| Date |
Text |
| 2005-08-03 00:00:00 | ****** UNSAT ******* |
| | |
| | 1)NOTE: PLEASE SEE FIRE PUMP INFORMATION |
| | IS CURRENTLY BEING REVIEWED UNDER |
| | GENERATOR PERMIT, HOWEVER FIRE PUMP WILL |
| | BE REQUIRED TO BE PERMITTED SEPARATELY. |
| | PLEASE SEE THIS MAY BE SUBMITTED ALONG |
| | WITH GENERATOR PERMIT SO IT MAY BE |
| | REVIEWED AND PERMITTED AT THE SAME TIME. |
| | PLANS, SPECS WILL BE REQUIRED FOR EACH |
| | AS EACH WILL BE FILED UNDER SEPRATE |
| | FILES. |
| | |
| | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR GENERATOR, ATS, |
| | FIRE PUMP, FIRE PUMP CONTROLLER. |
| | PLEASE SEE OTHER COMMENTS FOR FPC, AS |
| | SOME INFORMATION CAN NOT VERIFIED AT |
| | THIS TIME. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE CONDUCTORS FROM FPL, |
| | GENERATOR TO FIRE PUMP, FIRE PUMP CONT, |
| | SHALL BE BASED ON 125%. |
| | PLEASE SEE 695.6(C)(2) ETC. |
| | PLEASE SEE PLANS INDICATE EXSITING |
| | "NAMEPLATE @ 100HP, 250 FLA'S. THIS IS |
| | ONLY A NOTE FOR VERIFICATION. NO |
| | CORRECTION NEEDED. |
| | |
| | 4)NOTE: PLEASE SEE SPECS/CUT SHEETS FOR |
| | FPC WERE SUBMITTED, HOWEVER PLEASE NOTE |
| | THE MANUAL MEANS OF DISCONNECT LOCATED |
| | ON OUTSIDE OF EQUIPMENT, RATED FOR THE |
| | LAOD SERVED SHALL BE PART OF THE FPC. |
| | PLEASE SEE 230.76,230.79,NFPA-20 CHAPTER |
| | 7-4. |
| | 5)NOTE:PLEASESEE THE LOCATION OF FIRE |
| | PUMP CONTROLLER SHALL BE ARRANGED TO |
| | PREVENT ANY DAMAGE TO FPC EQUIPMENT IN |
| | THE EVENT OF FIRE/EXPLOSION ETC. |
| | PLEASE KNOW,IT IS KNOWN THIS IS AN |
| | EXSITING ROOM AND THERE ARE SOME |
| | EXISTING CONDITIONS WHICH CAN NOT BE |
| | AVOIDED. HOWEVER,A STEEL REINFORCED |
| | CONCRETE WALL WILL BE REQUIRED TO HELP |
| | IN SHIELDING ANY SUCH FIRE /EXPLOSION |
| | FROM MAIN SERVICE EQUIPMENT. |
| | PLEASE SEE 695.3, NFPA-20 6-2.1.ETC |
| | |
| | 6)NOTE: PLEASE SEE THE LOCATION OF FIRE |
| | PUMP CONTROLLER SHALL BE SUCH THE |
| | LEAKING OF ANY WATERFROM FIRE PUMP , |
| | FIRE SPRINKLERS ETC WILL NOT AFFECT THE |
| | FPC, PLEASE SEE NFPA-20 7-2,7-3.3.1, FOR |
| | ENCLOSURE TYPE ETC. |
| | PLEASE SEE NOTE ON PLANS MENTIONS FOR |
| | FEEDERS FROM GEN TO ENTER BLDG AS LOW AS |
| | POSSIBLE INTO REAR OF FIRE PUMP |
| | CONTROLLER, HOWEVER PLEASE SEE |
| | 7-2.2,695.12, WHICH REQUIRES FPC TO BE |
| | MOUNTED A MIN OF 12" ABOVE FLR. |
| | |
| | 7)NOTE: PLEASE PROVIDE NOTE FOR SIGNAGE |
| | FOR ALL ELECTRICAL EQUIPMENT. |
| | 695.4B3,4 ETC. |
| | |
| | 8)NOTE: PLEASE SEE PROTECTIVE BOLLARDS |
| | WILL BE REQUIRED OUTSIDE TO PROTECT GEN |
| | ENCLOSURE FROM PARKING LOT AREA. |
| | PLEASE SEE ANY ZONING COMMENTS. |
| | |
| | 9)NOTE: PLEASE SEE PLANS MENTIONS PIPING |
| | IN ROOM SHALL BE EMT, PLEASE SEE |
| | 695.6(2)(E). |
| | |
| | 10)NOTE: PLEASE SEE 701.11(B)(2)(3) FOR |
| | SOURCES OF FUEL. |
| | PLEASE SEE IT IS KNOWNTO OUR OFFICE |
| | THE LOCAL UTILITY COMAPNY SUPPLYING |
| | NATURAL GAS SEEMS TO BE AT OVER 500% |
| | CAPACITY. PLEASE SEE AN ALTERANTE FUEL |
| | SOURCE WILL BE REQUIRED FOR MIN REQUIRED |
| | RUN TIME. |
| | |
| | 11)NOTE: PLEASE SEE SITE PLAN / SURVEY |
| | WILL BE REQUIRED TO INDICATE THE BASE |
| | FLOOD ELEVATION (BFE). GEN SLAB SHALL BE |
| | A MIN OF 6" ABOVE BFE. PLEASE SEE BLDG |
| | REVIEW COMMENTS. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | BOLT/TIE DOWN CONNECTIONS REQUIRED. |
| | |
| | 12)NOTE: PLEASE SEE FBC LOCAL |
| | ADMINISTRATIVE SECTION 104.6.5, PERMIT |
| | VALUATION IS BASED ON ALL LABOR AND |
| | MATERIALS, EVEN IF EQUIPMENT IS OWNER |
| | SUPPLIED. PLEASE ADJUST. |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |