| 2005-08-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MAY BE DUE AND MUST BE |
| | PAID TO PALM BEACH COUNTY (IF IT IS |
| | DETERMINED THAT THERE HAS BEEN A CHANGE |
| | OF USE).THE PLANS MUST BE STAMPED AND |
| | THE RECEIPT ATTACHED TO THE APPLICATION. |
| | 233-5025 |
| | |
| | 3.)THIS IS AN OVER 50% IMPROVEMENT. |
| | SOME COMMENTS MAY BE DUE TO THE |
| | REQUIREMENTS OF FBC3401.7.2.6. |
| | |
| | 4.)I WAS UNABLE TO LOCATE CHISHOLM |
| | ARCHITECTS, INC. AAC001962 ON THE STATE |
| | WEBSITE.SEE FAC61G1-16.PLEASE |
| | ADDRESS. |
| | |
| | 5.)THE SURVEY IS REQUIRED TO CONTAIN |
| | THE LANGUAGE IN FAC61G17-6.003(2)(E) IN |
| | REGARDS TO THE SURVEY NOT BEING VALID |
| | WITHOUT A SEAL.ONLY ONE ORIGINAL |
| | SUBMITTED.BOTH COPIES REQUIRED TO BE |
| | ORIGINAL. |
| | |
| | 6.)FAC61G17-6.003(2)(B) REQUIRES THAT |
| | THE TYPE OF SURVEY BE STATED AS DEFINED |
| | IN RULE 61G17-6.002(8)(A)-(K). |
| | ALTA/ACSM LAND TITLE SURVEY IS NOT ONE |
| | OF THE SURVEY TYPES.ALSO SEE |
| | FAC61G17-6.0052.THIS DOES NOT APPEAR |
| | TO FALL UNDER THIS EXCEPTION. |
| | |
| | 7.)FAC61G17-6.003(2)(C), THE TITLE |
| | BLOCK IS TO INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE FIRM. |
| | |
| | 8.)THE JURISDICTION FOR THE ENERGY |
| | CALCS IS 604700, FBC13 APPENDIX A. |
| | INCLUDE ON THE ENERGY CALCS AS REQUIRED. |
| | |
| | 9.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS. |
| | |
| | 10.)PROVIDE INFORMATION IN REGARDS TO |
| | THE EXISTING USE AND PROPOSED USE. |
| | DECLARE AN OCCUPANCY SUBCLASSIFICATION |
| | FBC311 SO THAT CODE COMPLIANCE WITH |
| | FBC11, ACCESSIBILITY OR FAIR HOUSING CAN |
| | BE DETERMINED AS APPLICABLE. |
| | |
| | 11.)SHOW THE ELEVATIONS AT THE DOORS. |
| | THERE APPEARS TO BE A CHANGE IN |
| | ELEVATION, NOTE THE DIMENSION FOR |
| | ACCESSIBLE UNITS OR UNITS COMPLYING WITH |
| | FAIR HOUSING. |
| | |
| | 12.)THE CABINET DETAILS ON A3.2 SHOW |
| | DOORS ON THE CABINETS.SINKS REQUIRED |
| | TO BE ACCESSIBLE ARE TO COMPLY WITH |
| | FBC11-4.24.THERE IS REFERENCE TO AN |
| | ADA UNIT.NOTE THAT AT THIS TIME |
| | COMPLIANCE WITH FBC11 HAS NOT YET BEEN |
| | DETERMINED. |
| | |
| | 13.)A1-1, ITEM 12, EITHER SPECIFY AN |
| | APPROVED ASSEMBLY OR CALCULATED FIRE |
| | RESISTANCE FBC709. |
| | |
| | 14.)SHOW TENANT SEPARATION, HORIZONTAL |
| | AND VERTICAL, FBC704.3. |
| | |
| | 15.)INDICATE PROTECTION REQUIRED BY |
| | FBC1006.2.4. |
| | |
| | 16.)DECLARE TOTAL SF, DECLARE A |
| | BUILDING TYPE FBC CHAPTER 6. |
| | |
| | 17.)PROVIDE INFORMATION IN REGARDS TO |
| | THE EXISTING STAIRS (CONSTRUCTION, TREAD |
| | AND RISER DIMENSION, WIDTH).SEE |
| | FBC1001.3. |
| | |
| | 18.)PROVIDE BALCONY DIMENSIONS, |
| | LANDING DIMENSION. |
| | |
| | 19.)THE STAIR PLAN A3.2 IS NOT CLEAR. |
| | THE RAILING DETAILS SHOW EXTENSIONS AT |
| | THE TOP AND BOTTOM, BUT THE PLAN AND |
| | A1.2 SHOWS EXTENSIONS ON THE TOP ONLY. |
| | |
| | 20.)PROVIDE PRODUCT APPROVALS FOR |
| | DOORS AND WINDOWS.NOTE THAT THE PLANS |
| | SPECIFY IMPACT GLASS.ANY PRODUCT |
| | APPROVALS NOT REVIEWED PRIOR TO PERMIT |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS |
| | FOR THOSE ITEMS. |
| | |
| | 21.)THE ENERGY CALCS ON ONE SET HAVE A |
| | PHOTOCOPY OF A SEAL.DOCUMENTS PREPARED |
| | BY A DESIGN PROFESSIONAL SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS, FAC61G1-16.003,004 AND |
| | FAC61G15-23.002. |
| | |
| | 22.)THE ASBESTOS REPORT PREPARED BY |
| | GAUDET AND ASSOCIATES IS TO HAVE ALL |
| | INFORMATION REQUIRED BY FAC61G15-23.002 |
| | AND TO BE SIGNED, SEALED, DATED |
| | ORIGINALS. |