| 2005-08-03 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PUT THE GEC SYSTEM ON THE | | | RISER PER 250.53. | | | | | | 2} INDICATE THE EQUIPMENT GROUND TO THE | | | GENERATOR PER 250.122. | | | | | | 3} PLEASE NOTE THAT A DISCONNECT IS | | | REQUIRED ON THE BUILDING PER 225.31, | | | GROUPED PER 230.71. THE ATS MUST BE | | | SERVICE RATED PER 225.36 TO COMPLY WITH | | | THIS REQUIREMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|