2005-07-25 00:00:00********* PROVISO/ REVISION ********
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL
 NEW/ REVISED CIRCUITING AND CORRELATE
 WITH A PANEL SCHEDULE TO BE SUBMITTED.
 INCLUDE ANY NEW LOADS.
 215.5,220
  
 2)NOTE: PLEASE SEE 210.8B3 IN THE 2002
 NEC, WHICH REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 3)NOTE: PLEASE SEE ANY CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
  
 PLEASE REVISE AND SUBMIT THE ABOVE FOR
 REVIEW.