2005-08-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MAY BE DUE AND MUST BE
 PAID TO PALM BEACH COUNTY (IF IT IS
 DETERMINED THAT THERE HAS BEEN A CHANGE
 OF USE).THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 3.)THIS IS AN OVER 50% IMPROVEMENT.
 SOME COMMENTS MAY BE DUE TO THE
 REQUIREMENTS OF FBC3401.7.2.6.
  
 4.)I WAS UNABLE TO LOCATE CHISHOLM
 ARCHITECTS, INC. AAC001962 ON THE STATE
 WEBSITE.SEE FAC61G1-16.PLEASE
 ADDRESS.
  
 5.)THE SURVEY IS REQUIRED TO CONTAIN
 THE LANGUAGE IN FAC61G17-6.003(2)(E) IN
 REGARDS TO THE SURVEY NOT BEING VALID
 WITHOUT A SEAL.ONLY ONE ORIGINAL
 SUBMITTED.BOTH COPIES REQUIRED TO BE
 ORIGINAL.
  
 6.)FAC61G17-6.003(2)(B) REQUIRES THAT
 THE TYPE OF SURVEY BE STATED AS DEFINED
 IN RULE 61G17-6.002(8)(A)-(K).
 ALTA/ACSM LAND TITLE SURVEY IS NOT ONE
 OF THE SURVEY TYPES.ALSO SEE
 FAC61G17-6.0052.THIS DOES NOT APPEAR
 TO FALL UNDER THIS EXCEPTION.
  
 7.)FAC61G17-6.003(2)(C), THE TITLE
 BLOCK IS TO INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE FIRM.
  
 8.)THE JURISDICTION FOR THE ENERGY
 CALCS IS 604700, FBC13 APPENDIX A.
 INCLUDE ON THE ENERGY CALCS AS REQUIRED.
  
 9.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 10.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING USE AND PROPOSED USE.
 DECLARE AN OCCUPANCY SUBCLASSIFICATION
 FBC311 SO THAT CODE COMPLIANCE WITH
 FBC11, ACCESSIBILITY OR FAIR HOUSING CAN
 BE DETERMINED AS APPLICABLE.
  
 11.)SHOW THE ELEVATIONS AT THE DOORS.
 THERE APPEARS TO BE A CHANGE IN
 ELEVATION, NOTE THE DIMENSION FOR
 ACCESSIBLE UNITS OR UNITS COMPLYING WITH
 FAIR HOUSING.
  
 12.)THE CABINET DETAILS ON A3.2 SHOW
 DOORS ON THE CABINETS.SINKS REQUIRED
 TO BE ACCESSIBLE ARE TO COMPLY WITH
 FBC11-4.24.THERE IS REFERENCE TO AN
 ADA UNIT.NOTE THAT AT THIS TIME
 COMPLIANCE WITH FBC11 HAS NOT YET BEEN
 DETERMINED.
  
 13.)A1-1, ITEM 12, EITHER SPECIFY AN
 APPROVED ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 14.)SHOW TENANT SEPARATION, HORIZONTAL
 AND VERTICAL, FBC704.3.
  
 15.)INDICATE PROTECTION REQUIRED BY
 FBC1006.2.4.
  
 16.)DECLARE TOTAL SF, DECLARE A
 BUILDING TYPE FBC CHAPTER 6.
  
 17.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING STAIRS (CONSTRUCTION, TREAD
 AND RISER DIMENSION, WIDTH).SEE
 FBC1001.3.
  
 18.)PROVIDE BALCONY DIMENSIONS,
 LANDING DIMENSION.
  
 19.)THE STAIR PLAN A3.2 IS NOT CLEAR.
 THE RAILING DETAILS SHOW EXTENSIONS AT
 THE TOP AND BOTTOM, BUT THE PLAN AND
 A1.2 SHOWS EXTENSIONS ON THE TOP ONLY.
  
 20.)PROVIDE PRODUCT APPROVALS FOR
 DOORS AND WINDOWS.NOTE THAT THE PLANS
 SPECIFY IMPACT GLASS.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 FOR THOSE ITEMS.
  
 21.)THE ENERGY CALCS ON ONE SET HAVE A
 PHOTOCOPY OF A SEAL.DOCUMENTS PREPARED
 BY A DESIGN PROFESSIONAL SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS, FAC61G1-16.003,004 AND
 FAC61G15-23.002.
  
 22.)THE ASBESTOS REPORT PREPARED BY
 GAUDET AND ASSOCIATES IS TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002
 AND TO BE SIGNED, SEALED, DATED
 ORIGINALS.