| Plan Review Notes For Permit 05070913 |
| Permit Number |
05070913 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE CLOUD OR OTHERWISE INDICATE | | | THE REVISIONS TO THIS PLAN. | | | | | | 2} THE PERSON RESPONSIBLE FOR THE PLAN | | | MUST PRINT NAME AND SIGN PER 104.2.1 | | | FBC. | | | | | | 3} BEDROOMS MUST BE ARC FAULT PROTECTED | | | PER 210.12. | | | | | | 4} KITCHENS PER 210.8(A)(6), 210.52(C), | | | BATHS PER 210.8(A)(1), 215.52(D), | | | 210.11(C)(3). | | | | | | 5} SMOKE DETECTORS ARE REQUIRED PER | | | 8-1.4.1.6 NFPA-72. ALSO SEE CHAPTER 34 | | | FOR OTHER GFI REQUIREMENTS. | | | | | | 6} PLEASE SUBMIT A PANEL SCHEDULE SO | | | THAT COMPLIANCE WITH BRANCH CIRCUIT | | | REQUIREMENTS CAN BE DETERMINED. | | | | | | 7} THERE IS A NOTE INDICATING NEW POOL | | | WIRING. A SEPERATE APPLICATION AND | | | DOCUMENTS ARE REQUIRED FOR THE POOL. | | | | | | 8} PLEASE INCREASE THE VALUE OF THE JOB | | | TO REFLECT ALL LABOR AND MATERIAL | | | COST(104.6.5 FBC) RESULTING FROM THIS | | | REVISION.INDICATE SAME TO PERMIT CLERK | | | WHEN RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|