| Plan Review Notes For Permit 05070701 |
| Permit Number |
05070701 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. BOTH SETS OF PLANS TO BE SIGNED, | | | SEALED, AND DATED, AND THE CERTIFICATE | | | OF AUTHORIZATION FOR THE ARCHITECT CAN | | | NOT BE VERIFIED ON DBPR WEBSITE. SECTION | | | 104.2.2. FAC61G1-16.004 & FS 481.2055 | | | 2. SHT P-1.1 WATER RISER DIAGRAMS, AIR | | | CHAMBERS ARE NOT APPROVED AND SHALL BE | | | DELETED FROM WATER RISER DIAGRAMS. | | | SECTION 604.9 AND PDI-WH 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|