Plan Review Notes
Plan Review Notes For Permit 05070701
Permit Number 05070701
Review Stop P
Sequence Number 2
Notes
Date Text
2005-12-06 00:00:00PASSED/PROVISO
  
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.