Plan Review Notes
Plan Review Notes For Permit 05070760
Permit Number 05070760
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL REVIEW NOTE IN
 REGARDS TO LIGHTING IN MEANS OF EGRESS.
  
 2) PLEASE ALSO SEE OTHER REVIEW COMMENT
 REF: FS REQUIREMENT FOR PLANS.
  
 3) PLEASE INDICATE OCCUPANCY
 CLASSIFICATION FOR BUILDING AND EXISTING
 USE.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 5) SMOKE DETECTORS SHALL BE INSTALLED A
 MINIMUM DISTANCE OF 3' FROM HVAC
 DIFFUSERS.
  
 6) PLEASE SHOW ADDRESS ON BUILDING THAT
 MUST BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 7) PLEASE PROVIDE MORE INFORMATION
 REGARDING STAIRS AND RAMPS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722