2005-08-01 00:00:00*********** UNSAT ***********
  
 1)NOTE:
 A)PLEASE SEE MISSING REQUIRED
 INFORMAITON ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. MISSING PRINTED NAME
 AND LICENSE # FOR ARCH AND MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 FIRM.
 FAC 61G1-16.004 AND FS 481.219
  
 B)PLEASE SEE MISSING INFORMATION FOR
 ENGINEERING FIRM. MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, MISSING THE
 PRINTED NAME AND LICENSE NUMBER OF PE.
 PLEASE SEE, ONE SET OF PLANS ARE
 "PHOTOCOPIES" OF THE SEIGNED, DATED AND
 SEALED PLANS. PLEASE SEE THAT ALL SETS
 SHALLCONTAIN ORIGINAL SIGNATURE, DATE
 AND RAISED SEALED.
 PLEASE SEE ABOVE REQUIRED UNDER FAC
 61G15-23.002, FS 471.023 AND FS 471.025
 ** PLEASE SEE PLANS APPEAR TO BE SIGNED
 WITH INITIALS?, IF INDEED THIS IS THE
 LEGAL SIGNATURE FOR ENGINEER OF RECORD,
 PLEASE PROVIDE AND SIGNED, DATED, SEALED
 AND NOTORIZED LETTER FOR SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 THIS LTR WILL BE REQUIRED TO BE
 NOTORIZED UNDER THE STATUES IN THE STATE
 WHICH THENOTORIZATION WOULD TAKE
 PLACE.
 PLEASE SEE FS 117 FOR ANY QUESTIONS ON
 GUIDELINES AND POSSIBLE INFORMATION
 NEEDED.
  
  
 PLEASE SEE THAT PARTS "A & B" OF NOTE
 ONE IS REQUIRED OF ALL TRADES AND FOR
 ALL PLANS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE "NOTES" TO ELECTRICAL
 PLANS WHICH REFERENCES THE 1999 NEC.
 PLEASE SEE AS OF JULY 1ST, 2003, THE
 2002 NEC IS ADOPTED BY THE STATE.
  
 3)NOTE: PLEASE SEE RISERAND NOTES TO
 RISER DO NOT MENTION THE REQUIRED
 "EQUIPMENT GROUNDING" CONDUCTORS.
 PLEASE ALSO CLARIFY METHID OF EQUIPMENT
 GROUNDING FROM MAIN IN MAIN ELECTRICLA
 ROOM AND MAIN/ GUTTER AT TENANT SPACE.
 PLEASE SEE 250.110,250.30 ETCSIZING
 PER 250.66,250.122
  
 4)NOTE: PLEASE CLARIFY THE NUMBER OF
 CIRCUITS SHOWN FOR EACH PANEL. ? PLEASE
 SEE ONLY TWO PANELS ARE SHOWN ON RISER ,
 HOWEVER EACH PANEL APPEARS TO CAONTAIN
 "FEED-THRU" LUGS TO FEED A SECTION
 "TWO"?
 PLEASESEE 408.15
 IFMORE THAN TWO PANELS, PLEASE
 INDICATE ON RISER AND PLANS.215.5
 PLEASE ALSO SEE MAIN, GUTTER ETC ARE NOT
 SHOWN ON PLANS. COULD ONLY LOCATED
 PANELS LP1 AND LP2 AND TRANSFORMER.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE COPY OF OLD.VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]