| 2005-09-02 00:00:00 | ********* UNSAT ********** |
| | |
| | |
| | PLEASE RE-PRINT PLANS FORTHE BELOW |
| | ITEMS. |
| | |
| | 1)NOTE: PLEASE INDICATE ALL ITEMS |
| | RDLINED ON PLANS AND PLEASE INCLUDE |
| | ADDITIONAL MISSING ITEMS. |
| | PLEASE SEE FBC 104.2.1, WHICH STATES, |
| | TECHNICAL CODE SHALL NOT BE STATED IN |
| | LEIU OF DETAILS ON PLANS. |
| | PLANS ARE REQUIRED TO SHOW CODE |
| | COMPLIANCE |
| | |
| | 2)NOTE PLEASE SEE 210.52C1-5 FOR KITCHEN |
| | COUNTERSPACES AND REQ'D GFI RECEPTS. |
| | PLEASE SEE 210.8A6 |
| | |
| | 3)NOTE: PLEASE INDICATE GFI RECEPTS AT |
| | ALLLOCATIONS PER 210.8 |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1 |
| | PLEASE SHOW ALL REQUIRED SD'S INSIDE AND |
| | OUTSIDE ALL BEDRMS AND ON EACH LEVEL OF |
| | A MULTI-LEVEL DWELLING. |
| | |
| | 5)NOTE:PLEASE BE SURE PANEL SCHEDULE |
| | INCLUDES ALL MIN CONDUCTOR SIZES AND |
| | CORRELATE WITH OVER-CURRENT PROTECTION |
| | SHOWN.310.16, 240.4, 215.5 |
| | |
| | 6)NOTE: PLEASE SEE BATH CIRCUIT IS SHOWN |
| | ON KITCHEN CIRCUIT, |
| | PLEASE SEE 210.52B1,210.11C3, BOTH ARE |
| | REQUIRED TO BE DEDICATED CIRCUITS. |
| | |
| | 7)NOTE:PLEASE INDICATE THE REQUIRED |
| | FRONT AND REAR GFI'S PER 210.52E, 210.8 |
| | |
| | 8)NOTE: PLEASE INDICATE THE REQUIRED GFI |
| | FOR A/C CU LOCATED OUTSIDE. 210.63 |
| | |
| | 9)NOTE: PLEASE SHOW LOATIONS OF AHU'S |
| | AND DISCONNECTS PER 440.11 |
| | |
| | 10)NOTE: PLEASE INDICATE DISCONNECT |
| | REQUIRED FOR WATER HEATER. A RECEPT IS |
| | SHOWN. PLEASE SEE 422.31 |
| | |
| | 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | RENOVATIONS TO EXSITNG DWELLINGS. PLEASE |
| | SEE PLANS APPEAR TO SHOW HOUSE BEING |
| | RE-WIRED AND EXCEDDING 50%. PLEASE SHOW |
| | ALL OTHER AREAS WHICH MEET 2002 NEC OR |
| | SHOW ELECTRICAL TO BE UPDATED. |
| | |
| | 12)NOTE: PLEASE CORRELATE ALL A/C |
| | SYSTEMS SHOWN. PLEASE SEE MORE THAN ONE |
| | SHOWN AS SYSTEM ONE ETC. |
| | |
| | 13)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR ALL SHOWN ON ELECTRICAL PANEL |
| | SCHEDULE SHOWN. |
| | 215.5,220.31B |
| | |
| | 14)NOTE:PLEASE RE-PRINT PLANS WITH ALL |
| | ITEMS SHOWN CLEAR AND DETAILED. |
| | FBC 104.2.1.1 |
| | MIN 1/8" SCALE REQUIRED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |