| Permit Number |
05070825 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-03 00:00:00 | ---------------DENIED------------------- | | | | | | 1) PLANS MUST BE SIGNED/SEALED BY DESIGN | | | PROFESSIONAL PER FBC 104.2.1 | | | | | | 2) WINDOW IS BEING FILLED IN AT EXISTING | | | BATHROOM ADJACENT TO NEW MASTER BEDROOM. | | | NATURAL VENTILLATION IS LOST.MIN. 50 | | | CFM EXHAUST FAN REQUIRED PER FBC,M 403.3 | | | | | | 3) EQUIPMENT ROOM: WHAT TYPE OF | | | EQUIPMENT WILL BE LOCATED IN THIS ROOM | | | OTHER THAN AHU?PLANS INDICATE A | | | POSSIBLE GAS APPLIANCE VENTED TO | | | OUTDOORS.IS RETURN DUCTED BACK TO AHU | | | OR WILL THIS ROOM BE USED AS A PLENUM? | | | SUPPLY DUCT SIZE IS MISSING FROM AHU TO | | | DIST. BOX. | | | | | | 4)GAME ROOM: PLAN INDICATES EXISTING | | | EQUIPMENT TO BE UPGRADED.PROVIDE | | | INFORMATION ON EXISTING/NEW EQUIPMENT TO | | | BE INSTALLED. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|