| 2005-10-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 1. ALL ARCHITECTURAL SHEETS REQUIRE THE |
| | SEAL TO BE DATED WHEN AFFIXED TO THE |
| | PLANS. FAC 61G1-16.003 - 61G1-16.004(5) |
| | AND FS 481.2055. - FIRM LICENSE NUMBER |
| | REQUIRED IN THE TITLE BLOCK PER FAC |
| | 61G1-16.004(2) & FS 481.219 - 481.2055. |
| | 2. PER TABLE 403.1 AND SECTION 403.2 |
| | SEPARATE FACILITIES ARE REQUIRED FOR |
| | EACH SEX. BOTH TOILET ROOMS ARE |
| | REQUIRED. RESPONSE NOTED, BUT REFERENCE |
| | TO EMPLOYEE NOTE FOUND ON SHT A0.0. |
| | PLEASE CLARIFY. |
| | 3. MECHANICAL SHEETS AND ELECTRICAL |
| | SHEETS, A CERTIFICATE OF AUTHROIZATION |
| | IS REQUIRED FOR THE ENGINEERING BUSINESS |
| | FOR EACH SHEET, |
| | **************NEW COMMENT*************** |
| | 1B. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | FOR THE DRINKING FOUNTAIN. |
| | 2B. SUBMIT A SANT. AND A WATER RISER |
| | DIAGRAM FOR THE DRINKING FOUNTAIN |
| | SHOWING ALL PIPE SIZES, TRAPS, VENTS, |
| | AND POINTS OF CONNECTION FOR SANT. AND |
| | PIPE SIZES, VALVES, AND WATER HAMMER |
| | ARRESTOR, (IF REQUIRED BY SECTION |
| | 604.9), AND POINT OF CONNECTION FOR |
| | WATER. - NO DRINKING FOUNTAIN IS SHOWN |
| | ON THE DEMO/EXISTING SHEET TO INDICATE |
| | THE LOCATION OF EXISTING DRINKING |
| | FOUNTAIN. |
| | |
| | REVIEW BY KEN STEVENS |