Plan Review Notes
Plan Review Notes For Permit 05070760
Permit Number 05070760
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00*********** UNSAT ************
  
 SF HOUSE TO "LIVE/WORK" OCCUPANCY.
  
  
 1)NOTE: PLEASE SEE THIS APPEARS TO BEA
 CHANGE IN OCCUPANCY AND SHALL BE
 REQUIRED FOR ELECTRICAL TO BE BROUGHT UP
 TO CODE FOR ELECTRICAL. NEC, LS101,
 NFPA-72 ETC. PLEASE ALSO SEE COMMENTS
 FROM OTHER TRADES.
 FBC 104.1.1
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AT THIS TIME AND CORRELATE WITH
 PANEL SCHEDULES TO BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 3)NOTE: PLEASE SEE REQUIREMENTS FOR
 LIVE/WORK, A KITCHEN WITH A MIN OF TWO
 SMALL APPLIANCE CIRCUITS SHALL BE
 PROVIDED. PLEASE ALSO SEE 210.8A6
 220.16, 210.11C1
  
 4)NOTE: PLEASE SHOW AL MIN CIRCUITS FOR
 DWELLING UNIT ALSO. PLEASE SEE MISSING
 LAUNDRY CIRCUIT, 220.16,210.112
  
 5)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT(S) PER
 210.52D,210.11C3
 MUST BE 20A, #12.
  
 6)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING PER 210.70,LS 101 5-8 IN SOME
 AREAS.
  
 7)NOTE: PLEASE SEE ALL RECEPT SPACING
 SHALL BE BROUGHT UP TO CODE. 210.52
  
 8)NOTE: PLEASE SEE ELECTRICAL PANEL MAY
 NOT BE IN A CLOSET/STORAGE CLOSET.
 408.7, 110.26 ETC.
  
 9)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PLANS. PLEASE INCLUDE ALL ELECTRICAL
 PANELS ETC ON PLANS AND RISER.
 215.5
  
 10)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL NEW AND EXISTING. PLEASE
 INDICATE MIXED USE, PLEASE ALSO ADJUST
 ANY LOAD CALCULATIONS ACCORDINGLY.
 220,215.5,
  
 11)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 INSTALLED PER 8-1.4.2
  
 12)NOTE: PLEASE INDICATE ALL ELECTRICAL
 ON PLANS. IF EXISTING PLEASE SHOW AS "E"
 ETC. PLEASE SHOW ALL A/C EQUIPMENT, EVEN
 IF EXSITNG AND SHOW ALL DISCONNECTING
 MEANS EVEN IF EXSITING.440.11
 PLEASE SHOW ANY LTS/RECEPTS (GFI)
 REQUIRED FOR A/C UNTIS. 210.70,210.63 IF
 EXISTING,PLEASE SHOW.
  
 13)NOTE: PLEASE SEE NEW SIGN CIRCUIT
 REQUIRED PER 600.5
 THIS REQUIREMENT IS NOT CONTINGENT ON
 WHETHER AN ELECTRIC SIGN WILL BE
 INSTALLED AT THE TIME AN OCCUPANT MOVES
 INTO ASPACE.
  
 14)NOTE: PLEASE SHOW ALL RECEPTS WHICH
 ARE REQUIRED TO BE GFI/GFI PROTECTED.
 210.8
  
 15)NOTE: PLEASE SEE BOTH SETS OF PLANS
 SUBMITTED ARE NOT SIGNED, DATED OR
 SEALED BY THE ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
 THIS IS REQUIRED OF ALL TRADES AND ALL
 REVIEW WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESIATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  