| Plan Review Notes For Permit 05070949 |
| Permit Number |
05070949 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | DENIED: | | | 1. PLEASE PROVIDE LICENSE # AS REQUIRED | | | BY FS 471.025. PLEASE NOTE, BOTH COPIES | | | SUBMITTED ARE TO BE SIGNED, SEALED & | | | DATED IN ACCORDANCE WITH FAC | | | 61GA5-023.002 (2) & PER 2001 FBC | | | 104.2.1. | | | | | | 2. PLEASE PROVIDE CERTIFICATE OF | | | AUTHORIZATION NUMBER FOR THE | | | ARCHITECTURAL FIRM AS REQUIRED BY FAC | | | 61G1-16.004. | | | | | | 3. NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM. | | | | | | 4. FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION REQUIRED PER 2001 | | | FBC(M)606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|