2005-08-18 00:00:00DENIED:
 1. PLEASE PROVIDE LICENSE # AS REQUIRED
 BY FS 471.025. PLEASE NOTE, BOTH COPIES
 SUBMITTED ARE TO BE SIGNED, SEALED &
 DATED IN ACCORDANCE WITH FAC
 61GA5-023.002 (2) & PER 2001 FBC
 104.2.1.
  
 2. PLEASE PROVIDE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM AS REQUIRED BY FAC
 61G1-16.004.
  
 3. NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 4. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION REQUIRED PER 2001
 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  