| 2005-09-14 00:00:00 | ********** UNSAT ************ |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEWS WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE:PLEASE SHOW ALL RECEPTS SERVING |
| | KTICHEN COUNTERSPACE AS GFI/ GFI |
| | PROTECTED. PER 210.8A6, |
| | PLEASE SEE GFI INDICATION IS ONLY SHOWN |
| | FOR RECEPTS WITH IN 6' OF SINK. |
| | THE CODE CAN NOT BE REFERENCED IN LEIU |
| | OF SHOWING CODE COMPLIANCE. |
| | |
| | 2)NOTE: PLEASE SEE 220.31B WHICH DOES |
| | NOT PERMIT DE-RATING OFAHU HEAT LOADS. |
| | THESE MUST BE FIGURED AT 100%,PELASE |
| | ALSO SEE 1ST 8KW AT 100% AND REMAINDER |
| | AT 40%. |
| | |
| | 3)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU HEAT. MUST BE SIZED A MIN OF |
| | 125% FO RATING. IF AHU 1 IS 10KW, MIN |
| | OCP MUST BE 60A'S. |
| | PLEASE INDICATE KW RATING FOR EACH. |
| | |
| | 4)NOTE:PLEASE SEE PLANS MUST CONTAIN THE |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS/ DESIGN. |
| | FBC 104.2.1 |
| | |
| | 5)NOTE: PLEASE SEE PLANS ARE NOT |
| | PERMITTED TO BE SUBMITTED IN PENCIL. |
| | PLEASE MAKES COPIES OF BOTH AND |
| | RE-SUBMIT. |
| | |
| | 6)NOTE: PLEASE SEE REDLINED AREA FOR |
| | MISSING KITCHENOCUNTERSPACE RECEPTS/ |
| | PER 210.52C1-5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |