2005-09-10 00:00:00********** UNSAT 2ND REVIEW ***********
  
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE:
 A)PLEASE SEE MISSING REQUIRED
 INFORMAITON ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 FIRM. FAC 61G1-16.004 AND FS 481.219
  
 ***************************************
 PLEASE SEE THIS WAS NOT CORRECTED AN D
 TITLE BLOCKS FOR ALL FIRMS ARE STILL
 MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATIONS NUMBERS FOR SAID FIRMS AS
 REQUIRED PER ABOVE REFERENCE FLORIDA
 STATUES AND FLORIDA AMINISTRATIVE CODES.
 ***************************************
  
 B)PLEASE SEE MISSING INFORMATION FOR
 ENGINEERING FIRM. MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE THAT ALL SETS SHALLCONTAIN
 ORIGINAL SIGNATURE, DATE AND RAISED
 SEALED.
 PLEASE SEE ABOVE REQUIRED UNDER FAC
 61G15-23.002, FS 471.023 AND FS 471.025
 *** PLEASE SEE THIS WAS NOT DONE***
  
  
  
 ** PLEASE SEE PLANS APPEAR TO BE SIGNED
 WITH INITIALS?, IF INDEED THIS IS THE
 LEGAL SIGNATURE FOR ENGINEER OF RECORD,
 PLEASE PROVIDE AND SIGNED, DATED, SEALED
 AND NOTORIZED LETTER FOR SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 THIS LTR WILL BE REQUIRED TO BE
 NOTORIZED UNDER THE STATUES IN THE STATE
 WHICH THENOTORIZATION WOULD TAKE
 PLACE.
 PLEASE SEE FS 117 FOR ANY QUESTIONS ON
 GUIDELINES AND POSSIBLE INFORMATION
 NEEDED.
 **************************************
 PLEASE SEE NO RESPONSE LTR FROM ENGINEER
 OF RECORD COULD BE LOCATED.
 PLEASE ALSO SEE NO LETTER FOR LEGAL
 SIGNATURE VERIFICATION COULD BE LOCATED
 IN PACKAGE OR PLANS?
 ***************************************
  
  
 PLEASE SEE THAT PARTS "A & B" OF NOTE
 ONE IS REQUIRED OF ALL TRADES AND FOR
 ALL PLANS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PLEASE ALSO SEE ONE SET OF
 ARCHITECTURUAL PLANS WERE NOT DATED BY
 THE ARCHITECT.
  
 2)NOTE: PLEASE SEE "NOTES" TO ELECTRICAL
 PLANS WHICH REFERENCES THE 1999 NEC.
 PLEASE SEE AS OF JULY 1ST, 2003, THE
 2002 NEC IS ADOPTED BY THE STATE.
  
 ***SAME COMMENT**** PLEASE SEE PLANS.
  
 3)NOTE: PLEASE SEE EXISTING EQUIPMENT
 GROUNDING METHODS FOR ALL EQUIPMENT WILL
 BE REQUIRED TO VERIFIED IN FIELD AND CNA
 BE SET UP AS A "PROVSIO".
  
 4)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONALS AND PLANS WITH
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE BE SURE TO SEE NOTE # 1 AND #2.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE COPY OF OLD.VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 PLEASE CALL IF THERE ARE ANY QUESTIONS
 ABOUT COMMENTS ONE AND TWO.
 TO DATE, FROM FIRST REVIEW, NO CALLS
 HAVE BEEN MADE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717