Plan Review Notes
Plan Review Notes For Permit 05070701
Permit Number 05070701
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-28 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS RENOVATION OF ENTIRE BLDG,
 HOWEVER ELECTRICAL PLANS NOT SUBMITTED
 FOR ENTIRE BLDG? PLEASE SEE MISSING
 UNITS 1-8.
 PLEASE SEE THIS ALSO SEEMS TO BE A
 CHANGE IN OCCUPANCY CLASSIFICATION,
 THERFORE ALL ELECTRICAL ETC WILL BE
 REQUIRED TO BE BROUGHT UP TO CODE.
  
 2)NOTE: PLEASE SEE BOTH SETS OF PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND
 SEALED BY SAID ENGINEER. PLEASE ALSO SEE
 ARCHITECTUAL SHEETS.
 PLEASE SEE PRINT OUT FROM DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION
 (DBPR) WHICH SHOWS FIRM LICENSE NUMBER
 AS SHOWN ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. PLEASE SEE THE LICENSE NUMBER AS
 SHOWN DOES NOT SEEM TO CORRELATE WITH
 STATE PRINT FOR THIS FIRM. PLEASE
 VERIFY.
 PLEASE SEE FAC 61G15-23.002,
 61G1-16.004, FS 471.025, AND 481.221 FOR
 THE ABOVE COMMENTS.
 PLEASE SEE THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENTS ARE MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS FOR ALL NEW AND FOR ALL EXISTING
 BEING BROUGHT UP TO CODE. ITEMS SHOWN AS
 EXISTING WILL BE REQUIRED TO BE BROUGHT
 UP TO CODE FOR ALL GROUND FAULT, ARC
 FAULT, BRANCH CIRCUIT SIZING ETC.
 210.52,210.11,220.16 ETC.
 215.5
 PLEASE SEE FUTHER COMMENTS FOR 2002 NEC.
  
 4)NOTE: PLEASE SEE 210.52B, 210.11C1 AND
 220.16 FOR MIN OF TWO SMALL APPLIANCE
 CIRCUITS.
 PLEASE ADJSUT PANEL SCHEDULES, LOAD
 CALCULATIONS ETC.
  
 5)NOTE: PLEASE SEE 210.52C1-5 FOR
 RECEPTS TO MEET KITCHEN COUNTERSPACE.
 PLEASE SEE MISSING GFI'S AS REQUIRED.
  
 6)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 SHOWN AS GFI/GFI PROTECTED.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED UNDER 210.52 2',6',12 RULE.
 PLEASE EITHER SHOW AS NEW OR EXISTING TO
 NEW CIRCUITING.
  
 8)NOTE: PLEASE LIST ALL THE ARC FAULT
 REQUIRED CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE PLANS ARE NOTED FOR ARC FAULT
 PROTECTION FOR "RECEPT OUTLETS" AND
 SD'S??
 PLEASE SEE 2002 NEC 210.12, "ALL
 OUTLETS" ARE REQUIRED TO HAVE ARC FAULT
 PROTECTION, WHICH WOULD INCLUDE ALL
 LIGHTING, FANS ETC.
 PLEASE SEE NOTE ABOVE ARC FAULT NOTE
 MENTIONS FOR SD'S TO WIRED INTO KITCHEN
 LIGHTING CIRCUIT? THIS IS OK, HOWEVER
 ALL KITCHEN LIGHTING CIRCUITS WOULD ALSO
 BE REQUIRED TO BE ARC FAULT. PLEASE ALSO
 SEE CIRCUITING AS SHOWN ON PLANS AT
 PRESENT TIME DOES NOT SHOWS SD'S BEING
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT?
  
 9)NOTE: PLEASE SHOW DESIGNATIONS ON ALL
 PANELS ON PLANS.
 PLEASE KNOW DEPENDING ON OCCUPANCY AND
 USEAGE, PANELS MAY BE REQUIRED IN SPACE
 OF APT UNIT FOR ACCESS TO BREAKERS FOR
 TENANT OCCUPANTS.
 240.24A,B ,230.72C
  
 10)NOTE: PLEASE SEE 230.79 FOR MIN
 PANEL/SERVICE FOR EACH UNIT OF THIS
 MULTI-FAMILY BLDG. PLEASE SEE A MIN OF
 60A'S OR MORE SHALL BE PROVIDED FOR
 EACH.
  
 11)NOTE: PLEASE SHOW ALL HOUSE
 CIRCUITING ON PLANS AND CORRELATE WITH
 HOUSE PANELS TO BE SUBMITTED.
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. 215.3,230.42 ETC.
  
 12)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE FOR CLOSET LTS AND TYPE OF
 FIXTURES.
  
 13)NOTE: PLEASE SHOW "DINING AREA"
 DESIGNATIONS ON PLANS IN ORDER TO VERIFY
 CIRCUITING.
 215.5
  
 14)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL ELECTRICAL DEVICES TO MEETCHAPTER
 5 OF THE FAIR HOUSING ACT REGULATIONS,
 24 CFR 100.205.
 DEVICES ABOVE KTICHEN COUNTERSPACE SHALL
 NOT BE HIGHER THAN 46"
  
 15)NOTE: PLEASE CORRELATE LOAD SHOWN ON
 LOAD CALCULATIONS FOR NEW LOAD AND LOAD
 SHOWN ON RISER DIAGRMA ON NEW 400A
 DISCONNECT FUSED AT 300A'S.
 215.5
  
 16)NOTE: PLEASE CLARIFY EXISTING SERVICE
 DISCONNECTS/PANELS SHOWN AS CIRCUIT
 BRKR, WITH FUSES??
 215.5
  
 17)NOTE: PLEASE SEE CHAPTER 34 OF THE
 FBC FOR RENOVATIONS TO EXSITING BLDGS.
  
 18)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FORCOMMENTS FOR BLDG PERMIT
 APPLICATION VALUATION.
 PLEASE SEE BUILDING VALUATION IS BASED
 ON ALL LABOR AND MATERIALS, EVNE IF
 MATERIALS ARE OWNER SUPPLIED.
 104.6.5
  
 PLEASE SEE ANY COMMENTS FORM OTHER
 TRADESWHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE PLANS MAY HAVE ADDITIONAL
 COMMENTS DUE TO PLANS NOT BEING COMPLETE
 AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INOT COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]