| Plan Review Notes For Permit 05070910 |
| Permit Number |
05070910 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-25 00:00:00 | ********* PROVISO/ REVISION ******** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | NEW/ REVISED CIRCUITING AND CORRELATE | | | WITH A PANEL SCHEDULE TO BE SUBMITTED. | | | INCLUDE ANY NEW LOADS. | | | 215.5,220 | | | | | | 2)NOTE: PLEASE SEE 210.8B3 IN THE 2002 | | | NEC, WHICH REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NONDWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. | | | | | | 3)NOTE: PLEASE SEE ANY CIRCUITING FOR | | | EM/EXT LTS PER 700.12E. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|