Plan Review Notes
Plan Review Notes For Permit 05070866
Permit Number 05070866
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESPONSIBLE FOR THE
 DRAWING MUST PRINT AND SIGN NAME TO
 SAME, 104.2.1 FBC.
  
 2} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THESERVICE
 EQUIPMENT AND THE EMERGENCY EQUIPMENT SO
 THAT COMPLIANCE WITH 225.31 THROUGH
 225.37 CAN BE DETERMINED.
  
 3} PLEASE SUBMIT TWO COPIES OF ALL
 DOCUMENTS PER 104.2.1 FBC, MANUFACTURERS
 SPECS FOR THE TRANSFER SWITCH AND
 GENERATOR.
  
 4} INDICATE THE PRIME MOVER (FUEL
 SOURCE) FOR THE GENERATOR.
  
 5) THE VALUE OF THE PROJECT INDICATED ON
 THE APPLICATION MUST INCLUDE THE VALUE
 OF ALL THE EQUIPMENT BEING INSTALLED AND
 LABOR PER 104.6.5.
  
 6} PANEL A-1 IS FED THROUGH AND FED BACK
 FROM THE TRANSFER SWITCH? IT IS ALSO AN
 MLO. PLEASE VERIFY.
  
 7} PANEL "A" INDICATES IT IS BOTH A MLO
 AND HAS A 125 AMP MAIN. PLEASE
 CORRELATE. INDICATE WHICH EQUIPMENT IS
 NEW AND WHICH IS EXISTING.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  