| Plan Review Notes For Permit 05070760 |
| Permit Number |
05070760 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-16 00:00:00 | DENIED; | | | 1.PLANS ARE NOT SIGNED OR SEALED AND | | | HAND WRITEN DIAMENTIONS ARE NOT | | | PERMITED. | | | 2.BATHROOM 111, DOOR SWINGS INTO THE | | | CLEAT FLOOR SPACE OF THE HANDICAP | | | LAVATORY. FBC-2001 CHAPTER 11 | | | SEC.11-4.22.2. | | | 3.SHOW A DETAIL OF BREAK SINK. MUST | | | COMPLY WITH FBC CH. 11 SEC. 11-4.24/1 | | | THRU 11-4.24.7. | | | 4.SHOW COMPIANCE WITH FBC PLUMBING TABLE | | | 403.1. DRIMKING FOUNTAIN,AUTOMATIC | | | CLOTHES WASHER ARE REQUIRED. PLEASE SHOW | | | SQUIRE FOOTAGE AND NUMBER OF EMPLOYEES | | | TO MEET MINIMUM REQUIREMENTS. DRINKING | | | FOUNTAIN SHALL COMPLY WITH HANDICAP CODE | | | SEC. 11-4.1.3(10). MUST BE ACCESSIBLE | | | FOR PEOPLE IN WHEELCHAIRS AND PEOPLE WHO | | | HAVE TROUBLE BENDING AND STOOPING. | | | 5.BACKFLOW PROTECTION REQUIRED ON WATER | | | SERVICE PER UTILITY ORD. #2853-95. | | | 6. SANITARY AND WATER RISER DIAGRAMS ARE | | | REQUIRED SHOWING THE CHANGES TO BE MADE | | | TO THE PLUMBING SYSTEM. | | | 7.WHERE IS WATER HEATER LOCATED? | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|