| 2005-07-28 00:00:00 | *********** UNSAT ************ |
| | |
| | SF HOUSE TO "LIVE/WORK" OCCUPANCY. |
| | |
| | |
| | 1)NOTE: PLEASE SEE THIS APPEARS TO BEA |
| | CHANGE IN OCCUPANCY AND SHALL BE |
| | REQUIRED FOR ELECTRICAL TO BE BROUGHT UP |
| | TO CODE FOR ELECTRICAL. NEC, LS101, |
| | NFPA-72 ETC. PLEASE ALSO SEE COMMENTS |
| | FROM OTHER TRADES. |
| | FBC 104.1.1 |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AT THIS TIME AND CORRELATE WITH |
| | PANEL SCHEDULES TO BE SUBMITTED. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. THE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 3)NOTE: PLEASE SEE REQUIREMENTS FOR |
| | LIVE/WORK, A KITCHEN WITH A MIN OF TWO |
| | SMALL APPLIANCE CIRCUITS SHALL BE |
| | PROVIDED. PLEASE ALSO SEE 210.8A6 |
| | 220.16, 210.11C1 |
| | |
| | 4)NOTE: PLEASE SHOW AL MIN CIRCUITS FOR |
| | DWELLING UNIT ALSO. PLEASE SEE MISSING |
| | LAUNDRY CIRCUIT, 220.16,210.112 |
| | |
| | 5)NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT(S) PER |
| | 210.52D,210.11C3 |
| | MUST BE 20A, #12. |
| | |
| | 6)NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING PER 210.70,LS 101 5-8 IN SOME |
| | AREAS. |
| | |
| | 7)NOTE: PLEASE SEE ALL RECEPT SPACING |
| | SHALL BE BROUGHT UP TO CODE. 210.52 |
| | |
| | 8)NOTE: PLEASE SEE ELECTRICAL PANEL MAY |
| | NOT BE IN A CLOSET/STORAGE CLOSET. |
| | 408.7, 110.26 ETC. |
| | |
| | 9)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PLANS. PLEASE INCLUDE ALL ELECTRICAL |
| | PANELS ETC ON PLANS AND RISER. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR ALL NEW AND EXISTING. PLEASE |
| | INDICATE MIXED USE, PLEASE ALSO ADJUST |
| | ANY LOAD CALCULATIONS ACCORDINGLY. |
| | 220,215.5, |
| | |
| | 11)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| | INSTALLED PER 8-1.4.2 |
| | |
| | 12)NOTE: PLEASE INDICATE ALL ELECTRICAL |
| | ON PLANS. IF EXISTING PLEASE SHOW AS "E" |
| | ETC. PLEASE SHOW ALL A/C EQUIPMENT, EVEN |
| | IF EXSITNG AND SHOW ALL DISCONNECTING |
| | MEANS EVEN IF EXSITING.440.11 |
| | PLEASE SHOW ANY LTS/RECEPTS (GFI) |
| | REQUIRED FOR A/C UNTIS. 210.70,210.63 IF |
| | EXISTING,PLEASE SHOW. |
| | |
| | 13)NOTE: PLEASE SEE NEW SIGN CIRCUIT |
| | REQUIRED PER 600.5 |
| | THIS REQUIREMENT IS NOT CONTINGENT ON |
| | WHETHER AN ELECTRIC SIGN WILL BE |
| | INSTALLED AT THE TIME AN OCCUPANT MOVES |
| | INTO ASPACE. |
| | |
| | 14)NOTE: PLEASE SHOW ALL RECEPTS WHICH |
| | ARE REQUIRED TO BE GFI/GFI PROTECTED. |
| | 210.8 |
| | |
| | 15)NOTE: PLEASE SEE BOTH SETS OF PLANS |
| | SUBMITTED ARE NOT SIGNED, DATED OR |
| | SEALED BY THE ARCHITECT OF RECORD. |
| | PLEASE SEE FS 481.221 |
| | THIS IS REQUIRED OF ALL TRADES AND ALL |
| | REVIEW WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER REVIEWER(S). |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS , |
| | PLEASE DO NOT HESIATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |