05070977 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | REDLINED | | | | | | SHOW WINDOW LENGTH TO BE VERIFIED IN | | | FEILD. 210.62 | | | | | | LOAD ON PANEL STILL SHOWN AS 6KW, DEMAND | | | LOAD WAS CORRECTED. | | | | | | GFI CIRCUITS IN KITCHEN ONLY REQUIRED | | | PER 210.8B3 WHICH REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NONDWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. |
|