| Plan Review Notes For Permit 05070949 |
| Permit Number |
05070949 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT NFPA 101, 2003 | | | EDITION SHALL BE REFERENCED. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE DISTRIBUTED TO SATISFY THE 75' | | | TRAVEL DISTANCE REQUIREMENT. | | | | | | 3) PLEASE SHOW REQUIRED ADDRESS ON | | | BUILDING IF NEW OR EXISTING. MINIMUM 6" | | | FOR MAIN ADDRESS AND 3" FOR INDIVIDUAL | | | UNIT OR SUITE. | | | | | | 4) PLANS SHOW MIXED OCCUPANCY. HOW WILL | | | THIS WORK IMPACT EXISTING FIRE | | | PROTECTION EQUIPMENT FOR BUILDING? | | | | | | 5) PLEASE SEE OTHER REVIEW COMMENTS | | | REGARDING FS AND FAC REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN/CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|