| Plan Review Notes For Permit 05070701 |
| Permit Number |
05070701 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-16 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | | REGARDING FS AND FAC REQUIREMENTS FOR | | | PLANS. | | | | | | 2) PLEASE INDICATE THE OCCUPANT | | | CLASSIFICATION FOR NEW PROJECT AND | | | EXISTING USE OF BUILDING. | | | | | | 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GUARDS. | | | | | | 4) DOOR SWING FROM SECOND FLOOR STORAGE | | | ROOM APPEARS TO OBSTRUCT GREATER THAN | | | 1/2 DISTANCE OF THE EXIT ACCESS. | | | | | | 5) PLANS ILLUSTRATE THAT THE FIRE ALARM | | | PANEL IS TO REMAIN. SEPARATE SHOP | | | DRAWINGS AND PERMIT ARE REQUIRED FOR | | | FIRE ALARM REMODEL. | | | | | | 6) ADDRESS IF NOT ALREADY PROVIDED SHALL | | | BE ON BUILDING AT LEAST 6" IN HEIGHT AND | | | CONTRASTING TO BACKGROUND. | | | | | | 7) PLEASE SHOW LOCATION OF 2A-10B | | | RATED FIRE EXTINGUISHERS TO BE MOUNTED | | | TO SATISFY THE 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | 8) PLEASE EXPLAIN GATE OPERATION ON EAST | | | SIDE OF BUILDING THAT APPEARS TO BE | | | COMPONENT OF MEANS OF EGRESS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | |
|