| 2005-09-10 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05071027 |
| | ADD: 2211 N FLAGLER DR |
| | CONT: PLAN REVIEW |
| | OWNER: MERCO GROUP |
| | TEL: (561)296-3300 |
| | ARCH: SONG & ASSOC/ JOHN STRNDBERG |
| | |
| | TEL: (561) 655-2423 |
| | |
| | -PALADIO TERRACE- |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ALTHOUGH THERE IS A FOUNDATION PERMIT |
| | PLEASE SUBMIT THE FOLLOWING ITEMS SINCE |
| | THE FOUNDATION AND BUILDING PERMITS ARE |
| | STAND ALONE PERMITS. |
| | A) SOILS REPORT (3) |
| | B) THRESHOLD INSPECTION PLAN (3) |
| | C) THRESHOLD INSPECTOR AGREEMENT(1) |
| | D) NOTICE OF COMENCEMENT (1) |
| | E) UNITY OF TITLE |
| | F) PROVIDE A SITE PLAN W/ BUILDING LINE |
| | |
| | VS. THE PROPERTY LINE. |
| | |
| | 2) LS0.00 CODE ANALYSIS IS MISSING: |
| | 2A) 412.3.3 FIRE DEPARTMENT |
| | COMMUNICATION SYSTEM. A TWO-WAY FIRE |
| | DEPARTMENT COMMUNICATION SYSTEM SHALL BE |
| | PROVIDED FOR FIRE DEPARTMENT USE. |
| | IT SHALL OPERATE BETWEEN THE FIRE |
| | COMMAND STATION AND EVERY ELEVATOR, |
| | ELEVATOR LOBBY, ENTRY TO EVERY ENCLOSED |
| | EXIT STAIRWAY AND IN CORRIDORS. |
| | |
| | 412.3.4 COMBINED SYSTEM. WHEN APPROVED, |
| | THE FIRE DEPARTMENT COMMUNICATIONS |
| | SYSTEM MAY BE COMBINED WITH THE VOICE |
| | ALARM SIGNALING SYSTEM. |
| | |
| | FIRE COMMAND STATION |
| | |
| | 412.4.1 A FIRE COMMAND STATION FOR |
| | FIRE DEPARTMENT OPERATIONS SHALL BE |
| | PROVIDED IN A LOCATION APPROVED BY THE |
| | FIRE DEPARTMENT. |
| | |
| | 412.4.3 A FIRE COMMAND STATION SHALL |
| | CONTAIN: |
| | |
| | 1. CONTROLS FOR THE ONE-WAY VOICE |
| | ALARM SYSTEM. |
| | |
| | 2. CONTROLS FOR THE TWO-WAY FIRE |
| | DEPARTMENT COMMUNICATION SYSTEM. |
| | |
| | 3. FIRE ALARM SYSTEM ANNUNCIATOR |
| | PANELS. |
| | |
| | 4. STATUS INDICATORS SHOWING |
| | LOCATION OF ELEVATORS IN THE HOISTWAYS |
| | AND |
| | SWITCHES TO SELECTIVELY TURN |
| | POWER TO ELEVATORS ON OR OFF. |
| | |
| | 5. STATUS INDICATORS AND CONTROLS |
| | FOR AIR HANDLING SYSTEMS. |
| | |
| | 6. CONTROLS FOR UNLOCKING ALL |
| | STAIRWAY DOORS SIMULTANEOUSLY. |
| | |
| | 7. SPRINKLER VALVE, WATERFLOW |
| | DETECTOR AND FIRE PUMP DISPLAY PANELS. |
| | |
| | 8. EMERGENCY POWER, LIGHT AND |
| | EMERGENCY SYSTEM CONTROLS AND STATUS |
| | INDICATORS. |
| | |
| | 9. A TELEPHONE FOR FIRE DEPARTMENT |
| | USE WITH CONTROLLED ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM. |
| | |
| | 10. GENERATOR SUPERVISION DEVICES, |
| | MANUAL START AND TRANSFER FEATURES. |
| | |
| | PLANS INDICATE THAT THEY WILL COMPLY |
| | WITH FBC CHAPTER 9, SECTION 412.3 & NFPA |
| | 72-2002. 104.2.1 W.P.B. ADMINISTRATIVE |
| | CODE DRAWINGS & SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF |
| | NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. |
| | *************** |
| | SUCH INFORMATION SHALL BE SPECIFIC |
| | AND THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE |
| | TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". PLEASE PROVIDE ADDITIONAL |
| | INFORMATION FOR CODE COMPLIANCE. |
| | *************** |
| | |
| | 2B)SMOKE CONTROL 412.5 |
| | PROVIDE CODE COMPLIANCE. IF SYSTEM IS TO |
| | COMPLY WITH (3) 412.7.2).UNDER FIRE |
| | CONDITIONS, THE RETURN AND EXHAUST AIR |
| | SHALL BE MOVED DIRECTLY TO THE |
| | OUTSIDE WITHOUT RECIRCULATION TO OTHER |
| | SECTIONS OF THE BUILDING.THE AIR |
| | HANDLING SYSTEM SHALL HAVE THE |
| | CAPABILITY OF PROVIDING A MINIMUM OF ONE |
| | EXHAUST AIR CHANGE EVERY 10 MINUTES FOR |
| | ANY AREA WHICH MIGHT BE INVOLVED. |
| | |
| | 3) LS0.03 HAS THE TERM "TOWNHOUSE" |
| | DESCRIBING R2 UNITS. THESE UNITS ARE |
| | CONDOMINIUMS NOT TOWNHOUSES. THE FL BLDG |
| | CODE 2001 DEFINITION OF TOWNHOUSE IS: |
| | 202.TOWNHOUSE. A SINGLE FAMILY DWELLING |
| | CONSTRUCTED IN A SERIES OR GROUP OF |
| | ATTACHED UNITS WITH PROPERTY LINES |
| | SEPARATING EACH UNIT. |
| | IF TRUELY TOWNHOUSE CONSTRUCTION, |
| | PROVIDE THE RECORDED PLAT PLAN WWITH |
| | SEPERATE LOTS, OTHERWISE REMOVE TREM |
| | FROM ALL DOCUMENTS. |
| | |
| | 4) CONDO UNITS 1-14 (TOWNHOUSE UNITS) |
| | ARE TO COMPLY WITH FAIR HOUSING MANUAL |
| | REVISED APRIL 1998, PAGE 1.32. BUILDINGS |
| | WITH ONE OR MORE COMMON ENTRANCES TO ALL |
| | DWELLING UNITS IN BUILDINGS WITH ONE OR |
| | MORE ELEVATORS. AT LEAST ONE COMMON |
| | ENTRANCE SHALL BE ON AN ACCESSIBLE |
| | ROUTE. SITE IMPRACTICABILITY TEST DOES |
| | NOT APPLY TO ELEVATORED BUILDINGS. |
| | PROVIDE ON THE LIFE SAFETY PLAN THE |
| | ACCESSIBLE ROUTE FROM THE ELEVATOR TO |
| | THESE UNITS. |
| | |
| | 5) THESE UNITS ARE MISSING EXIT ACCESS |
| | CORRIDORS, EXIT ACCESS. THAT PORTION OF |
| | A MEANS OF EGRESS WHICH LEADS TO AN |
| | ENTRANCE TO AN EXIT. |
| | |
| | SEE MEANS OF EGRESS DEFINITIONS, MEANS |
| | OF EGRESS. A CONTINUOUS AND UNOBSTRUCTED |
| | WAY OF EXIT TRAVEL FROM ANY POINT IN A |
| | BUILDING OR STRUCTURE TO A PUBLIC WAY, |
| | CONSISTING OF THREE SEPARATE AND |
| | DISTINCT PARTS: (1) THE WAY OF EXIT |
| | ACCESS, (2) THE EXIT, AND (3) THE WAY OF |
| | EXIT DISCHARGE. A MEANS OF EGRESS |
| | COMPRISES THE VERTICAL AND HORIZONTAL |
| | WAYS OF TRAVEL AND SHALL INCLUDE THE |
| | INTERVENING ROOM SPACE, DOORS, |
| | CORRIDORS, PASSAGEWAYS, BALCONIES, |
| | STAIRS, RAMPS, ENCLOSURES, LOBBIES, |
| | HORIZONTAL EXITS, COURTS AND YARDS. |
| | PROVIDE EXIT ACCESS CORRIDORS FOR |
| | UNITS 1-14 COMPLING WITH TABLE 1004 |
| | TRAVEL DISTANCES FOR R2/ SPRINKLERED |
| | BUILDINGS MAXIMUM TRAVEL DISTANCE OF |
| | 325 FT TO AN EXIT. |
| | |
| | RESIDENTIAL UNITS 101-105 ARE AT |
| | GRADE LEVEL AND WILL NOT REQUIRE EXIT |
| | ACCESS CORRIDORS SINCE THEY CAN EXIT AT |
| | STREET LEVEL AND GO DIRECTLY TO THE WAY |
| | OF THE EXIT DISCHARGE. |
| | |
| | 6) A0.02 NOTE# 35 CABANA CANVAS TO BE |
| | REMOVED AT 75MPH, STRUCTURES ARE TO BE |
| | DESIGNED FOR 140 MPH WIND ZONE.SEE |
| | FIGURE 1606. |
| | |
| | 7A) A1.02C PLANS INDICATE A VALET DRIVE |
| | & A DROP OFF ZONE WITH A ZERO CURB |
| | PASSENGER DROP OFF. PROVIDE MORE |
| | INFORMATION ON THE DROP OFF ZONE. SHOW |
| | COMPLIANCE WITH FL ACCESSIBILITY FOR |
| | ACCESS AILSLE AT PASSENGER LOADING ZONES |
| | FIGURE 10 TO BE 240" LONG(ZERO CURB) AND |
| | 60" WIDE. 11-4.1.2(1)/ 11-4.6.6. |
| | |
| | 7B)A1.02NE & A1.02SE VALET DRIVE |
| | INDICATES "MAINTAIN 8'-0" MINIMUM |
| | CLEARENCE THROUGHOUT VALET DRIVE". |
| | 11-4.6.5 VERTICAL CLEARANCE. PROVIDE |
| | MINIMUM VERTICAL CLEARANCE OF 114 " |
| | (2895 MM) AT ACCESSIBLE PASSENGER |
| | LOADING ZONES AND ALONG AT LEAST ONE |
| | VEHICLE ACCESS ROUTE TO SUCH AREAS FROM |
| | SITE ENTRANCE(S) AND EXIT(S). |
| | |
| | 7C)11-4.1.2(7) BUILDING SIGNAGE. SIGNS |
| | WHICH DESIGNATE PERMANENTROOMS AND |
| | SPACES SHALL COMPLY WITH 11-4.30.1, |
| | 11-4.30.4, 11-4.30.5 AND 11-4.30.6. |
| | OTHER SIGNS WHICH PROVIDE DIRECTION TO, |
| | OR INFORMATION ABOUT, FUNCTIONAL SPACES |
| | OF THE BUILDING SHALL COMPLY WITH |
| | 11-4.30.1, 11-4.30.2, 11-4.30.3, AND |
| | 11-4.30.5.ELEMENTS AND SPACES OF |
| | ACCESSIBLE FACILITIES WHICH SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL |
| | OF ACCESSIBILITY AND WHICH SHALL COMPLY |
| | WITH 11-4.30.7 ARE: |
| | 11-4.1.2(7)(A) PARKING SPACES DESIGNATED |
| | AS RESERVED FOR INDIVIDUALS WITH |
| | DISABILITIES; |
| | 11-4.1.2(7)(B) ACCESSIBLE PASSENGER |
| | LOADING ZONES; |
| | 11-4.1.2(7)(C) ACCESSIBLE ENTRANCES WHEN |
| | NOT ALL ARE ACCESSIBLE (INACCESSIBLE |
| | ENTRANCES SHALL HAVE DIRECTIONAL SIGNAGE |
| | TO INDICATE THE ROUTE TO THE NEAREST |
| | ACCESSIBLE ENTRANCE); |
| | 11-4.1.2(7)(D) ACCESSIBLE TOILET AND |
| | BATHING FACILITIES WHEN NOT ALL ARE |
| | ACCESSIBLE. |
| | |
| | 7D) FOR ALL GROUPINGS OF ELEVATORS SHOW |
| | COMPLIANCE WITH; |
| | 3003.4 STRETCHER REQUIREMENTS |
| | 3003.4.1 IN ALL STRUCTURES THAT ARE |
| | MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THETOP |
| | TERMINAL LANDING EXCEEDS 25 FEET (7.6 M) |
| | MUST BE CONSTRUCTED TOCONTAIN AT |
| | LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL AND WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 76 INCHES (1931 MM) |
| | LONG AND 24 INCHES (610 MM) WIDE IN THE |
| | HORIZONTAL POSITION.THIS ELEVATOR |
| | SHALL BE IDENTIFIED. |
| | |
| | 7E) 3003.3 SIGNS. A PERMANENT SIGN SHALL |
| | BE INSTALLED IMMEDIATELY ABOVE EACH |
| | HALL PUSH BUTTON STATION ON EACH FLOOR |
| | READING:IN FIRE EMERGENCY, DO NOT |
| | USE ELEVATOR.USE EXIT STAIRS.THIS |
| | SIGN SHALL BE LETTERS NOT LESS THAN |
| | 1/2 INCH (12.7 MM) HIGH. |
| | |
| | |
| | 7F)EACH ELEVATOR MUST BE MADE |
| | ACCESSIBLE TO PHYSICALLY HANDICAPPED |
| | PERSONS WITH THE FOLLOWING REQUIREMENTS: |
| | OF 3003.4.2 (1-3) |
| | |
| | 7G) PROVIDE DETAILS HOW IN EACH GROUP OF |
| | 2 ELEVATORS ONE WILL COMPLY WITH: |
| | 3003.5 STANDBY POWER. IN ALL BUILDINGS |
| | OR STRUCTURES WHERE STANDBY POWER |
| | IS REQUIRED OR FURNISHED TO OPERATE AN |
| | ELEVATOR, THE OPERATION SHALL BE AS |
| | FOLLOWS: |
| | |
| | 1. WHERE ONLY ONE ELEVATOR IS |
| | INSTALLED, THE ELEVATOR SHALL TRANSFER |
| | TO STANDBY POWER WITHIN 60 SECONDS AFTER |
| | FAILURE OF NORMAL POWER. |
| | 2. WHERE TWO OR MORE ELEVATORS ARE |
| | CONTROLLED BY A COMMON OPERATING |
| | SYSTEM, ALL ELEVATORS MAY TRANSFER TO |
| | STANDBY POWER WITHIN 60 SECONDS AFTER |
| | FAILURE OF NORMAL POWER; OR IF THE |
| | STANDBY POWER SOURCE IS OF |
| | INSUFFICIENT CAPACITY TO OPERATE ALL |
| | ELEVATORS AT THE SAME TIME, ALL |
| | ELEVATORS SHALL TRANSFER TO STANDBY |
| | POWER IN SEQUENCE, RETURN TO THE |
| | DESIGNATED LANDING AND DISCHARGE THEIR |
| | LOAD.AFTER ALL ELEVATORS HAVE BEEN |
| | RETURNED TO THE DESIGNATED LANDING, AT |
| | LEAST ONE ELEVATOR SHALL REMAIN OPERABLE |
| | FROM THE STANDBY POWER SOURCE. |
| | |
| | 8A) INDICATE COMPLIANCE WITH: VAN |
| | PARKING:11-4.1.2(5)(B) IN PARKING |
| | STRUCTURES, ONE IN EVERY EIGHT |
| | ACCESSIBLE SPACES, BUT NOT LESS THAN |
| | ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL |
| | BE DESIGNED AS REQUIRED BY 11-4.6.3. |
| | THE VERTICAL CLEARANCE AT SUCH SPACES |
| | SHALL COMPLY WITH 11-4.6.5.ALL SUCH |
| | SPACES MAY BE GROUPED ON ONE LEVEL OF A |
| | PARKING STRUCTURE.WHEN SUCH SPACES ARE |
| | PROVIDED IN A PARKING STRUCTURE AND ONLY |
| | ONE IN EIGHT MEET THE HEIGHT REQUIREMENT |
| | OF 11-4.6.5 (98")AT THE PARKING SPACE |
| | AND ALONG AT LEAST ONE VEHICLE |
| | ACCESSIBLE ROUTE TO SUCH SPACES FROM |
| | SITE ENTRANCES AND EXITS, THEY SHALL BE |
| | DESIGNATED AS REQUIRED BY 11-4.6.4. |
| | |
| | 9) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEETS A1.02 NORTH VALET DRIVE INDICATES |
| | A "TILT UP SERVICE DOOR": |
| | |
| | 9A) PROVIDE DETAILS OF THIS UNIT, AND |
| | WHAT IT WILL BE USED FOR? |
| | |
| | 9B) IT APPEARS THERE MAY BE A DISCEPANCY |
| | BETWEEN THE TILT UP DOOR AND THE |
| | UNDERGROUND PASSAGE WAY. LS0.02 |
| | INDICATES THIS UNIT DIRECTLY OVER THE |
| | UNDERGROUND EXIT!LS0.01 DOESN'T INDICATE |
| | ANY OTHER STRUCTURE IN THIS AREA? |
| | |
| | 10A) SHEET A1.02SE & A1.02NE INDICATE A |
| | PEDESTRAIN CROSS WALK ON THE VALET DRIVE |
| | AND A CROSS SECTION #6 ON A3.12. THIS |
| | SECTION INDICATES THIS TO BE A RAISED |
| | CROSS WALK RATHER THAN CURB CUTS WITH |
| | A DESIGNATED EGRESS LANE. SINCE THIS IS |
| | A ELEVATED SLAB INDICATE THE HEIGHT |
| | DIFFERENCE BETWEEN THE CROSS WALK AND |
| | ADJACENT DRIVE? IT APPEARS THE CROSS |
| | WALKS RAMPS MAY NOT MEET THE 1:20 |
| | ADJOINING SLOPE REQUIREMENTS. |
| | |
| | 10B)11-4.7.7 DETECTABLE WARNINGS. A CURB |
| | RAMP SHALL HAVE A DETECTABLEWARNING |
| | COMPLYING WITH 11-4.29.2.THE |
| | DETECTABLE WARNING SHALL EXTEND THE FULL |
| | WIDTH AND DEPTH OF THE CURB RAMP. |
| | |
| | 10C)11-4.29.2(2) DETECTABLE WARNING |
| | TEXTURES ON WALKING SURFACES SHALL |
| | CONSIST OF EXPOSED AGGREGATE CONCRETE, |
| | CUSHIONED SURFACES MADE OF RUBBER OR |
| | PLASTIC, RAISED STRIPS, OR GROOVES. |
| | TEXTURES SHALL CONTRAST WITH THAT OF THE |
| | SURROUNDING SURFACE.RAISED STRIPS OR |
| | GROOVES SHALL COMPLY WITH FIGURE |
| | 11-40(A) AND FIGURE 11-40(B). |
| | |
| | 10D) BOTH SHEETS A1.02NE & A1.02SE BOTH |
| | INDICATE THE USE OF HORIZONTAL SLIDING |
| | DOORS C-0101-C & C-0101-E, 1012.4(9) 9. |
| | IN APARTMENT BUILDINGS, HOTELS AND |
| | DORMITORIES, HORIZONTAL SLIDING DOORS |
| | SHALL NOT BE USED ACROSS CORRIDORS. |
| | |
| | 11)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A1.02 NE UNITS 18& 19 APPEAR TO |
| | HAVE (3) COLUMNS JUST TO THE SOUTH OF |
| | THESE UNITS. JUST EAST OF THESE COLUMNS |
| | THERE IS A GATE, THERE IS ONLY 18" |
| | BETWEEN THE COLUMNS AND WALL LINE. WITH |
| | THE GATE IN THIS PLAN IT APPEARS THAT |
| | THIS AREA IS TO BE USED FOR A WALKWAY? |
| | EXPLAIN RATIONAL? |
| | |
| | 12) A1-04 HAS 2 AREAS NAMED OPEN STORAGE |
| | THAT ARE IN COMMON TO THE ENCLOSED |
| | PARKING AREAS. SEE 411.2.6 AUTOMOBILE |
| | PARKING GARAGES SHALL BE SEPARATED FROM |
| | OTHER OCCUPANCIES IN ACCORDANCE WITH |
| | 704. PROVIDE WHAT TYPE OF STORAGE WILL |
| | TAKE PLACE IN THESE AREAS, RATE DOORS |
| | ACCORDINGLY. |
| | |
| | 13) A1.04 THE REFUSE CHUTE ACCESS ROOM: |
| | |
| | 13A) PLANS DO NOT INDICATE AN ACCESS |
| | ROOM DOOR NOR IS THERE A CUT SECTION |
| | PROVIDING A HORIZONTAL SECTION OF THE |
| | CHUTE, WALL RATINGS AND DOOR RATINGS |
| | . |
| | 13B) 705.2.4.3 REFUSE CHUTES SHALL BE |
| | LOCATED IN ROOMS OR COMPARTMENTS |
| | COMPLETELY ENCLOSED BY CONSTRUCTION AND |
| | OPENING PROTECTIVES IN ACCORDANCE WITH |
| | TABLE 705.1.2. SHOW COMPLIANCE, ALSO SEE |
| | NFPA 82 5.2.5.3.3.THIS IS TAKEN WITH THE |
| | REFUSE CHUTE DOOR OPEN!!!! |
| | |
| | 13C) PROVIDE DETAILS FOR FIRE SPRINKLERS |
| | IN ACCORDANCE WITH: |
| | 705.2.4.6 AUTOMATIC SPRINKLERS. AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | SHALL BE INSTALLED AT THE TOP AND AT |
| | ALTERNATE FLOOR LEVELS IN REFUSE AND |
| | LAUNDRY CHUTES AND IN THE TERMINATION |
| | AND INCINERATOR ROOMS. |
| | |
| | 14) PLANS DO NOT HAVE A DOOR SCHEDULE . |
| | 14A)RATED DOORS SHALL COMPLY WITH TABLE |
| | 705.1.2 |
| | 14B) RATED DOORS ARE TO SHOW CLOSING |
| | DEVICES, HARDWARE, FRAMES AND SILLS |
| | INACCORDANCE WITH 705.1.3 AND UNDER CUT |
| | AS TO NFPA 80. |
| | |
| | 15) PLANS DO NOT HAVE A FINISH SCHEDULE |
| | FOR THE COMMON AREAS. |
| | |
| | 16) A1.04C THERE IS A TRUE ISSUE OF THE |
| | ATRIUM VERSUS THE ELEVATOR LOBBY.BY |
| | DEFINITION, ATRIUM. A SPACE, INTENDED |
| | FOR OCCUPANCY WITHIN A BUILDING, |
| | EXTENDING VERTICALLY THROUGH THE |
| | BUILDING AND ENCLOSED AT THE TOP.SINCE |
| | THE 3RD FLOOR IS ENCLOSED BY GLASS, THIS |
| | TRUELY MAKES A SHAFT SEPERATING IT FROM |
| | THE REST OF THE BUILDING. |
| | SINCE THIS IS A HIGH RISE, AND THE |
| | SHAFT SEPERATES THIS AREA REMOVING THE |
| | ATRIUM THEORY,412.6.1 CAN NOT TAKE THE |
| | EXEMPTION FOR ATRIUMS MAKING AN ELEVATOR |
| | LOBBY REQUIRED FOR FLOORS 2,3 & 4. |
| | 16B) FOR INFORMATION AS TO SMOKE CONTROL |
| | FOR THE ATRIUM THE MECHANICAL PLANS |
| | INDICATE ON PAGE AC-01 AC-02 TO SEE |
| | SHEET AC-20 FOR WORK IN THIS AREA, THIS |
| | PAGE IS FOR THE PENTHOUSE SUITES? |
| | 16C) PROVIDE THE AMOUNT OF CU FT OF AIR |
| | INCLUDED UNDER THE ATRUIM SMOKE CONTROL |
| | SYSTEM SEE 414.4.2 AND SHOW COMPLIANCE. |
| | (C)(1) LS0.03 PROVIDES THE TENANT |
| | SEPERATION WALLS AND OR FIRE SEPERATION |
| | WALLS. 414.5 ATRIUM SPACES SHALL |
| | SEPERATED FROM ADJACENT SPACES BY A |
| | 1-HR FIRE SEPERATION WALL. THE |
| | MECHANICAL PLAN DOESN'T INDICATE ANY |
| | FIRE DAMPERS SO THESE AREAS? |
| | 16D) PROVIDE INFORMATION FOR AUTOMATIC |
| | FIRE DETECTION IN ACCORDANCE WITH |
| | 414.6.1 SPOT-TYPE DETECTORS OR BEAM |
| | DETECTORS. |
| | 16D) PROVIDE INFORMATION, 414.7 STANDBY |
| | POWER. ALL EQUIPMENT REQUIRED TO PROVIDE |
| | SMOKE CONTROL SHALL BE CONNECTED TO A |
| | STANDBY POWER SYSTEM IN ACCORDANCE WITH |
| | 412.7. |
| | 16E) 414.10 INTERIOR FINISH. THE |
| | INTERIOR FINISH OF WALLS AND CEILINGS OF |
| | THE ATRIUM SHALL NOT EXCEED CLASS B WITH |
| | NO REDUCTION IN CLASS FOR SPRINKLER |
| | PROTECTION. |
| | 16F) PLEASE PROVIDE AREA CALCULATIONS |
| | FOR THE FIRST FLOOR OF THE ATRIUM AND |
| | THE MEZZANINE LEVEL 503.2.3.2. |
| | 16G) MEZZANINE LEVEL MUST MEET THE |
| | REQUIREMENTS OF 1005.7.3 THE SPACE |
| | BENEATH THE MEZZANINE MAY BE ENCLOSED |
| | PROVIDEDTHE ENCLOSED SPACE IS |
| | PROTECTED THROUGHOUT WITH A SMOKE |
| | DETECTION SYSTEM IN ACCORDANCE WITH NFPA |
| | 72 WHICH SOUNDS AN ALARM IN THE |
| | MEZZANINE. |
| | |
| | 17) A1.04C THE STAIR TOWERS TO THE LEFT |
| | AND RIGHT OF THE CENTER ASSEMBLY AREA |
| | HAVE EXIT ACCESS CORRIDORS WITH DOORS |
| | # 0302 N&S. WHAT IS THIS ROOM TO BE USED |
| | FOR. IF THIS IS SHAFT INDICATE SUCH. |
| | ALSO NO DOOR SCHEDULE TO INDICATE |
| | RATING. |
| | |
| | 18) THESE SAME STAIR TOWERS INDICATE A |
| | CIRCLE AND SQUARE IN THE LANDINGS OF THE |
| | STAIR TOWER BUT NOT SHOWN ON THE |
| | ENLARGED PLANS A5.07 & A5.08? |
| | |
| | 19) A1.04 INDICATES A HEALTH CLUB NO |
| | WALLS NOR DOORS SHOW RATINGS.A 5.15 |
| | PROVIDES ELEVATIONS BUT NO CROSS SECTION |
| | SHOWING COMPLIANCE WITH A 2HR SHAFT. |
| | |
| | 20) A1.04NE : |
| | A) ELEVATOR LOBBY# 7 HAS SOME |
| | UNIDENTIFIED ITEM WITH A DOOR IN LOBBY? |
| | B) THERE IS NO ELEVATOR LOBBY DOOR |
| | SEPERATING THE LOBBY FROM THE REST OF |
| | THE FLOOR. |
| | C) TELEPHONE ROOM APPEARS TO HAVE NO |
| | DOOR IT APPEARS TO HAVE THE REFUSE CHUTE |
| | IN THE SAME ROOM? |
| | D) ELEVATOR TOWERS# 3&5 INDICATES 2 |
| | DISTINCT ELEVATOR LOBBIES BUT ENTRANCE |
| | IS ONLY ON ONE SIDE? |
| | E) IN FRONT OF UNIT 0317 THERE IS A |
| | AREA THAT APPEARS TO BE A SHAFT?NO |
| | DETAILS OR CUT SECTIONS TO INDICATE |
| | USAGE. |
| | |
| | 21) A1.04 NW : |
| | A) THERE APPEARS TO BE A PASSENGER |
| | LOADING ZONE IN THE GARAGE JUST SOUTH OF |
| | ELEVATOR# 7, PROVIDE PASSENGER LOADING |
| | ZONE, AND ACROSS ELEVATION SECTION |
| | INDICATING CLEAR HEIGHT. |
| | B) NORTH END OF THE PARKING GARAGE HAS |
| | AN OPEN STORAGE AREA, THERE IS NO |
| | OCCUPANCY SEPERATION BETWEEN THE GARAGE |
| | AND STORAGE OCCUPANCY. SEE 411.2.6 |
| | C) THE OPEN STORAGE AREA, WHAT TYPE OF |
| | STORAGE WILL THIS BE TO CONSIDER RATING |
| | OF WALLS & DOORS. |
| | C) AREA NOT LABELED JUST SOUTH OF |
| | COLUMN LINE W-37, PLEASE PROVIDE USAGE? |
| | |
| | 22) A1.04SE AGAIN IT APPEARS THE THE |
| | ELEVATOR LOBBIES SHOULD HAVE ELEVATOR |
| | LOBBY DOORS , SAME OBJECT APPEARS |
| | UNIDENTIFIED OBJECT. |
| | |
| | 23) A1.04SW/ A1.04NW THERE IS A WALKWAY |
| | THAT BACKS UP AGAINST THE VARIOUS |
| | SOCALLED (TOWNHOUSE) UNITS, IT APPEARS |
| | TO BE A CROSSWALK OR MEANS OF EGRESS, |
| | REQUIRING A 44" PATH, THE COLUMNS STICK |
| | OUT CUTTING OF ABOUT 1/2 OF THE PATH OF |
| | TRAVEL. |
| | |
| | 24) A1.04P1: |
| | A) THE SOUTH END OF THE PARKING GARAGE |
| | APPEARS TO HAVE OPEN STORAGE, PROVIDE |
| | OCCUPANCY SEPERATION RATED WALLS AND |
| | DOORS. 411.2.6. |
| | B) PROVIDE INFORMATION FOR THE STEEL |
| | CABLE BARRIER SYSTEM TO WITHSTAND THE |
| | REQUIREMENTS IN 1608.2.3 GUARDRAIL |
| | PARKING. |
| | |
| | 25) A1.05C : |
| | A) CLARIFY, PLANS INDICATE AN ELEVATOR |
| | LOBBY & INDICATE A STORAGE AREA NO WALLS |
| | OR OCCUPANCY SEPERATION? |
| | B) RATING OF ELEVATOR DOOR TO KITCHEN, |
| | WHAT WILL THIS DOOR BE USED FOR?NO NAME |
| | ON PLANS. |
| | C) COVERED TERRACE THE OCCUPANT LOAD IS |
| | GREATER THAN 50 REQUIRING A 2 HR |
| | SEPERATION. |
| | |
| | 26) A1.05NE UNITS DO NOT HAVE EGRESS TO |
| | STAIR TOWER WITHOUT TRAVEL THROUGH THE |
| | ELEVATOR LOBBIES SEE 412.6.2. THE |
| | BEDROOM TERRACE LEVEL, LOCKABLE DOORS, |
| | 1001.1.3, 1012.4 FOR HORIZONTAL SLIDERS |
| | PARTOF A MEANS OF EGRESS. UNIT 512 OK |
| | UNITS THAT DO NOT COMPLY 513,514, 515, |
| | 516 & 517. |
| | |
| | 27 DOOR/ROOM 436 USAGE? |
| | |
| | 28) A1.05SE UNITS DO NOT HAVE EGRESS TO |
| | STAIRS WITHOUT TRAVEL THROUGH THE |
| | ELEVATOR LOBBY, UNITS 411, 410, 409, 408 |
| | & 404. LOCKABLE DOORS 1001.1.3 AND USE |
| | OF HORIZONTAL SLIDERS 1012.4 |
| | |
| | 29) WHEN TENANTS ARE AT THE POOL DECK |
| | WILL THE EXIT PASSAGEWAYS ALLOW ENTRENCE |
| | BACK INTO THE BUILDING? |
| | |
| | 30) A1.05SW: |
| | A) ROOM JUST NORTH OF THE POOL |
| | COLLECTOR TANKS, USAGE? |
| | B) STAIRWAY ( DOOR 401) WHAT WILL THE |
| | VACANT SPACE BE USED FOR WITHIN THE |
| | STAIR TOWER? |
| | B) MAIN POOL AREA, SOUTH END THE CHANGE |
| | IN GRADE IS GREATER THAN 6" GUARD RAILS |
| | OR EDGE TREAMENT SO A WHEELCHAIR COULD |
| | NOT JUST ROLL OVER INTO THE STEPPED |
| | GRASSED AREAS. |
| | C) DECK DRAINS OR GRATES SEE 11-5.4.5. |
| | D) CUT SECTION @ STAIRS 03/A6.11 NO |
| | HANDRAIL GUARDRAIL FOR STAIRS. |
| | E) NOTE STATE STATUTE FOR "EFFECTIVE |
| | BARRIER FOR THE PUBLIC POOLS/ SPAS |
| | D.O.H.64E-9. |
| | F) NOTE PUBLIC POOLS & SPAS |
| | 13-412.1ABCD.2.4.2 COVERED POOLS |
| | |
| | 31) A1.05 P1/P2 CABANA NOTE- SHALL BE |
| | DESIGNED TO 140 MPH WIND, 3 SECOND GUST. |
| | |
| | 32)A1.06NE |
| | A) DETAIL 08/A6.14 THE BLOCK WORK THAT |
| | ABUTTS STRUCTURAL COLUMNS, WHAT TYPE OF |
| | HORIZONTAL TIE IN SYSTEM WILL BE USED/ |
| | B) SAME SECTION INDICATES THE USE OF |
| | VERTICAL REBAR IN THE BLOCK CELLS NEXT |
| | TO OPENINGS, HOW WILL THE REINFORCING |
| | RODS TIE INTO THE SLAB ABOVE FOR THE |
| | HORIZONTAL AND VERTICAL REINFORCEMENT & |
| | TRANSFER OF WALL AND WINDOW/ DOOR |
| | LOADING? |
| | THIS HOLDS TRUE FOR ALL SIMILAR LOADING |
| | ISSUES. |
| | |
| | 33) A1.06NE THIS COMMENT WILL EFFECT |
| | MOST OF THE STAIRWELL, (EXITS) WITHIN |
| | THE BUILDING. THE PLANS INDICATE A EXIT |
| | DOOR THAT LEADS DIRECTLY FROM THE CONDO |
| | UNIT INTO THE SMOKEPROOF EXIT ENCLOSURE. |
| | THE INTENT IS TO HAVE AN EXIT THAT |
| | DOESN'T TRAVEL THROUGH THE ELEVATOR |
| | LOBBY.THE CODE SECTION THAT DOESN'T |
| | ALLOW HABITABLE ROOMS TO EMPTY DIRECTLY |
| | INTO THE EXIT IS: |
| | |
| | 1005.6.7 ACCESS TO THE STAIRWAY SHALL BE |
| | BY WAY OF A VESTIBULE OR BY WAY OF AN |
| | OPEN EXTERIOR BALCONY OF NONCOMBUSTIBLE |
| | MATERIALS. |
| | EXCEPTION: ACCESS BY WAY OF A |
| | VESTIBULE WHEN THE STAIRWAY MEETS THE |
| | REQUIREMENTS OF 1005.6.9.2 (1-3), |
| | 1005.6.9.9 AND 1005.6.9.10 & IS LOCATED |
| | IN A FULLY SPRINKLEREDBUILDING. |
| | PLEASE INDICATE COMPLIANCE. UNITS SUCH |
| | AS 1615 ON SHEET A1.08NE CAN NOT MAKE |
| | THE ROOM CONTAINING THE SECOND EXIT A |
| | LOCKABLE ROOM SUCH AS A BEDROOM. |
| | |
| | 34) A1.10 NE LEVEL 18 SHOWS A STAIR |
| | WITHIN THE UNIT GOING TO THE NEXT LEVEL |
| | BUT THERE IS NO FLOOR PLAN INDICATEING |
| | WHAT IS ON THIS LEVEL? A1.11NE DOES |
| | INDICATE A ROOF PLAN FOR THE NEXT LEVEL, |
| | IT APPEARS THIS IS THE ELEVATOR MACHINE |
| | ROOM LEVEL. DOES THE STAIR BELOW SERVICE |
| | THE ELEVATOR MACHINE ROOM? |
| | |
| | 35) A1.11SE THE SAME SITUATION APPEARS |
| | WITH THE EXCEPTION OF CIRCULAR |
| | STAIRS.PLEASE PROVIDE A FLOOR PLAN FOR |
| | THIS LEVEL. |
| | |
| | 36) PROVIDE THE DRAFT WIND PRESSURE |
| | REPORTCOMPLETED BY RWDI CONSULTING |
| | ENGINEERS, IT APPEARS THE NEGATIVE |
| | PRESSURES ARE LOW. |
| | 1606.1.1 DETERMINATION OF WIND FORCES. |
| | WIND FORCES ON EVERY BUILDING OR |
| | STRUCTURE SHALL BE DETERMINED BY THE |
| | PROVISIONS OF CHAPTER 6 OF ASCE 7-98. |
| | THE SIMPLIFIED FORM WILL NOT WORK ON |
| | THIS BUILDING BECAUSE OF HEIGHT AND THE |
| | SHAPE OF THE BUILDING. |
| | |
| | |
| | 37) A3.04A/ A3.05A INDICATES A |
| | STRUCTURAL STEEL AND GLASS SKYLIGHT TO |
| | BE USED SHOW COMPLIANCE WITH: |
| | A)13-104.4.5 FENESTRATION ENERGY RATING |
| | LABELS. ENERGY PERFORMANCE VALUES (I.E., |
| | U-FACTOR, SOLAR HEAT GAIN COEFFICIENT) |
| | OF FENESTRATION PRODUCTS (I.E., WINDOWS, |
| | DOORS AND SKYLIGHTS) SHALL BE DETERMINED |
| | BY AN ACCREDITED, INDEPENDENT LABORATORY |
| | AND LABELED AND CERTIFIED BY THE |
| | MANUFACTURER. |
| | B) 1604.3 CONCENTRATED FLOOR LIVE LOADS |
| | SKYLIGHT RIBS 200 LBS |
| | C) MUST MEET SMALL MISSLE IMPACT |
| | TESTING 30'-60' FROM THE GROUND. |
| | D) 1707.4.2.1.1 TEST AND LABELING OF |
| | SKYLIGHTS. EXTERIOR SKYLIGHTS SHALL BE |
| | TESTED BY AN APPROVED INDEPENDENT |
| | TESTING LABORATORY, AND SHALL BE LABELED |
| | WITH AN APPROVED LABEL IDENTIFYING THE |
| | MANUFACTURER, PERFORMANCE |
| | CHARACTERISTICS AND APPROVED PRODUCT |
| | EVALUATION ENTITY TO INDICATE COMPLIANCE |
| | WITH THE REQUIREMENTS OF THE FOLLOWING |
| | SPECIFICATION: AAMA/WDMA 1600/IS7, |
| | VOLUNTARY SPECIFICATION FOR SKYLIGHTS OR |
| | TAS 202 (HVHZ SHALL COMPLY WITH TAS 202) |
| | E)2405.3.2 SLOPED GLAZING.GLASS SLOPED |
| | MORE THAN 15 DEGREES (0.26 RAD) |
| | FROM VERTICAL IN SKYLIGHTS, SUNSPACES, |
| | SLOPED ROOFS AND OTHER EXTERIOR |
| | APPLICATIONS SHALL BE CHOSEN TO RESIST |
| | THE APPLICABLE LOADS FOR COMPONENTS |
| | AND CLADDING.THE ALLOWABLE COMBINED |
| | LOAD FOR THE GLASS SHALL BE DETERMINED |
| | IN ACCORDANCE WITH ?2405.3.2.1 THROUGH |
| | ?2405.3.2.3. |
| | |
| | 38) PROVIDE DETAILS FROM THE PRE-CAASST |
| | SPECIALTY ENGINEER HOW SYSTEM ISTO BE |
| | ASSEMBLED. WHAT TYPE MATERIAL IS TO BE |
| | USED, FORCES TO BE RESISTED, UPLIFT, |
| | LATERAL LOADS AND GRAVITY LOADS. |
| | |
| | 39) A3.09 DETAIL# 2FL BLD CODE |
| | 104.2.1.2 ADDITIONAL INFORMATION |
| | REQUIRED, PROVIDE INFORMATION ON THE |
| | TENSILE FABRIC & CANOPY STRUCTURE. |
| | |
| | 40)*******VERY IMPORTANT NOTE*********** |
| | *************FOR CONTRACTOR************ |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 41) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED, STOREFRONT, OPERTABLE |
| | PASS THROUGHS OR GLASS BLOCK |
| | B)EXTERIOR DOORS, SOLID, SWING, GLAZED |
| | SLIDERS ROLL UP |
| | C) MULLIONS BOTH VERTICAL & HORIZONTAL |
| | D) SKYLIGHTS |
| | E) EXTERIOR VENTS OR LOUVERS |
| | F) EXTERIOR GUARDRAILS |
| | G) PANEL WALL SYSTEMS: SOFFITS, EFIS |
| | SYSTEMS, DENSEGLASS |
| | H) LOUVERS |
| | I) ROOFING PRODUCTS/ ASSEMBLIES |
| | |
| | 42)1707.4.4.1 ANCHOR REQUIREMENTS: |
| | WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| | ED IN ACCORDANCE WITH THE PUBLISHED |
| | MANUFACTURER'S RECOMMENDATIONS TO |
| | ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| | SUBSTITUTE ANCHORING SYSTEM USED FOR |
| | THE SUBSTRATE NOT SPECIFIED BY THE |
| | FENESTRATION MANUFACTURER SHALL PROVIDE |
| | EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| | TED BY ACCEPTED ENGINEERING PRACTICES. |
| | |
| | 43)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 44) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED STATE TESTING |
| | LABORATORY OR BE ENGINEERED. IF TO BE |
| | USED IN CONJUNCTION WITH GLAZED UNITS |
| | WITH LARGE MISSLE TESTING THE MULLION |
| | ALSO REQUIRES LARGE MISSLE TESTING. |
| | |
| | 45) A3.10 DETAIL# 2 INDICATES ATTACHMENT |
| | OF LIMESTONE VENEER, PROVIDE THE WEIGHT |
| | PSF, METHOD OF ATTACHMENT, SPACING OF |
| | FASTENERS SEE SECTION 1403 FOR VENEER |
| | WALLS . |
| | |
| | 46) A4.00 DETAIL# 3 PROVIDES A DETAIL |
| | FOR SOFITS AND DROPPED CEILING. THE PLAN |
| | DOES NOT INDICATE HOW OFTEN THE TOP |
| | PLATE IS TO BE SECURED TO THE CONCRETE |
| | DECK NOR DOES THE DETAIL INDICATE WHAT |
| | THE LIMITATION IS FOR BRACING AT THE MID |
| | SPAN. THE PLAN DOESN'T INDICATE WHAT |
| | CENTERS THE FRAMING IS TO BE PLACED OR |
| | SCREW ATTACHMENT. |
| | |
| | 47) A4.00 DETAIL # 5 INDICATES THE USE |
| | OF WOOD BUCKS. 609.2.1 TYPE I AND TYPE |
| | II CONSTRUCTION. PARTITIONS SHALL BE |
| | CONSTRUCTEDOF NONCOMBUSTIBLE |
| | MATERIALS.EXCEPTIONS: 1. FRAMING MEMBERS |
| | MAY BE OF FIRE RETARDANT TREATED WOOD. |
| | |
| | 48) DETAIL# 2 INDICATES THE USE OF EFIS |
| | TRIM, SEE 1404.1.1 TYPE I BUILDINGS THAT |
| | ARE NOT OVER 3 STORIES OR 40' MAY HAVE |
| | TYPE VI TRIM. |
| | |
| | 49) A6.01 RAILING DETAIL INDICATES TWO |
| | INCHES CLEAR FROM THE BOTTOM RAIL TO THE |
| | DECK.1015.3 OPENINGS. A BOTTOM RAIL OR |
| | CURB SHALL BE PROVIDED THAT WILL REJECT |
| | THE PASSAGE OF 2-INCH (51 MM) DIAMETER |
| | SPHERE. |
| | |
| | 50) A6.06 MAIN GLASS CANOPY, PROVIDE |
| | INFORMATION ON THE CANOPY SYSTEM. ALSO |
| | PROVIDE INFORMATION ON THE GLAZING |
| | SYSTEM INDICATING COMPLIANCE WITH |
| | 2407.2.1 ALLOWABLE GLAZING MATERIALS. |
| | |
| | 51) A6.08 DETAI# 19 MAIN LOBBY |
| | HORIZONTAL SLIDING DOORS, PROVIDE THE |
| | MANUFACTURER SPECS FOR CODE COMPLIANCE |
| | WITH 1012.4 (1-9) |
| | |
| | 52)SHEET AC-02: |
| | 52A) THERE APPEARS TO BE A DESCREPANCY |
| | BETWEEN AC-02 NORTH END OF BUILDING |
| | WHERE THE INTAKE LOUVERS ARE INDICATES |
| | THIS TO BE AN ELECTRICAL ROOM VS A1.03 |
| | WHICH CALLS FOR OPEN STORAGE. OCCUPANCY |
| | SEPERATION FROM THE PARKING GARAGE. |
| | 52B) THE SAME SITUATION IS ON THE SOUTH |
| | END OF THE PARKING GARAGE WITH THE EF |
| | 23,24,& 25. PROVIDE A SECTION THROUGH |
| | THIS AREA AND THE OPEN AREA TO THE |
| | SOUTH. |
| | |
| | 53) THE SAME ISSUES AS 52 BUT ON AC-03. |
| | |
| | 54) P-2 INDICATES PLUMBING IN THE EXIT |
| | TOWERS, TOWER 5 STAIR A, TOWER8 STAIR A. |
| | 1006.1.3.1 PENETRATIONS INTO OPENINGS |
| | THROUGH A STAIRWAY ENCLOSURE ASSEMBLY |
| | ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, DUCTWORK AND EQUIPMENT NECESSARY |
| | FOR INDEPENDENT STAIR PRESSURIZATION, |
| | SPRINKLER PIPING, STANDPIPES AND |
| | ELECTRICAL CONDUIT SERVING THE |
| | STAIRWAY AND TERMINATING AT A STEEL BOX |
| | NOT EXCEEDING 16 SQ IN. (0.010 M^2). |
| | SUCH PENETRATIONS SHALL BE PROTECTED IN |
| | ACCORDANCE WITH ?705.4.THERE SHALL BE NO |
| | PENETRATIONS OR COMMUNICATING OPENINGS, |
| | WHETHER PROTECTED OR NOT, BETWEEN |
| | ADJACENT STAIR ENCLOSURES. |
| | |
| | 55)P-13 INDICATES A 4" RAIN WATER LITER |
| | IN EXIT NOTE "TO BUILD 2HR SOFFIT W/ |
| | ACCESS PANEL". 1006.1.4 THERE SHALL BE |
| | NO USABLE SPACE WITHIN AN EXIT ENCLOSURE |
| | |
| | 56) 1016.4 STAIR IDENTIFICATION. AN |
| | APPROVED SIGN SHALL BE LOCATED AT EACH |
| | FLOOR LEVEL LANDING IN ALL ENCLOSED |
| | STAIRWAYS OF BUILDINGS FOUR OR MORE |
| | STORIES IN HEIGHT.THE SIGN SHALL |
| | INDICATE THE FLOOR LEVEL AND THE |
| | AVAILABILITY OF ROOF ACCESS FROM THAT |
| | STAIRWAY AND AN IDENTIFICATION OF THE |
| | STAIRWAY.THE SIGN SHALL ALSO STATE THE |
| | FLOOR LEVEL OF AND DIRECTION TO |
| | EXIT DISCHARGE.THE SIGN SHALL BE |
| | LOCATED APPROXIMATELY 5 FT (1524 MM) |
| | ABOVE THE FLOOR LANDING IN A POSITION |
| | WHICH IS READILY VISIBLE WHEN THE |
| | DOOR IS IN THE OPEN OR CLOSED POSITION. |
| | |
| | 57) 412.8.1 ALL STAIRWAY DOORS WHICH ARE |
| | TO BE LOCKED FROM THE STAIRWAY SIDE |
| | SHALL HAVE THE CAPABILITY OF BEING |
| | UNLOCKED SIMULTANEOUSLY WITHOUT |
| | UNLATCHING UPON A SIGNAL FROM THE |
| | CENTRAL CONTROL STATION.THE DOORS |
| | SHALL BE SIMILARLY UNLOCKED UPON |
| | ACTIVATION OF THE SPRINKLER SYSTEM OR |
| | UPON POWER FAILURE. |
| | |
| | 412.8.2 TELEPHONE OR OTHER TWO-WAY |
| | COMMUNICATIONS SYSTEMS CONNECTED TO AN |
| | APPROVED EMERGENCY SERVICE WHICH |
| | OPERATES CONTINUOUSLY SHALL BE |
| | PROVIDED AT NOT LESS THAN EVERY FIFTH |
| | FLOOR IN EACH REQUIRED STAIRWAYWHERE |
| | OTHER PROVISIONS OF THIS CODE PERMIT THE |
| | DOORS TO BE LOCKED. |
| | |
| | 58) PROVIDE SIGNAGE AS REQUIRED BY |
| | 11-4.30 OF FL ACCESSIBILITYAS WELL AS |
| | FAIRHOUSING ANSI 117.1 703 FOR STAIRS |
| | AND OTHER REQUIRED ELEMENTS. |
| | |
| | 59) **STRUCTURAL WIND DESIGN LOADS** |
| | SHEET S0.02 INDICATE THE WIND DESIGN IS |
| | TAKEN FROM ASCE7-98 WITH A "EXPOSURE "C" |
| | THE PRESSURES ARE LOW FOR A BUILDING OF |
| | OVER 185'. TABLES FROM ASCE 7-88 FOR |
| | 180' BUILDING FOR END ZONES INDICATE |
| | 139.1 FOR END ZONES ON A TRIBUTARY AREA |
| | OF 20', WHY ARE THE PRESSURES SO LOW |
| | PROVIDE CALCULATIONS. WE LOOK FOR WINDOW |
| | AND DOOR PRESSURES +/- FOR OPENINGS IN |
| | BOTH, END ZONES AS WELL AS THE INTERIOR |
| | ZONES & THEIR TRIBUTARY AREA. THIS IS |
| | CRUCIAL INFORMATION REQUIRED FOR THE |
| | CONTRACTORS TO PROVIDE THE CORRECT |
| | WINDOW OR DOOR FOR THE REQUIRED |
| | PRESSURES. |
| | |
| | 60) SHEET S0.02 INDICATES WORK NOT |
| | COVERED BY THE ENGINEER OF RECORD WITH |
| | NOTE 7825 SPECIALTY ENGINERED ITEMS, |
| | THE ITEMS THAT COMPOSE COMPONENTS AND |
| | CLADDING TO ENCLOSE THE BUILDING WILL |
| | NEED TO SUPPLY TECHNICAL DATA FOR THE |
| | BUILDING TO BE PERMITTED.ADDITIOAL |
| | INFORMATION REQUIRED. FL BLD CODE |
| | 104.2.1.2*OTHER SPECIALTIES AS THE POOL |
| | WILL BE PERMITTED SEPERATELY. |
| | |
| | 61) STRUCTURAL SHEET S4.05 HAS A NOTE |
| | ABOUT HDS SEE NOTES, WHERE? CONCERNS |
| | ABOUT 707.1 CONCEALED SPACES IN TYPES I, |
| | II AND IV CONSTRUCTION.COMBUSTIBLES |
| | SHALL NOT BE PERMITTED IN CONCEALED |
| | SPACES OF TYPES I, II OR IV |
| | CONSTRUCTION. |
| | |
| | 62) DEALS WITH THE REQUIEMENTS FOR FIRE |
| | RESISTANCY IN TABLE 600 FOR A TYPE I |
| | BLDG. COLUMNS SUPPORTING MORE THAN 1 |
| | FLOOR REQUIRE A 4 HR RATING. SUPPORTING |
| | 1FLOOR ONLY A 3 HR RATING. TABLE 709.2.4 |
| | |
| | PROVIDES THE MINIMUM DIMENSION FOR THE |
| | FIRE RATED COLUMNS PROVIDE THE TYPE OF |
| | CONCRETE TO BE USED, THEN MINIMUM FIRE |
| | RESISTANCY OF COLUMNS CAN BE VERIFIED. |
| | PLEASE NOTE ON S6.01, S6.02 & S6.03. |
| | |
| | 63) S6.02 IDENTIFIES THE DIFFERENT TYPES |
| | OF HOOPS TO BE USED BY CONFIGURATION. |
| | PLEASE PROVIDE THE DIMENSIONS FOR THE |
| | MINIMUM REQUIRED COVERAGE OF STEEL IN |
| | 709.2.4.2. |
| | |
| | 64) A5.07-A5.13 SSTAIR TOWERS STAIRS TO |
| | COMPLY WITH1007.1.2 STAIRWAYS LOCATED |
| | IN A REQUIRED FIRE RESISTANT ENCLOSURE |
| | SHALL HAVE CLOSED RISERS. |
| | |
| | 65) PLANS TO INDICATE COMPLIANCE WITH: |
| | 1015.3 OPENINGS. OPEN GUARDRAILS SHALL |
| | HAVE INTERMEDIATE RAILS OR ORNAMENTAL |
| | PATTERN SUCH THAT A 4-INCH (102 MM) |
| | DIAMETER SPHERE CANNOT PASS THROUGH ANY |
| | OPENING UP TO A HEIGHT OF 34 INCHES.A |
| | BOTTOM RAIL OR CURB SHALL BE PROVIDED |
| | THAT WILL REJECT THE PASSAGE OF 2-INCH |
| | (51 MM) DIAMETER SPHERE. |
| | EXCEPTIONS: |
| | 1. A 6 INCH (152 MM) SPHERE SHALL NOT |
| | PASS THROUGH THE TRIANGULAR OPENING |
| | FORMED BY A TREAD, RISER AND BOTTOM OF A |
| | GUARDRAIL. |
| | |
| | |
| | THE ANSWERS TO THE LISTED QUESTIONS |
| | ABOVE MAY RESULT IN MORE QUESTIONS IN |
| | THE NEXT REVIEW. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |