| 2005-08-19 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- PACKAGE SUBMITTED IS MISSING THE |
| | PERMIT APPLICATION. |
| | |
| | 2- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. |
| | |
| | B) CLEARLY MARK ON SHUTTER DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS AND TYPE OF |
| | ANCHOR AND SPACING TO BE USED ACCORDING |
| | TO THE DESIGN PRESSURES, EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO (CONCRETE |
| | BLOCK, CONCRETE OR WOOD). |
| | |
| | 3- STOREFRONT WAS CHANGED FROM ONE BIG |
| | PANEL TO 3 PANELS MULLED TOGETHER. |
| | PROVIDE/REVISETHE FOLLOWING |
| | INFORMATION: |
| | |
| | A) ENGINEER OF RECORD TO REVISE THE BUCK |
| | SIZE. 1X3 BUCK SPECIFIED ON PLANS |
| | DOESN'T WORK. NEED BUCK TO PROVIDE FULL |
| | STOREFRONT FRAME SUPPORT AS REQUIRED BY |
| | SEC. 1707.4.4.2 FBC 2001. SEE STOREFRONT |
| | PRODUCT APPROVAL FOR SIZE OF STOREFRONT |
| | TO BE SUPPORTED. |
| | |
| | B) ENGINEER OF RECORD NOTES BELOW |
| | ELEVATION CALLS FOR ATTACHMENT OF FIXED |
| | GLASS WITH 3/16" TAPCONS. REVISE SIZE. |
| | SEE STOREFRONT PRODUCT APPROVAL FOR |
| | CORRECT TAPCON SIZE AND SPACING. |
| | |
| | C) CLEARLY SPECIFY STOREFRONT SIZE TO BE |
| | INSTALLED IN THE LARGE OPENING. (RIGHT |
| | HAND SIDE OPENING). |
| | |
| | 4- FLOOR PLAN AND ELEVATION DON'T MATCH. |
| | FLOOR PLAN CALLS FOR EXISTING SINGLE |
| | DOOR, WHILE ELEVATIONS SHOWS SINGLE DOOR |
| | WITH SIDELITES. REVISE AS REQUIRED. |
| | PERMIT APPLICATION IS FOR WINDOWS ONLY. |
| | |
| | 5- ENGINEER TO PROVIDE CALCULATIONS FOR |
| | THE OPENINGS DESIGN PRESSURES. THEY |
| | DON'T MATCH TABLE 1606.2B FBC 2001. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 6- CLARIFY SCOPE OF WORK NOTE #2. ARE |
| | OPENINGS REINFORCED AT BOTH SIDES TO |
| | RECEIVE THE NEW STOREFRONT OR NOT. NOTE |
| | SAYS OPENINGS WERE BLOCKED UP W/CBS. ARE |
| | THEY HOLLOW CORE OR CELL FILLED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7- CLARIFY WHAT ARE THE FLORIDA BUILDING |
| | CODE TABLE COPIES FOR?. WHO PREPARED THE |
| | INTERPOLATED VALUES?. WHY ARE THERE |
| | THREE UNITS IF THERE ARE ONLY TO NEW |
| | STOREFRONTS TO BE PROTECTED. |
| | |
| | 8- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 9- CONTRACTOR NEEDS TO UPDATE INSURANCE |
| | AND WORKERS COMP. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |