| 2005-07-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070843 |
| | ADD: 829 MADDOCK ST |
| | CONT: O/B JONES, THOMAS |
| | TEL: (561)909-8355 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: ADDITIONAL ELECTRICAL PERMIT WILL |
| | BE REQUIRED. |
| | |
| | 1) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WOOD/ WOOD STRAPS |
| | B) STORM SHUUTERSWINDOWS & DOORS |
| | C) HARDI PLANK SIDING |
| | |
| | 3) PLANS DO NOT INDICATE HOW INFILL WALL |
| | SECTIONS WILL BE SECURED TO EXISTING |
| | CONCRETE SLAB, COLUMNS & BEAM. |
| | 1606.1.3 ANCHORAGE AGAINST OVERTURNING, |
| | UPLIFT AND SLIDING. STRUCTURAL |
| | MEMBERS AND SYSTEMS, AND COMPONENTS |
| | AND CLADDING IN A BUILDING OR |
| | STRUCTURE SHALL BE ANCHORED TO RESIST |
| | WIND-INDUCED OVERTURNING, UPLIFT |
| | AND SLIDING AND TO PROVIDE CONTINUOUS |
| | LOAD PATHS FOR THESE FORCES TO THE |
| | FOUNDATION.WHERE A PORTION OF THE |
| | RESISTANCE TO THESE FORCES IS PROVIDED |
| | BY DEAD LOAD, THE MINIMUM DEAD LOAD |
| | LIKELY TO BE IN PLACE DURING A DESIGN |
| | WIND EVENT SHALL BE USED. |
| | |
| | 4) PLANS DO NOT INDICATE USAGE OF ROOM? |
| | PLANS ALSO INDICATE THAT THIS ROOM DOES |
| | NOT COMMUNICATE WITH THE REMAINDER OF |
| | THE HOUSE? |
| | |
| | 4) PLANS INDICATE TO REPLACE OLD SIDING |
| | AND REPLACE WITH 3/8" AND HARDI PLANK, |
| | WHERE, ON THE REMAINDER OF THE HOUSE? |
| | |
| | 5) PROVIDE A CUT SECTION, ELEVATION |
| | INDICATING COMPLINCE THESE CODE |
| | SECTIONS: |
| | 2303.3 MOISTURE PROTECTION. SURFACES |
| | EXPOSED TO THE WEATHER SHALL HAVE |
| | AN APPROVED BARRIER TO PROTECT THE |
| | STRUCTURAL FRAME AND THE INTERIOR WALL |
| | COVERING.THE BARRIER SHALL BE AT LEAST |
| | TYPE 15 FELT OR KRAFT WATERPROOF |
| | BUILDING PAPER.BUILDING PAPER AND FELT |
| | SHALL BE FREE FROM HOLES AND |
| | BREAKS OTHER THAN THOSE CREATED BY |
| | FASTENERS AND CONSTRUCTION SYSTEMS USED |
| | IN ATTACHING OF THE BARRIER, AND SHALL |
| | BE APPLIED OVER STUDS OR SHEATHING |
| | OF ALL EXTERIOR WALLS.SUCH FELT OR |
| | PAPER SHALL BE APPLIED HORIZONTALLY |
| | WITH THE UPPER LAYER LAPPED OVER THE |
| | LOWER LAYER NOT LESS THAN 2 INCHES (51 |
| | MM).WHERE VERTICAL JOINTS OCCUR, FELT |
| | OR PAPER SHALL BE LAPPED NOT LESS |
| | THAN 6 INCHES (152 MM). |
| | |
| | 2304.2.5 CLEARANCE BETWEEN WOOD SIDING |
| | AND EARTH ON THE EXTERIOR OF A |
| | BUILDING SHALL BE NOT LESS THAN 6 |
| | INCHES (152 MM) EXCEPT WHERE SIDING, |
| | SHEATHING AND WALL FRAMING ARE OF |
| | APPROVED PRESERVATIVE-TREATED WOOD OR |
| | APPROVED NATURALLY DURABLE WOOD. |
| | |
| | 6) FBC 104.2.1ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN.PLEASE COMPLY. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |