| Plan Review Notes For Permit 05070701 |
| Permit Number |
05070701 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-12-05 00:00:00 | ** PLANS REDLINED 2ND REVIEW ** | | | | | | PLEASE SEE PLANS WERE INITIALED BY | | | ENGINEER TO PLACE SD'S ON BATH CIRCUIT, | | | HOWEVER 210.11C3 DOES NOT PERMIT ANY | | | OTHER DEVICES ON BATH CIRCUIT. | | | SD'S SHOULD BE ON BEDRM CIRCUIT OR ARC | | | FAULT CIRCUIT PER 210.12 |
|