2005-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. ALL ARCHITECTURAL SHEETS REQUIRE THE
 SEAL TO BE DATED WHEN AFFIXED TO THE
 PLANS. FAC 61G1-16.003 - 61G1-16.004(5)
 AND FS 481.2055. - FIRM LICENSE NUMBER
 REQUIRED IN THE TITLE BLOCK PER FAC
 61G1-16.004(2) & FS 481.219 - 481.2055.
 2. PER TABLE 403.1 AND SECTION 403.2
 SEPARATE FACILITIES ARE REQUIRED FOR
 EACH SEX. BOTH TOILET ROOMS ARE
 REQUIRED. RESPONSE NOTED, BUT REFERENCE
 TO EMPLOYEE NOTE FOUND ON SHT A0.0.
 PLEASE CLARIFY.
 3. MECHANICAL SHEETS AND ELECTRICAL
 SHEETS, A CERTIFICATE OF AUTHROIZATION
 IS REQUIRED FOR THE ENGINEERING BUSINESS
 FOR EACH SHEET,
 **************NEW COMMENT***************
 1B. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAIN.
 2B. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM FOR THE DRINKING FOUNTAIN
 SHOWING ALL PIPE SIZES, TRAPS, VENTS,
 AND POINTS OF CONNECTION FOR SANT. AND
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTOR, (IF REQUIRED BY SECTION
 604.9), AND POINT OF CONNECTION FOR
 WATER. - NO DRINKING FOUNTAIN IS SHOWN
 ON THE DEMO/EXISTING SHEET TO INDICATE
 THE LOCATION OF EXISTING DRINKING
 FOUNTAIN.
  