| 2006-02-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05070720 |
| | ADD: 8583 EGRET MEADOW LANE |
| | CONT:RHR POOLS |
| | TEL: (772)263-9132 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | POOL REVIEW |
| | ACTION: REVIEWD |
| | BUILDING PROVISO: |
| | |
| | TO BE IN PLACE AT TIME OF C. O.: |
| | |
| | 1)424.2.17.1.8 ACCESS GATES, WHEN |
| | PROVIDED, SHALL BE SELF-CLOSING AND |
| | SHALL COMPLY WITH THE REQUIREMENTS OF |
| | ?424.2.17.1.1 THROUGH 424.2.17.1.7 AND |
| | SHALL BE EQUIPPED WITH A SELF-LATCHING |
| | LOCKING DEVICE LOCATED ON THE POOL SIDE |
| | OF THE GATE.WHERE THE DEVICE RELEASE |
| | IS LOCATED NO LESS THAN 54 INCHES FROM |
| | THE BOTTOM OF THE GATE, THE DEVICE |
| | RELEASE MECHANISM MAY BE LOCATED ON |
| | EITHER SIDE OF THE GATE AND SO PLACED |
| | THAT IT CANNOT BE REACHED BY A YOUNG |
| | CHILD OVER THE TOP OR THROUGH ANY |
| | OPENING OR GAP FROM THE OUTSIDE.GATES |
| | THAT PROVIDE ACCESS TO THE SWIMMING POOL |
| | MUST OPEN OUTWARD AWAY FROM THE POOL. |
| | THE GATES AND BARRIER SHALL HAVE NO |
| | OPENING GREATER THAN 1/2 INCH WITHIN 18 |
| | INCHES OF THE RELEASE MECHANISM. |
| | |
| | 2) 424.2.17.1.9 ALL DOORS AND WINDOWS |
| | PROVIDING DIRECT ACCESS FROM THE HOME TO |
| | THE POOL SHALL BE EQUIPPED WITH AN EXIT |
| | ALARM COMPLYING WITH UL 2017 THAT HAS A |
| | MINIMUM SOUND PRESSURE RATING OF 85 DB A |
| | AT 10 FEET AND IS EITHER HARDWIRED OR OF |
| | THE PLUG-IN TYPE.THE EXIT ALARM SHALL |
| | PRO-DUCE A CONTINUOUS AUDIBLE WARNING |
| | WHEN THE DOOR AND ITS SCREEN ARE OPENED. |
| | THE ALARM SHALL SOUND IMMEDIATELY |
| | AFTER THE DOOR IS OPENED AND BE CAPABLE |
| | OF BEING HEARD THROUGHOUT THE HOUSE |
| | DURING NORMAL HOUSEHOLD ACTIVITIES.THE |
| | ALARM SHALL BE EQUIPPED WITH A MANUAL |
| | MEANS TO TEMPORARILY DEACTIVATE THE |
| | ALARM FOR A SINGLE OPENING.SUCH |
| | DEACTIVATION SHALL LAST NO MORE THAN 15 |
| | SECONDS.THE DEACTIVATION SWITCH SHALL |
| | BE LOCATED AT LEAST 54 INCHES ABOVE THE |
| | THRESH-OLD OF THE DOOR.SEPARATE ALARMS |
| | ARE NOT REQUIRED FOR EACH DOOR OR WINDOW |
| | IF SENSORS WIRED TO A CENTRAL ALARM |
| | SOUND WHEN CONTACT IS BROKEN AT ANY |
| | OPENING. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |