Plan Review Notes
Plan Review Notes For Permit 05070760
Permit Number 05070760
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-29 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE AT THIS TIME.
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS TO LOCAL BRANCH
 CIRCUIT FEEDING LTS.
  
 3)NOTE: PLEASE INCLUDE MISSING SIGN
 CIRCUIT AS REQUIRED PER 600.5
  
 4)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PLANS AND PANELS.
 PLEASE SEE PLANS INDICATE AN ADDITONAL
 SUB PANEL, HOWEVER RISER DOES NOT
 INDICATE THIS.
 PLEASE SEE PANEL IS BEING SHOWN AS BEING
 DOWN GRADED TO A 150A PANEL.
 215.5
  
 5)NOTE: PLEASE INDICATE THE MIN REQUIRED
 EMERGENCY EGRESS LT FIXTURE(S). PLEASE
 SEE FIRE REVIEW NOTES MENTIONS TO SHOW,
 HOWEVER THIS IS REQUIRED AT THIS TIME.
 PLEASE SEE NFPA-101 7.8,7.9 2003
 PLEASE ALSO SEE MIN EGRESS LIGHTING FOR
 STAIRWAYS IS REQUIRED TO HAVE A MIN OF
 10 FT CANDLES DURING NORMAL POWER AND
 1FT CANDLE UNDER EM POWER.
 PLEASE ALSO SEE ABOVE LS101 WHICH
 REQUIRES THE EM ILLUMINATION TO THE
 PUBLIC RIGHJT OF WAY.
  
 6)NOTE: PLEASE SEE MIN KVA PER KNOWN
 RECEPTS AT 180VA IS SHOWN , HOWEVER LOAD
 EXCEEDS THAT OF THETWO BRANCH CIRCUITS
 SHOWN ON PANEL SCHEDULE FOR ENTIRE COMM
 OFFICES.
 PLEASE ALSO INDICATE ANY DEDICATE LOADS
 FOR ANY, FRIG, COPIER, ETC.
  
 7)NOTE: PLEASE SEE 110.26, 240.24, 408.7
 WHICH REQUIRES ELECTRICAL PANELS ONLY TO
 BE LOCATED IN DEDICATED ELECTRICAL RMS.
 PLEASE LABEL PLANS ACCORD.
  
 8)NOTE: PLEASE SEE PLANS MENTIONS
 UPSTAIRS EXISTING TO REMAIN, YET PLEASE
 KNOW, THAT DUE TO THE CHANGE IN
 OCCUPANCYALL ELECTRICAL IS REQUIRED TO
 BE BROUGHT UP TO CODE.
  
 9)NOTE: PLEASE BE SURE PANEL SCHEDULE
 INDICATES ALL AWG SIZES FOR CORRELATION
 WITH OCP AND LOADS ON CIRCUITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-11-22 00:00:00PLANS TO BE UNSAT, NOTES TO FOLLOW.
2005-11-10 00:00:00PLANS SENT BACK TO INCOMING PER RB,
 AWAITING COMM BOARD.DV PALMER