| 2006-01-27 00:00:00 | IN ELEC FOR REVIEW |
| | ********** UNSAT 3RD REVIEW ************ |
| | |
| | ** PLEASE SEE NOTES FROM TWO PREVIOUS |
| | REVIEWS WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | PLEASE ALSO SEE NEW COMMENTS DUE TO |
| | CHANGES IN PLANS. |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER, PLANS, |
| | PANEL SCHEDULE(S). |
| | PLEASE SEE PLANS NOW INDICATE A |
| | COMPLETELY NEW AND DIFFERENT RISER FROM |
| | FIRST TWO REVIEWS. |
| | PLEASE SEE RISER NOW SHOWS A NEW 225A |
| | MCB, HOWEVER NEW SERVICE ENTRANCE |
| | CONDUCTORS ARE NOT RATED FOR THE 225A |
| | MAIN. PLEASE SEE 310.16 FOR SIZING. |
| | 240.4,215.5 |
| | PLEASE CORRELATE AS PANEL SCHEDULE SHOWS |
| | 175A MCB AND PLANS INDICATE 200A?? |
| | PLEASE ALSO SEE PLANS NOW INDICATE A |
| | J-BOX LOCATED INSIDE ELECTRICAL CLOSET |
| | WHICH IS OK, HOWEVER PLEASE SEE RISER |
| | SHOWS THIS AS A 225A J-BOX? PLEASE |
| | VERIFY WHAT A 225A J-BOX IS? |
| | 215.5 |
| | ** NOTE #4, PREVIOUS REVIEW, NOTE #9 |
| | FROM FIRST REVIEW. |
| | |
| | 2)NOTE: PLEASE SEE MECHANICAL NOTES AS |
| | THEY MENTION TO ADDRESS PREVIOUS |
| | COMMENTS. PLEASE SEE MECHANICAL PLANS |
| | STILL DO NOT INDICATE THE HEAT KW |
| | RATING.PLEASE VERIFY THE KW RATING FOR |
| | HEAT STRIPS IN UNITS, SHOW ON MECHANICAL |
| | PLANS AS REQUESTED BY MECHANICAL |
| | REVIEWER AND IF THERE ARE ANY CHANGES |
| | PLEASE ADJUST ELECTRICAL PLANS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE NFPA-101 |
| | 7.8.1.3,7.9.2.2 FOR MIN LIGHTING LEVELS |
| | TO BE PROVIDED IN EGRESS STAIR AREAS. |
| | PLEASE SEE THE ONE FIXTURE INDICATED |
| | DOES NOT APPEAR ENOUGH TO PROVIDE 108 |
| | LUX(10FT CANDLES). |
| | NOTE #5 PREVIOUS REVIEW. |
| | |
| | 4)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| | PROFESSIONAL. |
| | PLEASE SEE PLANS WITH REPEAT COMMENTS |
| | THREE OR MORE TIMES FOR THE SAME CODE |
| | COMPLIANCE COMMENT SHALL BE ACCESSED AS |
| | 4X FEE FOR THE PLAN REVIEW PORTION OF |
| | THE PERMIT FEE. THIS FEE IS ACCESSED TO |
| | THE DESIGN PROFESSIONL. |
| | PLEASE SEE THE FEE ACCESSED IN THE |
| | AMOUNT OF $1836.00 IS DUE BEFORE PLANS |
| | MAY BE RETURNED FOR RESUB AND REVIEW. |
| | THE IS REQUIRED UNDER STATE STATUE AS |
| | MENTIONED ABOVE. |
| | PLEASE SEE FS 481.221 (5)&(6). THIS TEXT |
| | IS TAKEN DIRECTLY FROM THE FLORIDA |
| | STATUES. |
| | |
| | (6)NO REGISTERED ARCHITECT SHALL AFFIX |
| | HER OR HIS SIGNATURE OR SEAL TO ANY |
| | FINAL CONSTRUCTION DOCUMENT OR |
| | INSTRUMENT OF SERVICE WHICH INCLUDES |
| | DRAWINGS, PLANS, SPECIFICATIONS, OR |
| | ARCHITECTURAL DOCUMENTS WHICH WERE NOT |
| | PREPARED BY HER OR HIM OR UNDER HER OR |
| | HIS RESPONSIBLE SUPERVISING CONTROL OR |
| | BY ANOTHER REGISTERED ARCHITECT AND |
| | REVIEWED, APPROVED, OR MODIFIED AND |
| | ADOPTED BY HER OR HIM AS HER OR HIS OWN |
| | WORK ACCORDING TO RULES ADOPTED BY THE |
| | BOARD |
| | |
| | 5)NOTE: PLEASE SEE NOTICE OF COMMENCEMNT |
| | SUBMITTED ANDRECORDED ON 7/14/05 HAS |
| | SINCE EXPIRED. PLEASE SEE FLORIDA |
| | STATUES 713.13(2). WORK WHICH HAS NOT |
| | COMMENCED WITHIN 90 DAYS OF RECORDING |
| | SAID NOC, THAT NOC SHALL BECOME VOID. |
| | |
| | PLEASE KNOW, ONE COPY OF ALL THREE SETS |
| | OF ELECTRICAL PLANS ARE NOW BEING |
| | RETAINED AND MAY BE SENT TO THE STATE OF |
| | FLORIDA BOARD OF ARCHITECTS. |
| | |
| | IF THERE ARE ANY QUESTIONS, IT IS |
| | STRONGLY SUGGESTED A MEETING BE HELD |
| | WITH THE DESIGN PROFESSIONAL TO GO OVER |
| | ANY COMMENTS IN QUESTION. |
| | |
| | |
| | 5)NOTE: PLEASE REVMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE SEE THIS WAS NOT DONE |
| | WHEN PLANS WERE SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |