2005-08-02 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE THE AIC RATING FOR THE
 SERVICE EQUIPMENT PER 110.9&10.
  
 2} THE GENERATOR PERMIT MUST BE APPLIED
 FOR SEPARATELY.
  
 3} INDICATE THE SIZE AND TYPE OF ALL
 CONDUITS AND CONDUCTORS ON THE RISER
 DIAGRAM.
  
 4} INDICATE THE GROUNDING ELECTRODE
 SYSTEM CONDUCTOR SIZE PER 250.66 AND
 COMPONENETS PER 250-ALL AVAILABLE.
  
 5} PLEASE SEE THAT "A"PHASE CIRCUITS 13
 THROUGH 31 HAVE 20 AMP BREAKERS ON #14
 WIRE.CIRCUIT 13 THROUGH 27 ARE REQUIRED
 TO BE 20 AMP.PLEASE CLARIFY.
  
 6} PANEL "C" GUEST BATHS MUST COMPLY
 WITH 210.11(C)(3).
  
 7} SUBMIT BASE FLOOD ELEVATION
 CERTIFICATE AND INDICATE COMPLIANCE FOR
 THE HEIGHT REQUIREMENTS OF ALL
 ELECTRICAL EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  