| 2005-08-01 00:00:00 | *********** UNSAT *********** |
| | |
| | 1)NOTE: |
| | A)PLEASE SEE MISSING REQUIRED |
| | INFORMAITON ON TITLE BLOCK FOR |
| | ARCHITECTURAL FIRM. MISSING PRINTED NAME |
| | AND LICENSE # FOR ARCH AND MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | FIRM. |
| | FAC 61G1-16.004 AND FS 481.219 |
| | |
| | B)PLEASE SEE MISSING INFORMATION FOR |
| | ENGINEERING FIRM. MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER, MISSING THE |
| | PRINTED NAME AND LICENSE NUMBER OF PE. |
| | PLEASE SEE, ONE SET OF PLANS ARE |
| | "PHOTOCOPIES" OF THE SEIGNED, DATED AND |
| | SEALED PLANS. PLEASE SEE THAT ALL SETS |
| | SHALLCONTAIN ORIGINAL SIGNATURE, DATE |
| | AND RAISED SEALED. |
| | PLEASE SEE ABOVE REQUIRED UNDER FAC |
| | 61G15-23.002, FS 471.023 AND FS 471.025 |
| | ** PLEASE SEE PLANS APPEAR TO BE SIGNED |
| | WITH INITIALS?, IF INDEED THIS IS THE |
| | LEGAL SIGNATURE FOR ENGINEER OF RECORD, |
| | PLEASE PROVIDE AND SIGNED, DATED, SEALED |
| | AND NOTORIZED LETTER FOR SIGNATURE |
| | VERIFICATION. THIS WILL BE PLACED IN OUR |
| | SIGNATURE FILE FOR ANY FUTURE REFERENCE. |
| | THIS LTR WILL BE REQUIRED TO BE |
| | NOTORIZED UNDER THE STATUES IN THE STATE |
| | WHICH THENOTORIZATION WOULD TAKE |
| | PLACE. |
| | PLEASE SEE FS 117 FOR ANY QUESTIONS ON |
| | GUIDELINES AND POSSIBLE INFORMATION |
| | NEEDED. |
| | |
| | |
| | PLEASE SEE THAT PARTS "A & B" OF NOTE |
| | ONE IS REQUIRED OF ALL TRADES AND FOR |
| | ALL PLANS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE "NOTES" TO ELECTRICAL |
| | PLANS WHICH REFERENCES THE 1999 NEC. |
| | PLEASE SEE AS OF JULY 1ST, 2003, THE |
| | 2002 NEC IS ADOPTED BY THE STATE. |
| | |
| | 3)NOTE: PLEASE SEE RISERAND NOTES TO |
| | RISER DO NOT MENTION THE REQUIRED |
| | "EQUIPMENT GROUNDING" CONDUCTORS. |
| | PLEASE ALSO CLARIFY METHID OF EQUIPMENT |
| | GROUNDING FROM MAIN IN MAIN ELECTRICLA |
| | ROOM AND MAIN/ GUTTER AT TENANT SPACE. |
| | PLEASE SEE 250.110,250.30 ETCSIZING |
| | PER 250.66,250.122 |
| | |
| | 4)NOTE: PLEASE CLARIFY THE NUMBER OF |
| | CIRCUITS SHOWN FOR EACH PANEL. ? PLEASE |
| | SEE ONLY TWO PANELS ARE SHOWN ON RISER , |
| | HOWEVER EACH PANEL APPEARS TO CAONTAIN |
| | "FEED-THRU" LUGS TO FEED A SECTION |
| | "TWO"? |
| | PLEASESEE 408.15 |
| | IFMORE THAN TWO PANELS, PLEASE |
| | INDICATE ON RISER AND PLANS.215.5 |
| | PLEASE ALSO SEE MAIN, GUTTER ETC ARE NOT |
| | SHOWN ON PLANS. COULD ONLY LOCATED |
| | PANELS LP1 AND LP2 AND TRANSFORMER. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER TRADES WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STMAPING. |
| | ONE COPY OF OLD.VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-07-28 00:00:00 | IN ELEC FOR REVIEW |