| 2005-07-25 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)PLEASE VOID PERMIT #05051023 AS YOU |
| | HAVE NOW APPLIED FOR THE SAME SCOPE OF |
| | WORK UNDER A DIFFERENT PERMIT NUMBER. |
| | |
| | 2.)PROVIDE CURRENT STRUCTURAL PLANS |
| | FOR THE SCREEN ROOM ADDITIONK, |
| | FBC104.2.1, 104.3.1.1, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO THE FBC.INCLUDE |
| | DESIGN CRITERIA FBC1606.1.7. |
| | |
| | 3.)THE OLD ENGINEERING DATED 5/6/04 |
| | CANNOT BE USED DUE TO THE FOLLOWING: |
| | |
| | A.)THE SCREEN ENCLOSURE PLAN DOES NOT |
| | HAVE A TITLE BLOCK FAC61G15-23.002. |
| | |
| | B.)THE COMPANY ANDREW MORGAN SERVICES |
| | IS REQUIRED TO HAVE A CERTIFICATE OF |
| | AUTHORIZATION.BOTH THE CA NUMBER AND |
| | THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT ARE TO BE ON THE PLAN. |
| | |
| | C.)THE PLANS WERE PREPARED PRIOR TO |
| | THE HURRICANES OF SEPTEMBER 2004.AFTER |
| | THE FAILURE OF MANY SCREEN ENCLOSURES IT |
| | WAS DETERMINED THAT MANY ENGINEERS HAD |
| | BEEN USING THE 1/3 STRESS INCREASE WHICH |
| | IS NOT ALLOWED FBC1609.4.3(2).IF MR. |
| | ANDREW RECERTIFIES THE SAME ENGINEERING |
| | WITH A NEW DATE, HAVE HIM INCLUDE A NOTE |
| | INDICATING THAT HE HAS DESIGNED THIS |
| | ENCLOSURE WITHOUT THIS STRESS INCREASE. |