| 2005-08-17 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY (CHANGE OF USE).THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION. 233-5025 |
| | |
| | 3.)THE VALUE APPEARS TOO LOW.PROVIDE |
| | A REASONABLE VALUE OR AN ESTIMATE USING |
| | MARSHALL & SWIFT WILL BE DONE FOR YOU. |
| | |
| | 4.)THIS IS A CHANGE IN OCCUPANCY, |
| | FBC3401.2.2.1.SOME COMMENTS MAY RELATE |
| | TO THIS CODE SECTION. |
| | |
| | 5.)THIS IS AN OVER 50% IMPROVEMENT, |
| | FBC3401.7.2.6.SOME COMMENTS MAY RELATE |
| | TO THIS CODE SECTION. |
| | |
| | 6.)FBC3401.2.2.2, PROVIDE |
| | CERTIFICATION OF THE FLOOR LOADING. |
| | |
| | 7.)THE PLANS ARE TO BE SIGNED, SEALED, |
| | AND DATED ORIGINALS, FAC61G1-16.003. |
| | |
| | 8.)SHEET ASP-1 DECLARES: |
| | |
| | A. CLASSIFICATION AS TYPE B ? THIS IS A |
| | MIXED OCCUPANCY (LIVE/WORK), SEE FBC |
| | CHAPTER 3. |
| | |
| | B. CONSTRUCTION TYPE V SFBC2001. |
| | GOVERNING CODE IS FBC2001. |
| | |
| | 9.)PROVIDE A SURVEY OF THIS PROPERTY. |
| | |
| | 10.)PROVIDE AREA CALCULATIONS FOR THE |
| | FIRST FLOOR AND SECOND FLOOR SO THAT |
| | CODE COMPLIANCE CAN BE DETERMINED. |
| | |
| | 11.)THE PLANS SUBMITTED HAVE NOTES AND |
| | CALCULATIONS ON SHEET A2 WHICH WERE HAND |
| | WRITTEN.IF YOU WANT FOR THESE NOTES |
| | AND CALCULATIONS TO BE A PART OF THIS |
| | PLAN, LABEL EACH ONE SO THAT IT IS CLEAR |
| | AS TO WHAT IT APPLIES TO (OR REMOVE FROM |
| | THE PLAN). |
| | |
| | 12.)THE STAIRWAY FROM THE FIRST TO |
| | SECOND FLOOR IS TO BE PROTECTED, |
| | FBC1006.1. |
| | |
| | 13.)PROVIDE AN ASSEMBLY OR CALCULATED |
| | FIRE RESISTANCE (PROVIDING CALCULATIONS |
| | TO SHOW COMPLIANCE FBC709) FOR THE |
| | OCCUPANCY SEPARATION BETWEEN THE FIRST |
| | AND SECOND FLOOR. |
| | |
| | 14.)SEE FBC TABLE 600 AND SHOW |
| | COMPLIANCE FOR THE NORTH WALL WHICH IS |
| | LESS THAN 3? FROM THE PROPERTY LINE. |
| | |
| | 15.)MEANS OF EGRESS (FROM SECOND |
| | FLOOR) CANNOT BE THROUGH ADJACENT TENANT |
| | SPACE, FBC1001.1.3. |
| | |
| | 16.)FOR THE RAMP BETWEEN THE WAITING |
| | AREA AND SECRETARIES? AREA PROVIDE THE |
| | RISE AND THE WIDTH.SEE FBC11-4.8.5, |
| | FBC11-4.8.3, SEE EXCEPTION. |
| | |
| | 17.)PROVIDE THE RAMP WIDTH ADJACENT TO |
| | WAITING/RECEPTION AREA.THE WIDTH WAS |
| | PROVIDED ON ONE SIDE ONLY. |
| | |
| | 18.)SHOW THE ACCESSIBLE ROUTE, |
| | FBC11-11-4.1.2(1).IT APPEARS TO BE |
| | FROM 17TH STREET TO THE RAMP, PLEASE |
| | NOTE CONSTRUCTION AND SLOPE ON THE PLAN. |
| | ACCESSIBLE PARKING NOT SHOWN. |
| | |
| | 19.)NOTE THE MAXIMUM RAMP SLOPE ON THE |
| | PLAN FBC11-4.8.2 FOR THE FRONT RAMP.IF |
| | THE STAIR RISERS ARE 7? HIGH, THE SLOPE |
| | OF THE RAMP EXCEEDS 1:12. |
| | |
| | 20.)NOTE THE LANDING DIMENSION AT THE |
| | TOP AND BOTTOM OF EACH RAMP, |
| | FBC11-4.8.4. |
| | |
| | 21.)WHERE THE RAMP CHANGES DIRECTION, |
| | MINIMUM LANDING SIZE IS 60X60 (48X48 IS |
| | SHOWN), FBC11-4.8.3(3). |
| | |
| | 22.)SHOW MANEUVERING CLEARANCE FOR THE |
| | DOOR AT THE RAMP, FBC11-4.8.3(4), |
| | 11-4.13.6, CHAPTER 11 FIGURE 25. |
| | |
| | 23.)A HANDRAIL IS REQUIRED ON BOTH |
| | SIDES OF THE RAMP (FRONT), 11-4.8.5(1). |
| | ALSO SEE FBC11-4.8.5(2) IN REGARDS TO |
| | THE EXTENSION REQUIRED AT THE TOP. |
| | |
| | 24.)PROVIDE A DETAIL FOR THE HANDRAILS |
| | SHOWING DIMENSIONS AND HEIGHT FOR BOTH |
| | THE RAMP HANDRAIL AND STAIR HANDRAIL |
| | FBC11-4.8.5, 11-4.9.4. |
| | |
| | 25.)EDGE PROTECTION REQUIRED FOR THE |
| | EXTERIOR RAMPS, FBC11-4.8.7. |
| | |
| | 26.)PROVIDE A STAIR DETAIL, FBC11-4.9, |
| | FBC1007 FOR BOTH STAIRS. |
| | |
| | 27.)THE HANDRAIL EXTENSIONS FOR BOTH |
| | STAIRS ARE TO COMPLY WITH FBC11-4.9.4. |
| | PLEASE PROVIDE A DETAIL SHOWING ALL |
| | DIMENSIONS. |
| | |
| | 28.)PROVIDE A BACKING DETAIL FOR THE |
| | GRAB BARS. |
| | |
| | 29.)DOOR 111A APPEARS TO SWING INTO |
| | THE CLEAR FLOOR SPACE REQUIRED FOR THE |
| | SINK, FBC11-4.22.2. |
| | |
| | 30.)PROVIDE A DETAIL FOR THE BREAK |
| | ROOM SINK TO COMPLY WITH FBC11-4.24. |
| | |
| | 31.)BEDROOMS ARE TO COMPLY WITH |
| | FBC1005.4, EMERGENCY EGRESS.NOTE |
| | WINDOW SIZE AND TYPE ON THE PLAN TO SHOW |
| | COMPLIANCE. |
| | |
| | 32.)SAFETY GLASS REQUIRED AT THE TUB |
| | FBC2405.1. |
| | |
| | 33.)SHOW 2ND FLOOR BATHROOM DOOR SIZE, |
| | FBC11-11(1). |
| | |
| | 34.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO THE |
| | NOAS PROVIDED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 35.)PROVIDE LEGIBLE NOAS. THEY MAY BE |
| | AVAILABLE AT WWW.FLORIDABUILDNG.ORG OR |
| | WWW.MIAMIDADE.GOV (FIND A DEPARTMENT, |
| | BUILDING CODE COMPLIANCE, PRODUCT |
| | CONTROL SEARCH). |
| | |
| | 36.)NON IMPACT GLAZED DOOR PRODUCT |
| | APPROVALS WERE SUBMITTED.PLEASE SEE |
| | ATTACHED POLICY IN REGARDS TO MISSILE |
| | IMPACT PROTECTION, ITEM #13. |
| | |
| | 37.)FOR THE GAF BUILT UP ROOF, |
| | INDICATE WHICH APPROVED ASSEMBLY YOU ARE |
| | USING. |
| | |
| | 38.)FOR THE METAL ROOF PANELS, PROVIDE |
| | DESIGN PRESSURES AND SEE PRODUCT |
| | LIMITATION #7. |
| | |
| | 39.)ANY PRODUCT APPROVALS NOT REVIEWED |
| | PRIOR TO PERMIT ISSUANCE WILL REQUIRE |
| | SEPARATE PERMITS. |
| | |
| | |
| | |
| | |