| 2005-08-01 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE LOAD CALCULATIONS ON |
| | THE RIGHT SIDE OF PANEL SCHEDULE. PLEASE |
| | SEE LOAD ADDS UP TO 6KW, HOWEVER, LOADS |
| | LISTED ON PANEL SCHEDULE ADDS UP TO MORE |
| | THAN TOTAL OF 6KVA.? |
| | PLEASE SEE 220,215.5 |
| | |
| | 2)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | |
| | 3)NOTE: PLEASE SEE CIRCUITING FOR |
| | "SHOW/DISPLAY WINDOW" RECEPTS, PLEASE |
| | ALSO SEE # OF RECEPTS FOR EACH12 |
| | LINEAR FT, OR POSTION THERE-OF. |
| | 210.62,220.12 |
| | |
| | 4)NOTE: PLEASE SHOW THE "EXISTING" SIGN |
| | CIRCUIT J-BOX LOCATION ETC ON PLANS. |
| | |
| | PLEASE ANY POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |