2005-08-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE CLOUD OR OTHERWISE INDICATE
 THE REVISIONS TO THIS PLAN.
  
 2} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST PRINT NAME AND SIGN PER 104.2.1
 FBC.
  
 3} BEDROOMS MUST BE ARC FAULT PROTECTED
 PER 210.12.
  
 4} KITCHENS PER 210.8(A)(6), 210.52(C),
 BATHS PER 210.8(A)(1), 215.52(D),
 210.11(C)(3).
  
 5} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6 NFPA-72. ALSO SEE CHAPTER 34
 FOR OTHER GFI REQUIREMENTS.
  
 6} PLEASE SUBMIT A PANEL SCHEDULE SO
 THAT COMPLIANCE WITH BRANCH CIRCUIT
 REQUIREMENTS CAN BE DETERMINED.
  
 7} THERE IS A NOTE INDICATING NEW POOL
 WIRING. A SEPERATE APPLICATION AND
 DOCUMENTS ARE REQUIRED FOR THE POOL.
  
 8} PLEASE INCREASE THE VALUE OF THE JOB
 TO REFLECT ALL LABOR AND MATERIAL
 COST(104.6.5 FBC) RESULTING FROM THIS
 REVISION.INDICATE SAME TO PERMIT CLERK
 WHEN RESUBMITTING.
  