2005-08-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070949
 ADD: 701 S ROSEMARY # 145
 CONT: HIRSCH CONSTTRUCTION
 TEL: (978)979-1174
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CORRECT THE ADDRESS ON BOTH THE
 APPLICATION AND ON THE PLANS.
  
 3) SEE ELECTRICAL & PLUMBING NOTES FOR:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 STRUCTURAL CALCULATIONS PROVIDED
 INDICATE THAT INPUT PROPERTIES THE STUDS
 WILL HAVE HOLES PUNCHED 1.5"X 4.0" WHERE
 AS THE INPUT PARAMETERS INDICATE THAT
 THE SHEAR AND WEB CRIPPLING CAPACITY IS
 BASED ON " UNPUNCHED WEBS".CLARIFY?
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 THE ZELUCK PRODUCT APPROVALS DO NOT
 APPEAR ON THE FLORIDA WEB SITE. EITHER
 NEW PRODUCT APPROVALS ARE TO BE
 SUBMITTED OR SUBMIT FOR LOCAL WITH THIRD
 PARTY QUALITY ASSURANCE PROGRAM THAT IS
 LISTED WITH THE STATE. SEE LOCAL
 APPLICATION ATTACHED.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 WINDOWS
 DOORS
 EFIS SYSTEMS
  
 6)11-4.35 DRESSING AND FITTING ROOMS.
  
 11-4.35.1 GENERAL. DRESSING AND
 FITTING ROOMS REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.35
 AND SHALL BE ON AN ACCESSIBLE ROUTE.
  
 11-4.35.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN
 SHALL BE PROVIDED IN EVERYACCESSIBLE
 DRESSING ROOM ENTERED THROUGH A SWINGING
 OR SLIDING DOOR.NO DOOR SHALL SWING
 INTO ANY PART OF THE TURNING SPACE.
 TURNING SPACE SHALL NOT BE REQUIRED IN A
 PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 IN.(815
 MM) WIDE IF CLEAR FLOOR SPACE COMPLYING
 WITH 11-4.2 RENDERS THE DRESSING ROOM
 USABLE BY A PERSON USING A WHEELCHAIR.
  
 11-4.35.3 DOORS. ALL DOORS TO ACCESSIBLE
 DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH ?11-4.13.
  
 11-4.35.4 BENCH. EVERY ACCESSIBLE
 DRESSING ROOM SHALL HAVE A 24 IN. BY
 48 IN.(610 MM BY 1220 MM) BENCH FIXED
 TO THE WALL ALONG THE LONGER DIMENSION.
 THE BENCH SHALL BE MOUNTED 17 IN. TO 19
 IN.(430 MM TO 485 MM) ABOVE THE FINISH
 FLOOR.CLEAR FLOOR SPACE SHALL BE
 PROVIDED ALONGSIDE THE BENCH TO ALLOW A
 PERSON USING A WHEELCHAIR TO MAKE A
 PARALLEL TRANSFER ONTO THE BENCH.THE
 STRUCTURAL STRENGTH OF THE BENCH AND
 ATTACHMENTS SHALL COMPLY WITH 11-4.26.3.
  
 11-4.35.5 MIRROR. WHERE MIRRORS ARE
 PROVIDED IN DRESSING ROOMS OF THE SAME
 USE, THEN IN AN ACCESSIBLE DRESSINGROOM,
 A FULL-LENGTH MIRROR, MEASURING AT LEAST
 18 IN. WIDE BY 54 IN. HIGH (460 MM BY
 1370 MM), SHALL BE MOUNTED IN A POSITION
 AFFORDING A VIEW TO A PERSON ON THE
 BENCH AS WELL AS TO A PERSON IN A
 STANDING POSITION.
  
 7)SHEET A2.1 FLAME SPREAD NOTES REFRENCE
 THE UBC CODE TABLE 8-B, CORRECT.
  
 8) SHEET A2.2 REFRENCES A HANDICAPPED
 SIGNAGE PER ADA, SEE CHAPTER 11 FL BLDG
 CODE.
 THE TEXT ENCLOSED IN SHADED BOXES
 INDICATES CHANGES TO THE ADA
 ACCESSIBILITY GUIDELINES (ADAAG).
 CHANGES ARE BASED ON REQUIREMENTS
 ESTABLISHED BY FLORIDA LAW AND
 REQUIREMENTS ESTABLISHED BY 28 CFR 36
 SUBPART A AND D.
  
  
 11-1.1THIS CODE SHALL TAKE EFFECT
 OCTOBER 1, 1997.
  
 11-1.2 ALL NEW OR ALTERED BUILDINGS AND
 FACILITIES SUBJECT TO THIS CODE
 WHICH MAY BE FREQUENTED IN, LIVED IN, OR
 WORKED IN BY THE PUBLIC SHALL
 COMPLY WITH THIS CODE.
  
 11-1.3 THIS CODE ESTABLISHES STANDARDS
 FOR ACCESSIBILITY TO PLACES OF
 PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES BY INDIVIDUALS WITH
 DISABILITIES.THIS CODE SHALL ALSO
 APPLY:TO STATE AND LOCAL GOVERNMENT
 FACILITIES PURSUANT TO ?553.503, FLORIDA
 STATUTES; TO PRIVATE CLUBS
 PURSUANT TO ?553.505, FLORIDA STATUTES;
 AND TO RESIDENTIAL BUILDINGS
 PURSUANT TO ?553.504(2), FLORIDA
 STATUTES.IT IS TO BE APPLIED DURING
 THE DESIGN, CONSTRUCTION, AND ALTERATION
 OF SUCH BUILDINGS AND FACILITIES
 AS REQUIRED BY SECTIONS 553.501-553.512,
 FLORIDA STATUTES.
  
 9) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A2.1 DETAIL 4 & 5 INDICATE AN
 EQUIPMENT PLATFORM, DOES THIS PLATFORM
 CONTINUE OVER THE RESTROOM? PROVIDE THE
 LOADING OF THIS PLATFORM?
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 10) SHEET A3.0 EXTERIOR TRIM , NO WOOD
 EXTERIOR TRIM ALLOWED. SEE:
 1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS
 OF TYPE I, II AND IVCONSTRUCTION NOT
 MORE THAN THREE STORIES OR 40 FT (12.2
 M) HIGH MAY BE OFTYPE VI
 CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGSOF TYPE
 III, V AND VI CONSTRUCTION.TRIM SHALL
 BE SECURED TO THE WALL WITH METAL OR
 OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURALTRIM IS LOCATED
 ALONG THE TOP OF EXTERIOR WALLS, IT
 SHALL BE COMPLETELYBACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIORWALLS.
  
 11) NOTE TRIM ON PAGE 11 INDICATES WOOD
 TRIM.
 NOTE:803.4 FOAM PLASTICS. FOAM PLASTICS
 SHALL NOT BE USED AS INTERIOR FINISH.
  
 EXCEPTION: FOAM PLASTIC TRIM, DEFINED
 AS PICTURE MOLDS, CHAIR RAILS,
 BASEBOARDS, HANDRAILS, CEILING BEAMS,
 DOOR TRIM AND WINDOW TRIM SHALL BE
 PERMITTED TO BE USED PROVIDED:
  
 1. THE MINIMUM DENSITY IS 20 LB/CU FT
 (320 KG/M^3).
  
 2. THE MAXIMUM THICKNESS OF THE TRIM
 IS 1/2 INCH (12.7 MM) AND THE
 MAXIMUM WIDTH IS 4 INCHES (102 MM).
  
 3. THE TRIM CONSTITUTES NO MORE THAN
 10 PERCENT OF THE AREA OF ANY WALL
 OR CEILING.
  
 4. THE FLAMESPREAD RATING DOES NOT
 EXCEED 75 WHEN TESTED PER ASTM E 84.
 THE SMOKE DEVELOPED RATING IS NOT
 LIMITED.
  
 12)A9.0 INDICATES WOOD SUB BUCKS
 609.2.1 TYPE I AND TYPE II CONSTRUCTION.
 PARTITIONS SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS.
  
 13) A9.1 DETAILS INDICATE USE OF WOOD IN
 CONCEALED SPACES:
 707.1 CONCEALED SPACES IN TYPES I, II
 AND IV CONSTRUCTION.COMBUSTIBLES
 SHALL NOT BE PERMITTED IN CONCEALED
 SPACES OF TYPES I, II OR IV
 CONSTRUCTION.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026