Plan Review Notes
Plan Review Notes For Permit 05070913
Permit Number 05070913
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-02 00:00:00********* UNSAT **********
  
  
 PLEASE RE-PRINT PLANS FORTHE BELOW
 ITEMS.
  
 1)NOTE: PLEASE INDICATE ALL ITEMS
 RDLINED ON PLANS AND PLEASE INCLUDE
 ADDITIONAL MISSING ITEMS.
 PLEASE SEE FBC 104.2.1, WHICH STATES,
 TECHNICAL CODE SHALL NOT BE STATED IN
 LEIU OF DETAILS ON PLANS.
 PLANS ARE REQUIRED TO SHOW CODE
 COMPLIANCE
  
 2)NOTE PLEASE SEE 210.52C1-5 FOR KITCHEN
 COUNTERSPACES AND REQ'D GFI RECEPTS.
 PLEASE SEE 210.8A6
  
 3)NOTE: PLEASE INDICATE GFI RECEPTS AT
 ALLLOCATIONS PER 210.8
  
 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1
 PLEASE SHOW ALL REQUIRED SD'S INSIDE AND
 OUTSIDE ALL BEDRMS AND ON EACH LEVEL OF
 A MULTI-LEVEL DWELLING.
  
 5)NOTE:PLEASE BE SURE PANEL SCHEDULE
 INCLUDES ALL MIN CONDUCTOR SIZES AND
 CORRELATE WITH OVER-CURRENT PROTECTION
 SHOWN.310.16, 240.4, 215.5
  
 6)NOTE: PLEASE SEE BATH CIRCUIT IS SHOWN
 ON KITCHEN CIRCUIT,
 PLEASE SEE 210.52B1,210.11C3, BOTH ARE
 REQUIRED TO BE DEDICATED CIRCUITS.
  
 7)NOTE:PLEASE INDICATE THE REQUIRED
 FRONT AND REAR GFI'S PER 210.52E, 210.8
  
 8)NOTE: PLEASE INDICATE THE REQUIRED GFI
 FOR A/C CU LOCATED OUTSIDE. 210.63
  
 9)NOTE: PLEASE SHOW LOATIONS OF AHU'S
 AND DISCONNECTS PER 440.11
  
 10)NOTE: PLEASE INDICATE DISCONNECT
 REQUIRED FOR WATER HEATER. A RECEPT IS
 SHOWN. PLEASE SEE 422.31
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 RENOVATIONS TO EXSITNG DWELLINGS. PLEASE
 SEE PLANS APPEAR TO SHOW HOUSE BEING
 RE-WIRED AND EXCEDDING 50%. PLEASE SHOW
 ALL OTHER AREAS WHICH MEET 2002 NEC OR
 SHOW ELECTRICAL TO BE UPDATED.
  
 12)NOTE: PLEASE CORRELATE ALL A/C
 SYSTEMS SHOWN. PLEASE SEE MORE THAN ONE
 SHOWN AS SYSTEM ONE ETC.
  
 13)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL SHOWN ON ELECTRICAL PANEL
 SCHEDULE SHOWN.
 215.5,220.31B
  
 14)NOTE:PLEASE RE-PRINT PLANS WITH ALL
 ITEMS SHOWN CLEAR AND DETAILED.
 FBC 104.2.1.1
 MIN 1/8" SCALE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]