| Plan Review Notes For Permit 05070825 |
| Permit Number |
05070825 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-02 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE THE AIC RATING FOR THE | | | SERVICE EQUIPMENT PER 110.9&10. | | | | | | 2} THE GENERATOR PERMIT MUST BE APPLIED | | | FOR SEPARATELY. | | | | | | 3} INDICATE THE SIZE AND TYPE OF ALL | | | CONDUITS AND CONDUCTORS ON THE RISER | | | DIAGRAM. | | | | | | 4} INDICATE THE GROUNDING ELECTRODE | | | SYSTEM CONDUCTOR SIZE PER 250.66 AND | | | COMPONENETS PER 250-ALL AVAILABLE. | | | | | | 5} PLEASE SEE THAT "A"PHASE CIRCUITS 13 | | | THROUGH 31 HAVE 20 AMP BREAKERS ON #14 | | | WIRE.CIRCUIT 13 THROUGH 27 ARE REQUIRED | | | TO BE 20 AMP.PLEASE CLARIFY. | | | | | | 6} PANEL "C" GUEST BATHS MUST COMPLY | | | WITH 210.11(C)(3). | | | | | | 7} SUBMIT BASE FLOOD ELEVATION | | | CERTIFICATE AND INDICATE COMPLIANCE FOR | | | THE HEIGHT REQUIREMENTS OF ALL | | | ELECTRICAL EQUIPMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|