Plan Review Notes
Plan Review Notes For Permit 05070949
Permit Number 05070949
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-08-24 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT NFPA 101, 2003
 EDITION SHALL BE REFERENCED.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE DISTRIBUTED TO SATISFY THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 3) PLEASE SHOW REQUIRED ADDRESS ON
 BUILDING IF NEW OR EXISTING. MINIMUM 6"
 FOR MAIN ADDRESS AND 3" FOR INDIVIDUAL
 UNIT OR SUITE.
  
 4) PLANS SHOW MIXED OCCUPANCY. HOW WILL
 THIS WORK IMPACT EXISTING FIRE
 PROTECTION EQUIPMENT FOR BUILDING?
  
 5) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS.
  
  
 MIKE WENNERGREN/CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722