| Plan Review Notes For Permit 05070760 |
| Permit Number |
05070760 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-30 00:00:00 | *** DENIED *** | | | 1) RETURN AIR TRANSFER DUCTS ON 1ST. | | | FLOOR ARE SOT SIZED. PLEASE NOTE RETURN | | | TRANSFER DUCTS MUST BE 1 1/2 TIMES | | | LARGER THAN THE SUPPLY AIR DUCT (6" | | | SUPPLU DUCT REQUIRES 8" RETURN TRANSFER | | | DUCT, 8" SUPPLY DUCT REQUIRES 10" RETURN | | | TRANSFER DUCT). PER 2001 FBC/M601.4 . | | | 2) RETURN AIR TRANSFER DUCTS ON 2ND. | | | FLOOR ARE TO SMALL (10" SUPPLY AIR DUCT | | | REQUIRES A 13" RETURN AIR TRANSFER | | | DUCT). | | | 3) THE SUPPLY AIR DUCT TO THE 2ND. FLOOR | | | OFFICE IS NOT SIZED. | | | 4) THE SUPPLY AIR DUCT TO THE 1ST. FLOOR | | | BATHROOM IS NOT SIZED. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|