| Date |
Text |
| 2005-08-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR REQUIRED GAS PERMIT: |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | 7. INDICATE THE BTU LOAD OF EXISTING |
| | GENERATOR. IF NEW GENERTATOR IS A |
| | SUBSTANTIAL ADDITION TO SYSTEM, TOTAL |
| | BTU OF SYSTEM MAY BE REQUIRED TO CHECK |
| | PIPE SIZING OUT OF THE METER. (BTU LOAD |
| | OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO THE FBC-2001 |
| | FUEL GAS CODE SECS. 401.8 THRU 402.5.2 |
| | AND TABLES 402(1) THRU 402(34)). |
| | 8. PLANS INDICATE THAT THE UNDERGROUND |
| | PIPING SHALL HAVE A MINIMUM OF 12" |
| | COVER. SECTION 404.9 REQUIRES MINIMUM |
| | 18" COVER, BUT MAY BE REDUCED TO 12" |
| | WHERE EXTERNAL DAMAGE IS NOT LIKELY TO |
| | RESULT. PLEASE INDICATE HOW THIS |
| | EXCEPTION WILL BE APPROVED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |