERVED. |
| | |
| | 62)NOTE: PLEASE SEE MOST OF THE ABOVE |
| | ITEMS ARE REDLINED ON ONE SET OF |
| | ELECTRICAL PLANS, HOWEVER THESE DO NOT |
| | IDICATE ALL POSSIBLE LOCATIONS OF NEEDED |
| | CORRECTIONS. |
| | |
| | 63)NOTE: PLEASE SEE MUCH INFORMATION NOT |
| | SHOWN (PANEL SCHEDULES), (SPECS) ETC CAN |
| | NOT BE VERIFIED OR REVIEWED AT THIS |
| | TIME. PLEASE SUBMIT ALL INFOMATION. |
| | |
| | 64)NOTE: PLEASE SEE POOL WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | PLEASE PLACE NOTE ON PLANS. |
| | IF NIGHT-TIME/AFTER DUSK WILL BE |
| | PROPOSED, SIGNED, SEALED PHOTOMETRICS |
| | WILL BE REQUIRED TO BE SUBMITTED TO PALM |
| | BEACH COUNTY HEALTH DEPT FOR REVIEW AND |
| | STAMPING. |
| | THIS WILL BE REQUIRED WITH POOL PERMIT. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE A |
| | DIRECT EFFECT ON ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE AREA ANY QUESTIONS, |
| | PLEASE DO NOT HESIATE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2005-08-19 00:00:00 | PLANS STILL IN ELEC FOR REVIEW. |
| | UNITS, COMMON AREAS COMPLETED. |
| | SERVICE STILL NEEDS TO BE REVIEWED. |
| | REVIEW TO CONTINUE 8/22 |
| | NOTES TO FOLLOW. |
| 2005-08-18 00:00:00 | 1-SET OF SPEC BOOKS AND 1-SET OF MEP'S |
| | IN ELECTRIC FOR REVIEW. |
| | NOTES TO FOLLOW. |